47DR OPERATING MANUAL EM-9509-B Rev.7
17. SETTING BURNOUT
Burnout is a function to provide a fail-safe condition for equipment and devices on site by providing max. or min. output
when input is abnormal, disconnection of a wire, for instance. Burnout includes upscale burnout ‘H’ operating toward stop-
ping heating (max. output) and downscale burnout ‘L’ operating toward maintaining heating (min. output) in detecting the
input disconnection. When the unit detects the burnout, it indicates ‘B.ERR’. The default is upscale burnout.
IMPORTANT
Do not change the burnout setting while ‘B.ERR’ is indicated.
17.1 OPERATING PROCEDURE
NOTE
The following figures are display examples. The displays
depend on the specifications and settings.
1
Hold down Alarm/
↓
and Init/
↑
buttons at once for 3 seconds or
more to move on to Advanced Setting Mode.
• The averaging type is indicated.
• The SD indicates ‘AVE-TP’.
NOTE
With the I/O option code ‘6’ or ‘A’, the event trigger mode is indicated (‘EVENT’ on the SD).
2
Press Alarm/
↓
or Init/
↑
button to go to the burnout setting.
• The burnout is indicated.
• The SD indicates ‘BURNOUT’.
1,2,
4,5
1,2,
4,5
3