M-system 18KJM Скачать руководство пользователя страница 3

CHECKING

  1 ) Terminal wiring: Check that all cables are correctly con-

nected according to the connection diagram.

  2 ) Power input voltage: Check voltage supplied to the rack 

(model: 18KBXx).  For the DC power source, be sure 

that the ripple level is within 10% p-p.

  3 ) Output: Check that the load resistance meets the de-

scribed specifications.

ADJUSTMENT PROCEDURE

This unit is calibrated at the factory with the total resist-
ance input, therefore you do not need any calibration if you 
use the potentiometer’s total resistance.
When you don’t use the total resistance or in case of regular 
calibration, adjust the output as explained in the following.   
Zero and span are adjusted with using the Programming 
Unit (model: PU-2x).
Refer to the Operation Manual for Model PU-2x for expla-
nations how to use the programmer.

 

WARNING ON USE OF THE PROGRAMMING UNIT

• 

Be sure to disconnect the Programming Unit before you 
turn on/off power supply to the unit.

• 

The output signal is held when the Programming Unit is 
connected.  You need to disconnect when confirming cur-
rent output values.

 

HOW TO CALIBRATE THE OUTPUT SIGNAL

Use a signal source and measuring instruments of sufficient 
accuracy level.  Turn the power supply on and warm up for 
more than 10 minutes.
There is no need of adjusting the output 2.

• 

Calibrating the Output Range Proportionally to the 

Actual Input Resistance Range

The output range can be calibrated for input ranges nar-
rower than the total resistance, to match the actual input 
resistance range, by using the linearization table (ITEM 60 
through 91) to compensate unused resistance ranges (See 
the following figures).
If upper and lower overranges need not to be considered, 
only two calibration points will suffice.

X(02)

X(01)

0%

Y(02)

100%

Y(01)

OUTPUT

INPUT

(a), (c) : Unused Resistance

= (Total Resistance – Input Resistance)
(b) : Input Resistance

= Actual Resistance Range

100%

(a)

(b)

(c)

Figure 1. Unused Resistance

X(02)

X(01)

0%

100%

Y(02)

Y(01)

OUTPUT

INPUT

(b)

(b) : Input Resistance

= Actual Resistance Range

Figure 2. Example of Linearization

  1 ) Confirm actual lower-range and upper-range resist-

ance in percentage against the total resistance range 

0 – 100%.

In order to do this, provide actual resistance values and 
confirm them on the Programming Unit (ITEM 05: In-
put Status Monitor in %).

  2 ) Turn the unit into Program mode (ITEM 01).
  3 ) Enable use of the linearization table (ITEM 10: Pm-2 : 

curved).

  4 ) Set the lower-range input in % at ITEM 60.
  5 ) Set the lower-range output in %, usually ‘0’ (zero), at 

ITEM 61.

  6 ) Set the upper-range input in % at ITEM 62.
  7 ) Set the upper-range output in %, usually ‘100’, at ITEM 

63.

Table 1 shows an example of settings when you need to use 
10 – 90% of the total resistance and calibrate this range to 
0 – 100%.

Table 1. Setting Example

[GROUP 01]

ITEM

MDFY.

DATA INPUT

DATA EXAMPLE

01

S

1

MTSW : PRG. MODE

60

P

10.00

X (01) :   10.00

61

P

0.00

Y (01) :     0.00

62

P

90.00

X (02) :   90.00

63

P

100.00

Y (02) : 100.00

Modification Code

S: Modifiable at any time.
P: Modifiable only when the MAINTENANCE SWITCH is in 
the “PRG” mode.

18KJM

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: 

+81(6)6659-8510  E-mail: [email protected]

EM-0465  Rev.1  P. 3 / 5

Содержание 18KJM

Страница 1: ...r supply and input signal for safety ENVIRONMENT Indoor use When heavy dust or metal particles are present in the air install the unit inside proper housing with sufficient ventilation Do not install the unit where it is subjected to continuous vibration Do not subject the unit to physical impact Environmental temperature must be within 5 to 55 C 23 to 131 F with relative humidity within 30 to 90 ...

Страница 2: ...IAGRAM 5 6 1 3 2 Use either of module or external field terminals OUTPUT 2 OUTPUT 1 POWER Module Field Terminals Section A External Field Terminals Section A Section A Field Terminals CONNECTOR OUTPUT 2 PU 2x MODULARJACK 2 3 1 3 2 1 POTENTIOMETER max min TERMINAL ASSIGNMENTS 1 2 3 4 7 8 5 6 18KJM 5 2 55 Minamitsumori Nishinari ku Osaka 557 0063 JAPAN Phone 81 6 6659 8201 Fax 81 6 6659 8510 E mail ...

Страница 3: ...match the actual input resistance range by using the linearization table ITEM 60 through 91 to compensate unused resistance ranges See the following figures If upper and lower overranges need not to be considered only two calibration points will suffice X 02 X 01 0 Y 02 100 Y 01 OUTPUT INPUT a c Unused Resistance Total Resistance Input Resistance b Input Resistance Actual Resistance Range 100 a b ...

Страница 4: ...inearization table ITEM 10 Pm 2 curved in order to activate the settings X nn Input Signal in Y nn Output Signal in X or Y 15 00 to 115 00 15 0 X01 X02 X03 X04 X05 115 Y01 Y02 Y03 Y04 100 Y05 INPUT OUTPUT Figure 3 Linearization Table GROUP 01 ITEM MDFY DATA EXAMPLE 60 P X 01 XXX XX 61 P Y 01 XXX XX 62 P X 02 XXX XX 63 P Y 02 XXX XX 64 P X 03 XXX XX 65 P Y 03 XXX XX 66 P X 04 XXX XX 67 P Y 04 XXX X...

Страница 5: ...ered output is shown LINEARIZATION TABLE 60 P Percentage X 01 XXX XX Input 1 61 P Percentage Y 01 XXX XX Output 1 91 P Percentage Y 16 XXX XX Output 16 Modification Code D No modification writing possible Used only for monitoring reading S Modifiable at any time P Modifiable only when the MAINTENANCE SWITCH is in the PRG mode MAINTENANCE Regular calibration procedure is explained below CALIBRATION...

Отзывы: