P. 2 / 2
EM-0493 Rev.1
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
18KBXH
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Power input voltage: Check voltage across terminals 1
(+) – 2 (–). Use a power source of ripple level 10% p-p or
less.
3) Installation & environment: Check ambient temperature.
Also check that there are no excessive dust particles around.
Check that there is no vibration.
n
CONNECTOR PIN ASSIGNMENT
•
Fujitsu FCN type I/O connector
(Fujitsu FCN-365P40-AU)
Connector Pin Assignment
CN1
: output 1 or input
CN2
: output 2
PIN NO.
ASSIGNMENT
PIN NO.
ASSIGNMENT
A 1
ch. 1 +
B 1
ch. 1 –
A 2
ch. 2 +
B 2
ch. 2 –
A 3
ch. 3 +
B 3
ch. 3 –
A 4
ch. 4 +
B 4
ch. 4 –
A 5
ch. 5 +
B 5
ch. 5 –
A 6
ch. 6 +
B 6
ch. 6 –
A 7
ch. 7 +
B 7
ch. 7 –
A 8
ch. 8 +
B 8
ch. 8 –
A9 – A20, B9 – B20: Unused
Pin assignment is common to both CN1 and CN2.
• Toshiba DCS SAMP1 card use
• Toshiba DCS SAIN1, SAI06, SAO06 card use
Connector Pin Assignment
PIN NO.
ASSIGNMENT
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
ch.1 +
ch.1 –
ch.2 +
ch.2 –
ch.3 +
ch.3 –
ch.4 +
ch.4 –
ch.5 +
ch.5 –
ch.6 +
ch.6 –
ch.7 +
ch.7 –
ch.8 +
ch.8 –
Pin assignment is common to both CN1 and CN2
The signal that is connected to the connector is the input signal
or the output signal 1.
Toshiba DCS SAMP1 uses Panasonic AXM220001. As con-
nector is discontinued, Omron XG4A-2034 is used as an
alternative. (Replace receptacle side.)
1
2
3
4
5
6
7
8
CN1
,
CN2
1
2
3
4
5
6
7
8
Location
Output connector
: HIF3BA-40PA-2.54DS (11)
CN1
: SAMP1
CN2
: SAMP1 for redundancy
18K-RACK LOCATION NO.
SAMP1 INPUT NO.
1
2
3
4
5
6
7
8
CN1
,
CN2
1
2
3
4
5
6
7
8
Location
I / O connector
: Omron XG4A-2034
CN1
: SAIN1, SAI06, SAO06 (ch.1
–
ch.8)
CN2
The input or output 1 is connected to the connector.
18K-RACK LOCATION NO.
SAIN1, SAI06, SAO06 INPUT or OUTPUT NO.
: SAIN1, SAI06, SAO06 (ch.1
–
ch.8)
for redundancy