PROGRAMMABLE ITEMS

The following items can be monitored and programmed.  For detailed explanations, please refer to the Operation Manual for 
Model PU-2x (EM-9255), Section A.

[GROUP 01]

ITEM

MDFY.

DATA INPUT

DISPLAY

CONTENTS

01

S

MAINTENANCE SWITCH (lock command)

0

MTSW: MON.MODE

MONITOR mode: data monitoring only

1

MTSW: PRG.MODE

PROGRAM mode: “P” marked data modifiable

02

P

Alphabets & No.

TG: XXXXXXXXXX

Tag name entry (10 characters max.)

03
05
06

P

D
D

Number (%)
No input
No input

OUTPER XXX.XX
INPPER XXX.XX
INPFRQ XXXXXX

Output status monitor (%) & simulation output
Input status monitor (%)
Input frequency monitor, same unit as selected in ITEM 11

10

P

LINEARIZATION

1

PA-1: straight

Without

2

PA-2: curved

With (ITEM 60 to 91 for data input)

11

P

COARSE FREQUENCY RANGE SELECTION

0
1
2

FRQRNG: 10mHz
FRQRNG: 100mHz
FRQRNG: 1.0Hz

0 – 10 mHz
0 – 100 mHz
0 – 1 Hz

3
4
5

FRQRNG: 10Hz
FRQRNG: 100Hz
FRQRNG: 1.0kHz

0 – 10 Hz
0 – 100 Hz
0 – 1 kHz

6
7

FRQRNG: 10kHz
FRQRNG: 100kHz

0 – 10 kHz
0 – 100 kHz

13

P

Percentage

DRPOUT XXX.XX

Low-end cutout adjustment, 0.00 – 100.00%

14
15

P
P

Actual value
Actual value

SCLLOW XXXXXX
SCLHIG XXXXXX

Input range scaling 0% value
Input range scaling 100% value
Up to 150% of the coarse range selected in ITEM 11.  Use the 
same unit.

18

P

Number

SMPLRATE XXX

Sampling rate modification for irregular pulse input (No. of 
pulses to be counted during one rotation of input flowmeter)
Frequency range ≤ 100 Hz: 1 – 255
Frequency range 0 – 1 kHz: 1 – 25
Frequency range 0 – 10 kHz: 1 – 2

19

P

Percentage

FINZER

Fine zero adjustment
Initial status shows actual bias (%).  When data is entered, out-
put (%) is shown.

20

P

Percentage

FINSPN

Fine span adjustment
Initial status shows actual gain (%).  When data is entered, out-
put (%) is shown.

LINEARIZATION TABLE

60
61

P
P

Percentage
Percentage

X (01) : XXX.XX
Y (01) : XXX.XX

Input 1
Output 1

:
:

91

:
:

P

       :
       :
Percentage

       :
       :
Y (16) : XXX.XX

       :
       :
Output 16

Modification Code

D: No modification (writing) possible.  Used only for monitoring (reading).
S: Modifiable at any time.
P: Modifiable only when the MAINTENANCE SWITCH is in the “PRG” mode.

10JPA