PROGRAMMABLE ITEMS
The following items can be monitored and programmed. For detailed explanations, please refer to the Operation Manual for
Model PU-2x (EM-9255), Section A.
[GROUP 01]
ITEM
MDFY.
DATA INPUT
DISPLAY
CONTENTS
01
S
MAINTENANCE SWITCH (lock command)
0
MTSW: MON.MODE
MONITOR mode: data monitoring only
1
MTSW: PRG.MODE
PROGRAM mode: “P” marked data modifiable
02
P
Alphabets & No.
TG: XXXXXXXXXX
Tag name entry (10 characters max.)
03
05
06
P
D
D
Number (%)
No input
No input
OUTPER XXX.XX
INPPER XXX.XX
INPVAL XXX.XX
Output status monitor (%) & simulation output
Input status monitor (%)
Input status monitor in actual value, same unit as selected in
ITEM 10.
10
TYPE OF TRANSMITTER INPUT
D
11
Fx-1: 5 – 100mV
D
12
Fx-2: 0.05 – 1V
P
13
Fx-3: 0.5 – 10V
P
14
Fx-6: 1 – 5V
D
15
Fx-A: 4 – 20mA
D
16
Fx-H: 10 – 50mA
11
P
COARSE INPUT RANGE SELECTION
Fx-1
(± mV)
Fx-2
(± V)
Fx-3
(± V)
Fx-6/A/H
0
INPRNG: XXXX
5
0.05
0.5
No
Adjustment
Needed
1
INPRNG: XXXX
10
0.10
1.0
2
INPRNG: XXXX
20
0.20
2.0
3
INPRNG: XXXX
50
0.50
5.0
4
INPRNG: XXXX
100
1.00
10.0
14
15
P
P
Actual value
Actual value
SCLLOW XXXXXX
SCLHIG XXXXXX
Input range scaling 0% value
Input range scaling 100% value
Use the same engineering unit as the coarse range selected in
ITEM 11.
19
P
Percentage
FINZER
Fine zero adjustment
Initial status shows actual bias (%). When data is entered, out-
put (%) is shown.
20
P
Percentage
FINSPN
Fine span adjustment
Initial status shows actual gain (%). When data is entered, out-
put (%) is shown.
LINEARIZATION TABLE
60
61
P
P
Percentage
Percentage
X (01) : XXX.XX
Y (01) : XXX.XX
Input 1
Output 1
:
:
91
:
:
P
:
:
Percentage
:
:
Y (16) : XXX.XX
:
:
Output 16
Modification Code
D: No modification (writing) possible. Used only for monitoring (reading).
S: Modifiable at any time.
P: Modifiable only when the MAINTENANCE SWITCH is in the “PRG” mode.