M.K.Plastics AXCL Скачать руководство пользователя страница 7

 
Typical Damper Motor Schematic 

 

For 3 phase, damper motor voltage should be the same between L1 
and L2. For single phase application, disregard L3. *Damper motors 
may be available in 115, 230 and 460 volt models. The damper motor 
nameplate voltage should be verified prior to connection. **A 
transformer may be provided in some installations to correct the 
damper motor voltage to the specified voltage. 

 
Final Installation Steps 

1.  Inspect fasteners and setscrews, particularly fan mounting and bearing fasteners, and tighten according to the 

recommended torque shown in the table Recommended Torque for Setscrews/Bolts. 

2.  Inspect for correct voltage with voltmeter. 
3.  Ensure all accessories are installed. 

 
 

 

Recommended Torque for Setscrews/Bolts (IN/LB) 

  

Operation 

Pre-Start Checks 

1.  Lock out all the primary and secondary power sources. 
2.  Ensure fasteners and setscrews, particularly those used for mounting the fan, are tightened. 
3.  Inspect belt tension and pulley alignment. 
4.  Inspect motor wiring. 
5.  Ensure belt touches only the pulleys. 
6.  Ensure fan and ductwork are clean and free of debris. 
7.  Inspect wheel-to-inlet clearance. The correct wheel-to-inlet clearance is critical to proper fan performance. 
8.  Close and secure all access doors. 
9.  Restore power to the fan. 

 

Start Up 

  Turn the fan on. In variable speed units, set the fan to its lowest speed and inspect for the following: 

1.  Direction of rotation. 
2. Excessive 

vibration. 

3. Unusual 

noise. 

4. Bearing 

noise. 

5.  Improper belt alignment or tension (listen for squealing). 
6.  Improper motor amperage or voltage. 

 

If a problem is discovered, immediately shut the fan off. Lock out all electrical power and check for the cause of the 
trouble. 

See

 Troubleshooting. 

 

 
 
 

 

7

Содержание AXCL

Страница 1: ...Information on special fan application requirements contact M K Plastic s Corporate office at 514 871 9999 Receiving and Inspection Carefully inspect the fan and accessories for any damage and shortag...

Страница 2: ...prevent damaging conditions Personal Safety Disconnect switches are recommended Place the disconnect switch near the fan in order that the power can be swiftly cut off in case of an emergency and in...

Страница 3: ...provide a minimum clearance of between the top plate and the housing 3 Install the adjusting and leveling bolts through the equipment mounting holes until the bolt comes into contact with the spring...

Страница 4: ...ake sure the spring coils are not closed solid Duct Installation Efficient fan performance relies on the proper installation of inlet ducts where factory inlet plenums are not provided For duct inlets...

Страница 5: ...ached For proper tension a deflection of approximately per foot of center distance should be obtained by firmly pressing the belt Refer to Fig 7 3 Lock the motor plate adjustment nuts in place 4 Ensur...

Страница 6: ...nance personnel are provided complete control of the power source Follow the wiring diagram in the disconnect switch and the wiring diagram provided with the motor Correctly label the circuit on the m...

Страница 7: ...eration Pre Start Checks 1 Lock out all the primary and secondary power sources 2 Ensure fasteners and setscrews particularly those used for mounting the fan are tightened 3 Inspect belt tension and p...

Страница 8: ...ry Dirty Daily to 2 weeks Any Speed Any Temperature Extreme Conditions Daily to 2 weeks Inspect springs and rubber isolators for deterioration and replace as needed Inspect for cleanliness Clean exter...

Страница 9: ...section Bearing Replacement The fan bearings are pillow block ball bearings or flange bearing assembly depending on type of fan An emery cloth or file may be needed to remove imperfections in the sha...

Страница 10: ...maximum torque Flange Bearing Replacement Please refer to Fig 11 for the following procedures The fan bearings are housed inside the flange bearing assembly which includes the shaft It is easier and...

Страница 11: ...orn or oily belts Speed too high Incorrect direction of rotation Make sure the fan rotates in same direction as the arrows on the motor or drive belt assembly Bearings need lubrication or replacement...

Страница 12: ...Parts List Fig 12 Inline Fans typical Fig 13 Centrifugal Fans typical 12...

Отзывы: