background image

3

Installation

In order to install the EPC in accordance with national/local code requirements, a qualified electrician 

should  review  &  understand  the  installation  instructions.  Check  voltage  &  current  requirements.  

Verify & lock out circuit breakers on both regular (utility) power & 24 hour emergency generator or 

inverter circuit.  Install a self-adhesive 2" x 3" caution label in each fixture or load controlled by an EPC 

cautioning that the load is supplied from 2 different power sources, normal & emergency.  Review 

wiring diagram & connect wires, one at a time, in accordance with the numeric identification.

Setup/Programming

Turn on Normal/Emergency power sources.

Initial Testing

In order to test that the wires are connected correctly, without any inconvenience to occupants, do 

not turn off regular (utility) power off until you have checked each device as follows:

1)  Check that regular branch circuit breaker is connected & utility power is available.  Green LED on 

If green LED is not lit, check connections & continuity to branch circuit breaker.  If using 3 phase 

sense mode, ensure power is applied to all 3 phases.  If using 1 phase only, connect Orange Brown 

Yellow wires together.

2)  Check that emergency branch circuit breaker is connected & emergency power is available.  Red 

LED should be lit.  If red LED is not lit, check connections & continuity to emergency branch circuit 

breaker.

4)  Emergency Operation Test:  Press and hold test button, dry contact should change position.

Maintenance

No maintenance is required to keep the EPC functional.  However, regular testing should be 

performed when the lamps or ballasts have been replaced or when remodeling has taken place.

Single Line Drawings

Normal/Utility

Power Source

Emergency

Power Source

Neutral

Not Shown

NORMAL

POWER

PANEL

EMERGENCY

POWER

PANEL

UL 1008

Transfer

Switch Or 

Equivalent

EPC-THPH

BMS, Relay

Panel, etc.

Отзывы: