3
Installation
In order to install the EPC in accordance with national/local code requirements, a qualified electrician
should review & understand the installation instructions. Check voltage & current requirements.
Verify & lock out circuit breakers on both regular (utility) power & 24 hour emergency generator or
inverter circuit. Install a self-adhesive 2" x 3" caution label in each fixture or load controlled by an EPC
cautioning that the load is supplied from 2 different power sources, normal & emergency. Review
wiring diagram & connect wires, one at a time, in accordance with the numeric identification.
Setup/Programming
Turn on Normal/Emergency power sources.
Initial Testing
In order to test that the wires are connected correctly, without any inconvenience to occupants, do
not turn off regular (utility) power off until you have checked each device as follows:
1) Check that regular branch circuit breaker is connected & utility power is available. Green LED on
If green LED is not lit, check connections & continuity to branch circuit breaker. If using 3 phase
sense mode, ensure power is applied to all 3 phases. If using 1 phase only, connect Orange Brown
Yellow wires together.
2) Check that emergency branch circuit breaker is connected & emergency power is available. Red
LED should be lit. If red LED is not lit, check connections & continuity to emergency branch circuit
breaker.
4) Emergency Operation Test: Press and hold test button, dry contact should change position.
Maintenance
No maintenance is required to keep the EPC functional. However, regular testing should be
performed when the lamps or ballasts have been replaced or when remodeling has taken place.
Single Line Drawings
Normal/Utility
Power Source
Emergency
Power Source
Neutral
Not Shown
NORMAL
POWER
PANEL
EMERGENCY
POWER
PANEL
UL 1008
Transfer
Switch Or
Equivalent
EPC-THPH
BMS, Relay
Panel, etc.