Multipliers for determining the performance with other indoor sections.
NOTE:
For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
HL19B6021S
AIR TEMP.
ENTERING
OUTDOOR UNIT (°F)
IDCFM
1500
1800
2100
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
65
T.C.
54.1
58.3
57.7
60.2
63.5
56.4
59.7
58.8
61.1
57.5
58.8
61.1
59.8
62.1
51.5
S.C.
54.1
47.7
39.8
38.5
31.0
56.4
50.6
41.7
40.1
28.0
58.8
53.5
43.6
41.7
25.1
KW
3.02
3.02
3.04
3.03
3.06
3.13
3.14
3.14
3.15
2.66
3.24
3.26
3.25
3.26
2.25
75
T.C.
53.0
56.8
56.6
60.2
64.5
55.8
58.4
58.0
61.6
62.1
58.6
60.1
59.4
62.9
59.8
S.C.
53.0
47.3
39.8
38.7
30.7
55.8
51.0
42.5
41.0
30.3
58.6
54.8
45.3
43.3
29.8
KW
3.30
3.33
3.33
3.36
3.39
3.43
3.46
3.45
3.48
3.24
3.55
3.58
3.57
3.60
3.10
85
T.C.
51.9
55.3
55.5
60.3
65.4
55.1
57.2
57.3
62.0
66.8
58.3
59.2
59.0
63.8
68.1
S.C.
51.9
47.0
39.9
38.9
30.4
55.1
51.5
43.4
42.0
32.5
58.3
56.1
46.9
45.0
34.6
KW
3.58
3.64
3.62
3.69
3.71
3.72
3.77
3.75
3.82
3.83
3.86
3.90
3.88
3.94
3.95
95
T.C.
49.7
52.9
52.8
57.9
62.9
52.8
54.8
54.6
59.7
64.5
56.0
56.6
56.3
61.4
66.1
S.C.
49.7
46.1
38.7
38.2
29.7
52.8
50.8
42.2
41.5
31.8
56.0
55.4
45.8
44.8
33.9
KW
4.00
4.05
4.02
4.09
4.11
4.13
4.17
4.15
4.21
4.23
4.26
4.29
4.27
4.34
4.35
105
T.C.
47.6
50.6
50.2
55.6
60.4
50.6
52.3
51.9
57.3
62.3
53.6
54.0
53.6
59.0
64.2
S.C.
47.6
45.3
37.5
37.5
29.0
50.6
50.0
41.0
41.0
31.0
53.6
54.0
44.6
44.6
33.1
KW
4.41
4.45
4.42
4.49
4.50
4.53
4.57
4.54
4.61
4.62
4.66
4.69
4.66
4.73
4.74
115
T.C.
45.4
48.0
47.7
52.7
57.4
48.2
49.7
49.3
54.4
59.3
51.1
51.4
50.8
56.0
61.2
S.C.
45.4
43.6
36.3
36.0
27.9
48.2
48.0
39.8
39.5
30.0
51.1
51.4
43.2
43.0
32.0
KW
4.84
4.87
4.85
4.92
4.93
4.97
4.99
4.97
5.04
5.05
5.10
5.11
5.09
5.15
5.17
125
T.C.
43.1
45.4
45.3
49.9
54.5
45.9
47.1
46.7
51.4
56.4
48.6
48.7
48.1
53.0
58.2
S.C.
43.1
42.0
35.1
34.6
26.9
45.9
46.0
38.5
38.1
29.0
48.6
48.7
41.8
41.5
31.0
KW
5.28
5.30
5.27
5.34
5.36
5.40
5.42
5.39
5.46
5.48
5.53
5.54
5.51
5.58
5.60
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (O INDOOR).
Green shaded cells are ACCA (TVA) conditions.
Blue shaded cells are AHRI conditions.
COIL MULTIPLIERS - 5 TON
Air Handler
Coil
T.C.
S.C.
KW
AE60DX21
–
1.00
1.05
1.00
AVC60DX21
–
1.00
1.06
1.04
ME20DN21
CF/CM64D
1.01
1.07
1.01
MVC20DN21
CF/CM64D
1.00
1.00
1.00
FURNACE MULTIPLIERS - 5 TON
Furnaces
Coil
T.C.
S.C.
KW
TM8V100C20MP12C
CF/CM64D
1.00
1.05
1.04
TM8V120C20MP12C
CF/CM64D
1.00
1.05
1.04
TM8X100C20MP11
CF/CM64D
1.00
1.05
1.04
TM8X120C20MP11
CF/CM64D
1.00
1.05
1.04
TM8Y100C20MP11
CF/CM64D
1.00
1.05
1.04
TM8Y120C20MP11
CF/CM64D
1.00
1.05
1.04
TM9E100C20MP11
CF/CM64D
0.99
1.05
1.05
TM9E120D20MP11
CF/CM64D
1.00
1.05
1.04
TM9V100C20MP12C
CF/CM64D
1.00
1.06
1.06
TM9V120D20MP12C
CF/CM64D
1.00
1.05
1.04
TM9Y100C20MP11
CF/CM64D
0.99
1.05
1.05
TM9Y120D20MP11
CF/CM64D
1.00
1.05
1.04
TMLV100C20MP12C
CF/CM64D
1.00
1.05
1.04
TMLV120C20MP12C
CF/CM64D
1.00
1.05
1.04
TMLX100C20MP11
CF/CM64D
1.00
1.05
1.04
TMLX120C20MP11
CF/CM64D
1.00
1.05
1.04
TP9C100C20MP13C
CF/CM64D
1.00
1.06
1.06
TP9C120D20MP13C
CF/CM64D
1.00
1.05
1.04
TPLC100C20MP13C
CF/CM64D
1.00
1.05
1.04
TPLC120C20MP13C
CF/CM64D
1.00
1.05
1.04
LP9C100C20MP13C
CF/CM64D
1.00
1.06
1.06
LP9C120D20MP13C
CF/CM64D
1.00
1.05
1.04
LPLC100C20MP13C
CF/CM64D
1.00
1.05
1.04
LPLC120C20MP13C
CF/CM64D
1.00
1.05
1.04
FURNACE MULTIPLIERS - 5 TON (Continued)
Furnaces
Coil
T.C.
S.C.
KW