Modbus addresses TOPAX® MC
43
© Lutz-Jesco GmbH 2020
Subject to technical changes.
200123
BA-46020-02-V04
Multi-Channel Controller
TOPAX
®
MC
Operating instructions
Address
Read
Write
Description
Meaning
2225
x
Alarm status 1
If the bit is set, the associated alarm or
message is active.
Message or alarm
Bit
Sensor error 1
Sensor error 2
Sensor error 3
Sensor error 4
Sensor 1 maximum alarm
Sensor 2 maximum alarm
Sensor 3 maximum alarm
Sensor 4 maximum alarm
Virtual 1 maximum alarm
Virtual 2 maximum alarm
Virtual 3 maximum alarm
Virtual 4 maximum alarm
Sensor 1 minimum alarm
Sensor 2 minimum alarm
Sensor 3 minimum alarm
Sensor 4 minimum alarm
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
2226
x
Alarm status 2
If the bit is set, the associated alarm or
message is active.
Message or alarm
Bit
Virtual 1 minimum alarm
Virtual 2 minimum alarm
Virtual 3 minimum alarm
Virtual 4 minimum alarm
Controller 1 Y alarm
Controller 2 Y alarm
Controller 3 Y alarm
Controller 4 Y alarm
Temperature 1 maximum alarm
Temperature 2 maximum alarm
Temperature 3 maximum alarm
Temperature 4 maximum alarm
Temperature 1 minimum alarm
Temperature 2 minimum alarm
Temperature 3 minimum alarm
Temperature 4 minimum alarm
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Tab. 29: Modbus addresses