background image

English

Single-Pole:

Insulated wires 

connected to two 

screws of the same 

color. 

See Step 5a 

when wiring.

OR

3-Way:

Insulated wires connected to three 

screws. One of these wires is connected 

to a screw of a different color (not green) 

or labeled COMMON. 

MARK

 or 

TAG

 this

wire to identify it when wiring. 

See Step 

5b when wiring.

Tag

Different-colored screw  

(Common). Actual location may vary.

OR

Ground  

(Bare Copper 

or Green Wire)

Ground (Bare Copper 

or Green Wire)

Installation

1

Turn OFF Power.

•  Turn power OFF at circuit break er or remove fuse.

2

Removing Wallplate and Switch.

•  Remove wallplate and switch mounting screws.

•  Carefully remove switch from wall 

(do not remove wires).

WARNING

: Shock Hazard. May result in 

serious injury or death. 

Turn off power 

at circuit breaker before installing 

the unit.

3

Identifying the Type of Circuit.

4

Disconnecting Switch Wires.

Important Note:

 Your wall switch may have two wires attached to 

the same screw (see illustrations below for examples). Tape these 

two wires together before disconnecting. Connect both wires to the 

control wire in Step 5.

One wire in the backwired 

hole and one to the screw.

Looped Wire:

Turn screw to loosen.

Screw Terminals: 

Turn screws to loosen.

Push-in Terminals:

Insert screwdriver. Pull wire out.

OR

OR

For installations involving more than one control in wallbox, 

refer to 

Multi-Unit Installations

 before beginning.

AYFSQ-F

CTFSQ-F

DLFSQ-F

DVFSQ-F

DVSCFSQ-F

DVWFSQ-F

LGFSQ-F

LXFSQ-F

TGFSQ-F

120 V

~

  60 Hz  1.5 A

Models:

DVFSQ-F-HO

DVSCFSQ-F-HO

LXFSQ-F-HO

120 V

~

  60 Hz  2 A

Models:

Break Off Side Sections

Each Control Has Inside 

Sections Removed

Middle Control Has Two 

Side Sections Removed

Important Notes: 

Please read before installing.

1.

  

CAUTION:

 To avoid overheating and possible damage to other equipment, do not use to control 

receptacles, lighting, fluorescent lighting fixtures, or transformer-supplied appliances.

2.

Do not use control with a fan and light that operate with the same switch.

3.

  When no “grounding means” exists within the wallbox for an existing control, the 2011 National 

Electrical Code

®

 (NEC

®

) allows a control to be installed as a replacement as long as 1) a nonmetallic, 

noncombustible faceplate is used with nonmetallic attachment screws or 2) the circuit is protected 

by a ground fault circuit interrupter. The 2008 NEC

®

 has the same allowances but does not contain 

the requirement for nonmetallic attachment screws. When installing a control according to any of 

these methods, cap or remove the green wire before screwing the control into the wallbox.

4.

  Wiring controls in a circuit which contains a ground fault circuit interrupter (GFCI) or an arc fault circuit

interrupter (AFCI) may cause nuisance tripping and is not recommended.

5.

  Use control with a ceiling paddle fan only. Use only one ceiling paddle fan per control.

6.

For new installations, wire a test switch before installing the control.

7.

Set multi-speed fans to their highest setting before installing controls.

8.

Use only one control in a 3-way circuit.

9.

Install in accordance with all national and local electrical codes.

10. 

Clean control with a 

soft damp cloth only

. Do not use any chemical cleaners.

Multi-Unit Installations

When combining controls in one wallbox, 

remove all inner side sections before wiring 

(see at right). Use pliers to bend each side 

section up and down until it breaks off. 

Reduction of control capacity is not required.

Single Pole/3-Way

Quiet Fan-Speed Controls

7

Turn ON Power.

Turn ON power at circuit break er or replace fuse.

6

Mounting Control to Wallbox.

•  Form wires carefully into the wallbox, mount and align control.

•  Install faceplate.

• 

Note:

 Only one control can be used in a 3-way 

circuit. Control can be used in either location.

• Connect the 

green

 ground wire

 

on the control

 

to the bare copper or green ground wire in the

wallbox. (See Important Note 3.)

• Connect 

black 

control wire to the tagged wire 

removed from the switch. If you had taped 

together two wires (see step 4), connect both 

wires to the 

black

 control wire screw and

remove the tape

• Connect the 

red

 wire on the control to one of the 

remaining wires removed from the switch.

•  Connect the 

red/white

 wire on the control to the 

remaining wire removed from the switch.

• Connect the 

green

 ground wire

 

on the control

to the bare copper or green ground wire in the 

wallbox. (See Important Note 3.)

• Connect the 

black

 control wire to one of the

wires removed from the switch. If you had taped 

together two wires (see step 4), connect both 

wires to the 

black

 control wire and remove

the tape.

• Connect the 

red

 wire on the control to the other 

wire removed from the switch.

•  Cap off the 

red/white

 wire on the control. 

Do 

NOT

 connect to any other wire or ground.

5

 5a - Single-Pole Wiring

 5b - 3-Way Wiring

OR

Green

Ground

Red

Red /  

White

Black

Ground

Red

Red /  

White

Black

Tag

120 V

~

60 Hz

Live      Black

Red

Red/White

Green

Ground

Neutral

Fan

Control

Red

Red/White

Green

Ground

Ground

Fan

Neutral

3-Way

Switch

Control

Note: 

Depending on model number, the control may include a Lutron

®

 

Claro

®

 or Fassada

®

 wallplate. 

A Lutron

®

 wallplate consists of 2 parts, a faceplate (front) that snaps into 

an adapter plate (back).

 

Please detach faceplate from adapter plate before installing. This will 

expose control mounting holes and prevent faceplate  

damage during installation.

Grasp top 

of faceplate 

and pull 

forward to 

detach it 

from adapter 

plate.

Faceplate (Front)

Adapter plate (Back)

•  

Note:

 Control can be installed in either

location.

Attach standard wallplate.

Attach Claro

R

 or Fassada

R

 wallplate which consists of 2 parts, an 

adapter plate (back) and faceplate (front).

OR

Faceplate 

(Front)

Adapter plate 

(Back)

Note: 

Do not 

overtighten 

mounting screws. 

Permanent damage 

may occur.

Snap on faceplate

Note: 

Follow recommended strip lengths and combinations for supplied wire 

connectors. Wire connectors are suitable for copper wire only. For aluminum 

wire, consult an electrician.

Twist wire 

connector tight.

Ensure that no 

bare wire is 

exposed.

Wiring the Control.

•  For installations involving more than one control in a wallbox, refer to the section on 

Multi-Unit Installations before beginning.

120 V

~

60 Hz

Live       Black

Green

Do Not Remove 

Outside Sections

Отзывы: