Distribution
Panel
Neutrals
Earth/Grounds
Hot/Live
Danger - Locate and lock the supply breaker in
the OFF position or remove the supply fuse
before working on any circuit.
Momentary
SPDT Switch
(wallbox not
shown)
AC Motorized
Window
Treatment Shown
Pre-installation Motor Wiring Check
Test your wiring before connecting to the Group Controller.
Use either a momentary, Single Pole Double Throw
(SPDT) switch (as described below) or a motor wiring test
kit (available from Lutron). To order the motor wiring test
kit, contact Lutron at 1-888-SIVOIA1 (1-888-748-6481) and
ask for model 6020086.
Note: If using the motor wiring test kit, please refer to the
instructions provided with the kit.
Testing motor wiring using a SPDT switch:
1.
Turn power OFF at circuit breaker (MCB) or remove
fuse.
2.
Connect the motor ground wire to earth ground.
Connect earth ground to the ground terminal on the
switch.
3.
Connect the motor neutral wire to supply neutral.
4.
Using one momentary, Single Pole Double Throw
(SPDT) switch for each motor, connect hot/live to the
common terminal on the switch.
5.
Connect one each of the motor power wires to the
output terminals on the switch. Never wire more than
one motor to a switch.
6.
Mount switch in a wallbox. Be sure no bare wires or
terminals on the switch are exposed.
7.
After verifying it is safe to restore power, turn power
ON.
8.
Verify motor will raise/open and lower/close properly. If
necessary, remove power and correct wiring.