Input 
100 V

~

  50/60 Hz  1.5 A

Output
35 V

-  

143 mA

Lutron Electronics Co., Inc.

7200 Suter Road

Coopersburg, PA 18036-1299, U.S.A.

02/2020

P/N 045650 Rev. B

QS Link Plug-In Power Supply

Installation Guide

 – Please read before installing

English

  Important Notes

1. 

All wiring and circuit protection must be in accordance with national and local electrical codes.

2. 

Ambient operating temperature: 0 °C to 40 °C (32 °F to 104 °F), 0 to 90% humidity, non-condensing.

3. 

This product is intended for indoor use only.

Mount the Power Supply (optional)

•  The power supply can be mounted using the mounting tabs and fasteners of appropriate type for the mounting 

surface. Hand tighten only. 

DO NOT

 use a power tool to tighten the fasteners.

•  It is recommended to mount power supplies in a location that will remain accessible, where it will not interfere with 

window treatments or other moving devices.

Rules for QS Link Wiring

•  +35 V

-

 must NEVER be connected between devices that supply PDUs (Power Draw Units).*

•  Use a Lutron-specific wire for the QS link.
•  The maximum total distance of the QS link is 600m (1969ft) (when using GRX-CBL-46L).
•  Only use the cable noted above for the QS link wiring. Using other cable may cause malfunction.

Maximum devices powered by one 

QSPS-1-35V

Shades

Controls

1 shade or 

drapery drive

Up to  

1 PDU*

None

Up to 

8 PDUs*

*  For more information, refer to the QS Link Power Draw Unit Specification Submittal (P/N 369405) at www.lutron.com

Connect the Power Supply

•  Strip 6 mm (0.25 in) of insulation from each conductor.
•  Tighten each terminal screw securely to 0.5 N•m (5 in-lb), and ensure there is no insulation inside the  

terminal block.

 1 

  Connect the drive for the window treatment or connected PDUs

a. Connect the power and common wires to the corresponding 35 V and COM terminals.
b. Connect the communication wires to the corresponding MUX and MUX terminals.

 2 

  Daisy Chain Power Supply Communication Lines (optional)

Multiple power supplies (and their connected devices) may be daisy-chained along the wired communications 

link as shown.

a. Connect the incoming communications link wires to the corresponding terminals on one side of the communications link 

pass-through.

b. Connect the outgoing communications link wires to the corresponding terminals on the other side of the 

communications link pass-through.

 3 

  Connect the AC Cord

Use the 3-prong power cord supplied. This device must utilize earth ground to ensure proper operation.

a. Connect the AC power cord to the power supply.
b. Plug the power cord into a standard 3-prong receptacle.

Worldwide Headquarters

Lutron Electronics Co., Inc.
7200 Suter Road
Coopersburg, PA 18036-1299 USA
USA, Canada, Caribbean:
1.844.LUTRON1 (588-7661)
Mexico: +1.888.235.2910
Central & South America:
+1.610.282.6701
www.lutron.com/support
[email protected]

United Kingdom

In EEA imported by:
Lutron EA Ltd
125 Finsbury Pavement
4th Floor, London, EC2A 1NQ UK
TEL: +44.(0)20.7702.0657
FAX: +44.(0)20.7480.6899
Tech Support: +44.(0)20.7680.4481
FREEPHONE: 0800.282.107

Asian Headquarters

Lutron GL Ltd.
390 Havelock Road
#07-04 King’s Centre
Singapore,  169662
TEL: +65.6220.4666
FAX: +65.6220.4333
[email protected]

Japan

Free Dial: 0120.083.417

www.lutron.com/japan

Customer Assistance

www.lutron.jp/file/limited_warranty.pdf

Warranty

Lutron is a trademark or registered trademark of Lutron Electronics Co., Inc. in the US and/or other countries.

32 mm

(1.25)

70 mm

(2.75)

103 mm

(4.00)

6 mm 

(0.25)

0.5 N•m

(5 in-lb)