A
Press and release the “Cal.” button on the
Daylight Sensor.
B
Turn lights in room on using the Relay Toggle
button on the PowPak Relay Module or an
associated Pico.
C
Press and hold the “Cal.” button for 6 seconds.
D
Exit room for 5 minutes to allow calibration to be completed.
Note:
When calibration has completed, all lights will flash and
begin to respond to daylight.
vive.lutron.com
X
Programming with a Vive Hub
2
A
Use an iOS
®
or Android
®
compatible device.
C
Open the app and follow the
instructions.
Note:
For further information on set up,
programming, and troubleshooting with a
Vive system, please refer to the installation
instructions included with the Vive hub or
visit www.lutron.com/vive
Note:
For programming the PowPak Relay
Module without a Vive hub see below.
X
Vive
B
Download the Lutron
Vive app.
PowPak
|
Programming without a Vive Hub
Start Here
1
A
PowPak Relay Module can be installed in a junction
box or marshalling box using the conduit nut
(provided) or with mounting screws (not provided).
Please consult local and national electric codes for
proper installation.
If installing unit inside a junction box, please see
Application Note #423 (P/N 048423) at
www.lutron.com
B
Once installed, energize the PowPak Relay Module.
C
Use the Relay Toggle button to toggle between high-
end and OFF to verify wiring.
Install PowPak Relay Module
Suggested Installation Location: Center of
room to ensure proper RF coverage of area.
Part of the Vive Family
PowPak | Installation
Relay Module
English
041647
Rev. A
03/2018
RMJS-16R-DV-B | URMJS-16R-DVB |
RMJS-16R-DV-B-EM
With Softswitch
RMJS-16RCCO1DV-B | URMJS-16RCCO1DVB
With Softswitch
and Occupancy-Status CCO
120 / 277 V
~
50 / 60 Hz 16 A
1/2 HP at 120 V
~
1
1
⁄
2
HP at 277 V
~
Shock Hazard. May result in serious injury or death.
Turn off power at circuit breaker before installing the unit.
WARNING
All Wireless Transmitters must be installed within
30 ft (9 m) of the PowPak Relay Module.
Radio Powr Savr
Occupancy
Sensor
30 ft (9 m)
Maximum
40 ft (12 m)
30 ft (9 m)
PowPak
Relay Module
Install in center of room to
maximize RF coverage.
Pico
Remote
Control
Note for Replacement:
RMJS and URMJS - the "S" model can replace the non-"S" model
Important
Notes:
Please read before installing.
•
For installation by a qualified electrician in accordance with all local and national
electrical codes (including periodic testing and maintenance of emergency
systems).
•
Note:
Use copper conductors only.
•
Check to see that the device type and rating is suitable for the application.
•
DO NOT
install if product has any visible damage.
•
If moisture or condensation is evident, allow the product to dry completely
before
installation.
•
Operate between 32 °F (0 °C) and 131 °F (55 °C).
•
0% to 90% humidity, non-condensing.
•
For indoor use only.
RMJS-5R-DV-B
RMJS-5RCCO1-DV-B
With Occupancy-Status CCO
120 / 277 V
~
50 / 60 Hz 5 A
1/6 HP at 120 V
~
1/3 HP at 277 V
~
PowPak Relay Module
UL 2043 Plenum Rated
UL 924 Listed (RMJS-16R-DV-B-EM)
Test
Link
Cal.
For each system ensure you have:
At least one PowPak Relay Module
At least one Wireless Transmitter
Required Components
Radio Powr Savr Occupancy
Sensor (10 maximum)
PowPak Relay Module
Load
Status
LED
Relay Toggle
Advanced
Operations
Contact
Closure
Output
(CCO)
(Class 2)
(Occupancy-Status CCO Option Shown)
Relay Module
without
occupancy-status
CCO also
available.
Radio Powr Savr
Daylight Sensor
(1 maximum)
Pico
Remote Control
(10 maximum)
Customer Assistance www.lutron.com/support
+
Reset Factory Defaults
Note:
In some instances it may be necessary to reset the
PowPak
Relay Module back to factory default settings.
A
Triple-tap the Advanced Operations (“ADV”) button on the
Relay Module and hold until the LED begins to flash slowly.
B
Within 3 seconds of flashing, release and triple-tap the button
again and the LED will flash rapidly indicating that the unit has
been reset to factory defaults.
Note:
Any associations or programming previously set up with
the unit will be lost and will need to be re-programmed.
CCO Information
•
Some PowPak Relay Modules include a dry contact closure
output that provides occupancy status to 3rd-party equipment
such as building management systems, HVAC, and VAV
controllers.
•
CCO provides both normally open (NO) and normally closed (NC)
maintained-type outputs.
•
CCO rated to switch resistive loads at
voltages up to 24 V only. To properly
control inductive load types such as
relays, solenoids, or motors, refer to
Application Note #434.
Switching
Voltage
0-24 V
-
0-24 V
~
Resistive
Load
1.0 A
0.5 A
R
Note:
When wiring a CCO model
to
3rd-party systems, use
20 AWG to 16 AWG (0.5 mm
2
to
1.5 mm
2
) solid or stranded wire.
To 3rd Party Equipment
NO
(Normally Open)
NC
(Normally Closed)
COM
(Common)
CCO operation affected only by
associated occupancy or vacancy sensors.
Room Occupied:
NO = Close NC = Open
Room Unoccupied:
NO = Open NC = Close
Line/Hot
(Black)
Neutral
Switched
Line/Hot (Red)
To Normal Load
Neutral (White)
1/2 in (21 mm) Knockout Opening
Conduit Nut
To Emergency
Loads
Emergency
Backup Generator
Automatic
Transfer
Switch
Regular
Utility Power
Neutral
120 / 277 V
~
Normal Feed
Neutral
120 / 277 V
~
Emergency Feed
Note:
For periodic testing and maintanance of
emergency systems, use the toggle button
of the RMJS-16R-DV-B-EM to ensure proper
operation. Make sure PowPak buttons remain
accessible.
Note:
Momentary power outages can envoke
emergency mode on the relay module.
See
Troubleshooting
section for details.
RMJS-16R-DV-B-EM only
Line/Hot
(Black)
Neutral
Switched
Line/Hot (Red)
Neutral (White)
Associate Wireless Transmitters to PowPak Relay Module
Before beginning this step, make sure that there are no other PowPak modules being set up within the same building. It is possible that Wireless
Transmitters from other systems can be incorrectly associated to this system.
1
A
Hold the Relay
Toggle button on
the PowPak Relay
Module for 6 seconds
to enter association
mode.
B
Hold the indicated button
on a Wireless Transmitter
for 6 seconds to
associate the device.*
Repeat for any additional
Wireless Transmitters.
C
Hold the Relay Toggle button on
the PowPak Relay Module for 6
seconds to save association(s).
* If no
g
button, hold
“Lights Off” button.
Note:
The load
will flash once
after each step to
confirm successful
completion.
Test
Link
Cal.
Calibrate the Radio Powr Savr
Daylight Sensor
Daylight Sensor will control all wired fixtures equally.
2
D
Permanently install wireless
transmitters (consult individual
component installation guides for
information).
Test
Link
Relay
Toggle
Advanced
Operations
Lutron, Pico, PowPak, Softswitch, and Vive are trademarks of Lutron Electronics Co., Inc., registered in the U.S. and other countries. Radio Powr Savr is a trademark of Lutron Electronics Co., Inc. Safari is a trademark of Apple Inc., registered in the U.S. and other countries. iOS is a registered trademark of Cisco in
the U.S. and other countries and is used under license. Google is a registered trademark and Android and Chrome are trademarks of Google Inc.NEC is a registered trademark of the National Fire Protection Association, Quincy, Massachusetts. ©2013 – 2018 Lutron Electronics Co., Inc.
Lutron Electronics Co., Inc. | 7200 Suter Road
Coopersburg, PA 18036-1299, U.S.A.
Customer Assistance | 1.844.LUTRON1
U.S.A., Canada, and the Caribbean
| +44.(0)20.7680.4481
Europe
| +1.610.282.3800
Others
| www.lutron.com/support
Limited Warranty:
www.lutron.com/TechnicalDocumentLibrary/369-119_Wallbox_Warranty.pdf
For FCC/IC information:
Please visit: www.lutron.com/fcc-ic
Load does not respond to
Wireless Transmitter(s)
• Ensure breaker to the PowPak Relay Module is on.
• Ensure the load has been properly wired to the PowPak Relay Module.
• Ensure Wireless Transmitter is properly associated to PowPak Relay
Module.
• Ensure Wireless Transmitter’s battery is installed correctly.
Wireless Transmitter(s)
cannot be associated to
PowPak Relay Module
• The maximum number of Wireless Transmitters have been
associated to the PowPak Relay Module. To remove a previously
set up Wireless Transmitter, tap the button used for association on
the Wireless Transmitter three times, on the third tap hold for three
seconds and then tap three more times.
PowPak is in emergency
mode
(RMJS-16R-DV-B-EM only)
• In systems with a Vive hub: Contact Lutron Customer
Assistance for further details.
• In systems without a Vive hub: Wait 90 minutes for the PowPak
to return to normal operation.
PowPak will not go into
emergency mode
(RMJS-16R-DV-B-EM only)
• Contact Lutron Customer Assistance for further details.
Troubleshooting
www.lutron.com/support
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions should always be
followed including the following:
READ AND FOLLOW ALL SAFETY
INSTRUCTIONS.
• Do not use outdoors.
• Do not mount near gas or electric heaters.
•
Equipment should be mounted in locations and at heights where it will not be
subjected to tampering by unauthorized personnel.
•
The use of accessory equipment not recommended by the manufacturer may cause
an unsafe condition.
• Do not use this equipment for other than its intended use.
SAVE THESE INSTRUCTIONS
Junction Box
Junction Box
1/2 in (21 mm)
Knockout Opening
Conduit Nut