Assemble
Mount and Install
Associate
Connect
1
3
4
2
a.
Insert the Pico
®
control wiring connector through the
hole in the unmounted wallplate adapter.
a.
Carefully mount and align the wallplate adapter.
b.
Attach wallplate adapter to wallbox with provided screws.
c.
Snap wallplate onto wallplate adapter.
a.
Turn on power to the Wallstation control by energizing the link.
b.
Wallstation controls must be programmed through the Lutron
®
Hospitality System Guestroom Control unit’s software before the
controls will function as described.*
* Door chime functionality requires the installation and programming of the door
chime components
a.
Wire the connector terminals to the QS link wiring in wallbox. See
QS
Link Wiring Notes
for further details.
b.
Connect the Pico
®
control connector to the QS link of the Lutron
®
Hospitality Room Controller.
b.
Slide the Pico
®
control onto the wallplate adapter guide rails that
match the opening in the wallplate.
Pico
®
Wallstations
Installation
For use with Lutron
®
Hospitality Guestroom Solution
Important Notes
Please read before installing
• For installation by a qualified electrician in accordance with all local and
national electrical codes.
• Operate between 0 °C (32 °F) and 40 °C (104 °F).
• Do not connect line-voltage wires to wallstation terminals. Improper
wiring can result in personal injury or damage to the control or to other
equipment.
• Use only a cloth with warm water and mild soap to clean faceplates (no
chemical cleaners).
QSWP-DM
QSWP-CP
IEC PELV/NEC
®
Class 2 24 V
-
30 mA
Required Components
For each system, ensure that you have:
One for each single Pico
®
Control:
Wallplate/Wallplate Adapter kit
(PWP-S1, PWP-S2, PWP-D3, PWP-D4)
Pico
®
Privacy Control (QSWP-DM)
and
/
or
Pico
®
Corridor Control (QSWP-CP)
Top LED
(green)
Top Button:
toggle for
make-up-room
request
Bottom LED
(red)
Bottom Button:
toggle for
do-not-disturb
request
Top LED
(green)
Button:
press to
sound door
chime
Bottom LED
(red)
+
WARNING. Shock Hazard. May result
in serious injury or death.
Turn off
power at circuit breaker before installing
the unit.
4: MUX
3: MUX
2: 24 V
-
1: Common
Need Help? Call Lutron Technical Support at +44.(0)20.7680.4481 or visit www.lutron.com
QS Link Wiring Notes
• Operating Voltage: 24 V
-
(IEC PELV/NEC
®
Class 2), powered off of the
QS link or an external 24 V
-
supply
• Current Draw: 30 mA maximum
• Consumes 1 Power Draw Unit (PDU) on the QS link; for more
information on PDUs, see “Power Draw Units on the QS Link”, Lutron
P/N 369405 at www.lutron.com
• Counts as one device and no zones on the QS link
• For more information regarding Lutron
®
cable specifications, please see
Lutron P/N 369597 at www.lutron.com
• For wire runs over 610 m (2 000 ft), please contact Lutron
®
Technical
Support
Terminals
• Accept up to two 1.0 mm
2
(18 AWG) wires;
one twisted, shielded pair 0.50 mm
2
(22 AWG) wire; or
one 4.0 mm
2
(12 AWG) wire, typically.
• For wiring limits, see chart below.
QS Link
Wiring Length
Wire Gauge
Lutron
®
Cable
Part Number
Less than
153 m (500 ft)
Power (terminals 1 and 2):
1 pair 1.0 mm
2
(18 AWG)
GRX-CBL-346S
(non-plenum)
GRX-PCBL-346S
(plenum)
Data (terminals 3 and 4):
1 twisted, shielded pair 0.50 mm
2
(22 AWG)
Up to 610 m
(2 000 ft)
Power (terminals 1 and 2):
1 pair 4.0 mm
2
(12 AWG)
GRX-CBL-46L
(non-plenum)
GRX-PCBL-46L
(plenum)
Data (terminals 3 and 4):
1 twisted, shielded pair 0.50 mm
2
(22 AWG)
Troubleshooting
Symptoms
Possible Causes
No communication
with the Room
Controller
Miswire or loose connection at the control
link data lines 3 and 4.
Wallstation LEDs scroll
in reverse order
Wallstation buttons do
not work. LEDs and
buttons do not function
as intended
Wallstation is miswired.
Wallstation is not powered.
Wallstation has been programmed incorrectly.
LEDs do not light
Miswire or loose connection at wallstation(s)
or processor on the control link common and
power connections 1 and 2.
Wallstation has been programmed incorrectly.
Warranty
For warranty information, please visit
www.lutron.com/TechnicalDocumentLibrary/Warranty.pdf
Technical Assistance
U.S.A. / Canada: 1.800.523.9466
Mexico: +1.888.235.2910
Brazil: +55 11 3257 6745
United Kingdom: +44.(0)20.7680.4481
India: +91.124.471.1900
United Arab Emirates: +971.4.299.1224
China: 10.800.120.1536
Singapore: 800.120.4491
Other Countries: +1.610.282.3800
Pico
®
Privacy Control
Inside Guestroom
Pico
®
Corridor Control
Outside Guestroom
IEC PELV/NEC
®
Class 2 control wiring:
2: 24 V
-
1: Common
4
3
2
1
Drain
Data Link: 1 twisted, shielded pair
4: MUX
3: MUX
Lutron
®
Hospitality Guestroom Controller
(GCU-HOSP)
Radio Frequency (RF) Receiver with Door Chime or third-party door bell solution with QSE-IO.
+
+
Lutron, Pico, and
)
are registered trademarks of Lutron Electronics Co., Inc.
NEC is a registered trademark of National Fire Protection Association, Quincy, Massachusetts
©2013 Lutron Electronics Co., Inc.
Lutron Electronics Co., Inc.
7200 Suter Road
|
Coopersburg, PA 18036-1299
TEL: +1.610.282.3800
Start Here
040397 Rev. A
04/2013
English