Step 5: Set the SMC55-HWQS Advanced Parameters to Modify the
Functionality of the HVAC System
(continued)
Parameters Applicable to Conventional and Heat Pump Systems
(continued)
(74A) Heat Stage 1
–
On Delta
1
Use this parameter to identify the temperature below the heat setpoint when Heat Stage 1 should turn on. Refer to the control
diagrams in
Appendix A
. These diagrams graphically represent the Heat Stage 1-On Delta for Conventional and Heat Pump
systems.
(75A) Heat Stage 1
–
Off Delta
1
Use this parameter to identify the temperature above the heat setpoint when Heat Stage 1 should turn off. Refer to the control
diagrams in
Appendix A
. These diagrams graphically represent the Heat Stage 1-Off Delta for Conventional and Heat Pump
systems.
(76A) Heat Stage 2 (Y
2
/W
2
/Aux)
–
On Delta
1
Use this parameter to identify the temperature below the heat setpoint when Heat Stage 2 should turn on. Refer to the control
diagrams in
Appendix A
. These diagrams graphically represent the Heat Stage 2-On Delta for Conventional and Heat Pump
systems.
(77A) Heat Stage 2
–
Off Delta
1
Use this parameter to identify the temperature above the heat setpoint when Heat Stage 2 should turn off. Refer to the control
diagrams in
Appendix A
. These diagrams graphically represent the Heat Stage 2-Off Delta for Conventional and Heat Pump
systems.
(78A) Heat Stage 3 (Aux)
–
On Delta
1
Use this parameter to identify the temperature below the heat setpoint when Heat Stage 3 (Aux) should turn on. Refer to the
control diagrams in
Appendix A
. These diagrams graphically represent the Heat Stage 3-On Delta for Conventional and Heat
Pump systems.
(79A) Heat Stage 3 (Aux)
–
Off Delta
1
Use this parameter to identify the temperature above the heat setpoint when Heat Stage 3 (Aux) should turn off. Refer to the
control diagrams in
Appendix A
. These diagrams graphically represent the Heat Stage 3-Off Delta for Conventional and Heat
Pump systems.
(80A) Cool Stage 1
–
On Delta
1
Use this parameter to identify the temperature above the cool setpoint when Cool Stage 1 should turn on. Refer to the control
diagrams in
Appendix A
. These diagrams graphically represent the Cool Stage 1-On Delta for Conventional and Heat Pump
systems.
(81A) Cool Stage 1
–
Off Delta
1
Use this parameter to identify the temperature below the cool setpoint when Cool Stage 1 should turn off. Refer to the control
diagrams in
Appendix A
. These diagrams graphically represent the Cool Stage 1-Off Delta for Conventional and Heat Pump
systems.
(82A) Cool Stage 2
–
On Delta
1
Use this parameter to identify the temperature above the cool setpoint when Cool Stage 2 should turn on. Refer to the control
diagrams in
Appendix A
. These diagrams graphically represent the Cool Stage 2-On Delta for Conventional and Heat Pump
systems.
1
Included with SMC55-HWQS version 7420 or newer, SMC55-RESI version 7302 or newer and HomeWorks Palladiom Thermostat version 1.10 or newer.