background image

Factory Settings

SENSOR ADJUSTMENTS

Timer Test Mode

1. Remove the retainer cover.
2. Rotate the black timer adjustment knob to 

about midway (12 o’clock).

3. Return setting to minimum setting (full CCW).

Note: The timer will remain in the 8-second test
mode for 1 hour, then automatically reset to 
8 minutes.

4. To manually take the timer out of the 8-second 

test mode, turn the timer adjustment approximately
1/16” clockwise to make the setting slightly above
minimum (just above the 8-minute setting).

Adjusting the “Lights Not On” Level: LOS-CDT-xxxxR only

1. Ensure ambient light is at desired level.
2. Place sensor in Test Mode as indicated above.
3. Set photo cell: Turn the blue knob full clockwise (lights on no

matter how bright the natural light is), then about 30 degrees
counterclockwise.

4. Check for Lights-Out: Move from underneath the sensor,

and remain still until the lights turn off. Move around normally
to turn the light on.

5. Adjust to desired level: If lights turn on, adjust the blue knob

another 30 degrees counterclockwise and repeat step 3 until
the lights remain off.

Note:

Set blue knob to 100% to disable photo cell function-

ality and leave secondary dry contact closure output func-
tionality intact.

Factory

Settings

12 o’clock

Full CCW

ON

ON

ON

ON

A

   1

   2

   3

   4

B

1

2

3

4

Black: Timer 
8 min. default

Blue: Photo cell 
(R model only)
100% default

Red: Infrared
sensitivity 
75% default

Green: Ultrasonic
range 
50% default

Recommendation: Leave sensitivity settings as shipped.
Note: Not all models have every knob.

Control Settings (Blue Knob): LOS-CDT-xxxxR only

0

1000

0

1000

0

1000

Minimum (low):
Lights will never come on, even though
room is occupied.

Maximum (high):
Photo cell has no effect on operation 
(factory setting).

Normal:
200 to 600 LUX is normal range.

Lighting
Control
system

Red (+20-24 V    )

Gray (control: occupancy & photo cell signal)

Black (common)

Yellow/White (NO)

Black/White (NC)

Blue/White (Relay Common)

Gray wire: logic with photo cell active:

Room First Occupied

During Occupancy

Light level:

Lights:

Light level:

Lights:

Below set value

Turn on

Falls below set value

Turn on

Above set value

Remain off

Moves above set value

Remain on

Choose wire based on functionality:
• Yellow/White: NO (normally open)

Open: Unoccupied
Closed: Occupied

• Black/White: NC (normally closed)

Open: Occupied
Closed: Unoccupied

Cap off unused wire.

WIRING DIAGRAMS

Relay Model Option: LOS-CDT-xxxxR only

PRE-INSTALLATION

1. For installation by a qualified electrician in accordance with national and local codes and the following instructions.
2. For indoor use only.
3. 

CAUTION: RISK OF ELECTRIC SHOCK. Disconnect power before installing. Never wire energized electrical

components.

4. 

CAUTION: USE COPPER CONDUCTORS ONLY.

5. 

CAUTION: Do not connect this Class 2/PELV product to line voltage/mains cable.

6. Check to see that the device type and rating is suitable for the application.
7. Do not install if product or lens have any visible damage.
8. If moisture or condensation is evident, allow the product to dry completely before installation.

INSTALLATION AND MOUNTING

Cutter end

13/16”
(21mm)

Mounting Plate Dimensions

4.2”
(106.6mm)

2.5”
(63mm)

.52”
(13.3mm)

Wire Lengths (feet)

# Sensors

1

2

3

1

2

1

# Aux. PPs

0

0

0

1

1

2

22 AWG

750

375

250

375

250

250

20 AWG

1200

600

400

600

400

400

18 AWG

2400

1200

800

1200

800

800

Using the Infrared Mask

Typical Mask Patterns

Center Ceiling Mount

(Mask blocks sensor

seeing out doorway

into hall)

Corner Ceiling Mount

(No mask needed)

Conference

Room Mask

180° Mask

Full Mask

Rectangular

Areas

Over the

Door

Specific

Areas You

Wish to

Mask

Normal Mounting:
Twist and lock threaded mounting post onto cover
plate. Drill through ceiling tile with assembly, using cut-
ter end of the threaded mounting post. Secure with
washer and nut.

Mounting to Non-Standard Ceiling/Fixture:
Mount twist-lock cover plate using mounting screws,
nuts, and washers (included). Drill/punch wire routing
hole through ceiling tile at center of cover plate.

Auto/Manual

Threshold

LED Motion Indicator

Reset Learned Settings

Strong Airflow Compensation

Over Doorway Installation

Timer Adjust

Auto Sensitivity

1

2

3

4

Off (Default)

On

Automatic (Normal)

Manual on/off (Override)

Auto Threshold Adjustment

High Sensitivity (Low turn-on threshold)

Lights indicate motion

Disable LED Indicator

Retain Settings (Normal)

Erase all learned settings,
restart Learning (Toggle On)

Off (Default)

On

Disable Compensation (Normal)

Enable Compensation

No (Normal)

Yes (Use increased turn-on threshold)

Adjust Timer Automatically

Use Manual Setting

Adjust Sensitivity Automatically

Adjust Sensitivity Manually

ON

ON

SENSOR ADJUSTMENTS

Override Settings

1

2

3

4

R

3

2

R

A

B

Blue: Cap off

Отзывы: