OCCUPANT SENSOR
LOS-C SERIES
Installation Instructions
Please Read
DESCRIPTION
The LOS-C Series of ceiling-mounted sensors incorporate ultrasonics (CUS), infrared (CIR), and dual technologies
(CDT). They integrate into Lutron systems or function as stand-alone controls using a Lutron power pack.
FEATURES
• Intelligent, continually adapting sensors
• 20-24V , Class 2 (PELV) low voltage, 33 mA nominal
• 450 to 2000 sq.ft. coverage, as indicated in model number (when mounted on 8 ft. ceiling)
• Second dry contact closure available on R models
• LED indicators: Ultrasonic (US)-green, Infrared (IR)-red, Dual Tech (DT)-red and green
• For indoor use only
COVERAGE AND PLACEMENT
• The occupant sensor must have an unobstructed view of the room. Do not mount behind or near tall cabinets,
shelves, hanging fixtures, etc.
• Keep the occupant sensor away from air flow.
• If installing a 180° occupant sensor, place the sensor on the same wall as the doorway so that hallway traffic will not
affect the sensor; otherwise, place in center of room.
• Closely follow the diagrams for major and minor motion coverage.
• Decrease total coverage area by 15% for “soft“ rooms (for example, heavy draperies or heavy carpeting).
• Indicated range is when unit is mounted on an 8 ft. ceiling.
Model
US Minor Dims.
US Major Dims.
IR Minor
IR Major
CUS-500*
16 x 16 (4.9 x 4.9)
22 x 22 (6.7 x 6.7)
NA
NA
CUS-1000*
23 x 23 (7.0 x 7.0)
32 x 32 (9.8 x 9.8)
NA
NA
CUS-2000**
23 x 45 (7.0 x 13.7)
32 x 64 (9.8 x 19.5)
NA
NA
CIR-450**
NA
NA
6.5 (1.9)
12 (3.7)
CIR-1500**
NA
NA
12 (3.7)
22 (6.7)
CDT-500*
23 x 16 (7.0 x 4.9)
32 x 22 (9.8 x 6.7)
12 (3.7)
22 (6.7)
CDT-1000*
23 x 23 (7.0 x 7.0)
32 x 32 (9.8 x 9.8)
12 (3.7)
22 (6.7)
CDT-2000**
23 x 45 (7.0 x 13.7)
32 x 64 (9.8 x 19.5)
12 (3.7)
22 (6.7)
*180° field of view
**360° field of view
US Major Motion
US Minor Motion
US
Minor
Motion
US
Major
Motion
IR Minor Motion
IR Major Motion
Motion Detection Ranges
Dimensions and Ranges are in feet (m).
Single Sensor to System
2 or More Sensors to System
Lighting
control
system
Red (+20-24 V )
Blue (signal)
Black (common)
Red (+20-24 V )
Blue (signal)
Black (common)
Lighting
control
system
To additional sensors, maximum
determined by lighting controller
120/277/347 V 60 Hz;
230 V 50/60 Hz
Neutral
Power Pack
Manual switch
off (optional)
Load
Note: Maximum 3 occupant sensors.
Red (+20-24 V )
Blue (signal)
Black
(common)
Black
White
Red
Red
1 to 3 Sensors with Power Pack
Switching Multiple Loads with Auxiliary Power Packs
Hot
Manual switch off (optional)
Load
Load
Power
Pack
Auxiliary
Power
Pack
Red
Red
Red (+20-24 V )
Black
(common)
Note: Maximum of 3 devices total
(occupant sensors and auxiliary power packs) can be connected to a power pack.
Neutral
Hot
Blue (signal)
Black
White
Red
Red
WIRING DIAGRAMS (continued)
LOS-CUS-500/1000/2000
LOS-CIR-450/1500
LOS-CDT-500/500R/1000/1000R/2000/2000R
Class 2 (PELV) Devices
English
Espanol
Francais
Portugues
LIMITED WARRANTY
Lutron will, at its option, repair or replace any unit that is defective in materials or manufacture within one year after
purchase. For warranty service, return unit to place of purchase or mail to Lutron at 7200 Suter Rd., Coopersburg, PA
18036-1299, postage pre-paid.
This warranty is in lieu of all other express warranties, and the implied warranty of merchantability is limited to one year
from purchase. This warranty does not cover the cost of installation, removal or reinstallation, or damage resulting
from misuse, abuse, or improper or incorrect repair, or damage from improper wiring or installation. This warranty
does not cover incidental or consequential damages. Lutron’s liability on any claim for damages arising out of or in
connection with the manufacture, sale, installation, delivery, or use of the unit shall never exceed the purchase price of
the unit.
This warranty gives you specific legal rights, and you may also have other rights which vary from state to state. Some
states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you.
Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or
exclusion may not apply to you.
Lutron and the sunburst logo are registered trademarks of Lutron Electronics Co., Inc. © 2005.
World Headquarters
Lutron Electronics Co., Inc.
7200 Suter Road
Coopersburg, PA 18036
TEL +1-610-282-3800
FAX +1-610-282-1243
Internet: www.lutron.com
E-mail: [email protected]
Lutron Electronics Co., Inc.
Made and printed in U.S.A.
P/N 031-260 Rev. A 6/05
TROUBLESHOOTING
Problem
Possible Cause
Test
Result
Lights stay on
Air conditioning
Reduce both green and
Move sensor; temporarily
interference
red knob by 15%
reduce sensitivity
Lights on too long
Timer setting too high
Check switch settings
Typical setting is 8 min.
Hallway traffic
Sensor “sees”
Put in timer test mode;
Move sensor
turns lights on
into hallway
walk along hallway
Sensor not responding
Unit is locked up
--
Cycle power to sensor
R
R
120/277/
347 V
60 Hz;
230 V
50/60 Hz