background image

Contractor Quick Start Guide for 
Vive Integral Fixture Controls

Part of the Vive System

Customer Assistance  |  1.844.LUTRON1  

USA, Canada, and the Caribbean

  |  +1.888.235.2910 

Mexico

  |  +1.610.282.3800 

Others

  |  www.lutron.com

   Important Installation and Startup Notes 

1.  

If access to the fixture is required in order to supply power:

 A. 

 

Minimize the length of wires (incoming power) that can bundle up in close proximity to the Vive Integral 
Fixture Control.

 B. 

 

Keep incoming power wires separated from the wires that run between the driver and the fixture control.

2.  

Fixture will run through the self-test as described to the left.

 A. 

 

If at the end of that self-test the fixture control LED turns green and the fixture is ON,  
the fixture passes the test. Proceed with commissioning.

 B. 

 

If at the end of that self-test the fixture control LED turns red and the fixture is OFF:

 

  i.   Adjust wiring as described in Step 1 above. Ensure incoming power wires and LED wires are 

separated from the sensor wires. Wires may have shifted during shipping/installation or may have 
been bundled together when closing up the driver channel.

  

ii. 

 

Repeat the self-test by doing one of the following:

 

   

a. Toggle power to the fixture (at the breaker or fixture quick connects).

  

 b. 

 

 

With fixture powered, Reset Factory Defaults for fixture control. See the 

Reset Factory Defaults

 

section.

  

iii. 

 

If the self-test still results in a red LED the range of the fixture may be reduced in certain 
installations.

 Work with whomever is doing the commissioning of the system to test performance  

(i.e. still able to control the fixture with a Pico remote? Still able to properly associate the fixture to the 
Vive System? etc.)

 

   

a. If the above yields satisfactory results, the evaluation is done.

 

   

b. If the above yields unsatisfactory results, consult the fixture manufacturer and / or Lutron.

 

 NOTE:

 Lutron recommends as best practice that this information 

be provided with the fixture to the electrical contractor.

Status LED

Important Notes about Initial Fixture 
Power-up:

When power is applied to the fixture, the fixture will run through 
a 10-second self-test described below before normal operating 
mode commences unless the fixture was previously powered for 
an hour or more continuously, or is associated to a Vive hub.

1.  

While the self-test is in progress, the status LED alternates 
between green and red. During the test, the Vive integral fixture 
control will not respond to button presses or commands from 
other Lutron Clear Connect devices. 

2.  

Fixture will turn ON to full intensity for 5 seconds and then will turn 
OFF for 5 seconds. 

3.  Once the self-test is complete: 

A.  If the fixture passes, the status LED blinks green twice, 

repeating every 2 seconds, and the fixture will turn ON. 

B.  If the fixture fails, the status LED blinks red twice, repeating 

every 2 seconds, and the fixture will remain OFF. See 

Important Installation and Startup Notes

 section for 

managing a self-test failure.

4.  

The LED and load state will continue to display the self-test result 
(from #3 above) for 5 minutes unless the button is pressed or until 
the unit is associated to a Vive hub.

Note:

 Do NOT disconnect power to the fixture until the pass/fail 

determination has been made.

5.  

See video at https://youtu.be/LS6MmjqhH2M

  Reset Factory Defaults

  

 

Note:

 In some instances, it may be necessary to reset 

the Fixture Control back to factory default settings. Before 
beginning, make sure the Fixture Control is connected and 
powered.

A

  Rapidly tap the button on the Fixture Control three times and 

hold on the fourth until the green LED begins to flash rapidly; 
release button.

B

  Within 1 second of releasing the button, again rapidly tap the 

button three times and the green LED will flash slowly indicating 
that the unit has been reset to factory defaults.

  

 

Note:

 Any associations or programming previously set up 

with the Fixture Control will be erased and will need to be 
re-programmed. Upon successful completion of Reset Factory 
Defaults, the fixture control will commence with the self-test as 
described above in 

Important Notes about Initial Fixture  

Power-up

.

Programming without a Vive Hub  
(Associating transmitters to Fixture Control)

1.  

Press and hold the button on the Integral Fixture Control for 6 seconds until the load attached to the Fixture 
Control starts flashing (every 2 seconds).

 

 

Note: 

Multiple Fixture Controls can be placed into association mode by repeating Step 1 prior to moving to 

Step 2.

2.  

Hold the indicated button on each transmitter for 6 seconds. The fixture will flash at a different rate than in 
Step 1 to show that wireless transmitters have been associated. Alternatively, for Radio Powr Savr occupancy/
vacancy and daylight sensors, the green laser pointer can be used. See the 

Using a Green Laser to 

Program Lutron Ceiling and Wall-Mounted Devices

 App Note #407 (048407) on www.lutron.com for more 

information. To associate another transmitter, repeat Steps 1 and 2 above.

Test

Link

Step 1

Step 2

Default Sensor Settings for DFCSJ-OEM-OCC (adjustable ONLY via the 
Vive hub user interface unless otherwise noted)

•  Occupancy sensor timeout: 15 minutes

•  Occupancy sensor sensitivity: Medium

•  Mode: Occupancy detection (auto-ON, auto-OFF)

•  

Occupied light level: 100% (note this can also be changed with a Pico remote and Radio Powr Savr sensor. See 
App Note #556 [048556] at www.lutron.com)

• Daylighting: Enabled

•  

Daylighting dims lights to OFF from low light level when sufficient ambient light is present for  
15 minutes or more

Lutron Electronics Co., Inc. 7200 Suter Road
Coopersburg, PA 18036-1299 USA

Please read before installing fixture

041657 
Rev. B
07/2018

DFCSJ-OEM-OCC 

Vive Integral Fixture Control with Sensor

DFCSJ-OEM-RF 

Vive Integral Fixture Control (RF only)

9.5 – 20.5  V

-

250 mA max

IEC  SELV / NEC

R

 Class 2 

UL2043 Plenum Rated

Programming with a Vive Hub

  A

   

Use an iOS

R

 or Android

R

  

compatible device.

  B

   

Download the Lutron  
Vive app.

  C

   

Open the app and follow 
the instructions.

Note:

 For further information on set up, programming, and troubleshooting with a Vive system, please 

refer to the installation instructions included with the Vive hub or visit www.lutron.com/vive

Note:

 For programming the Vive Integral Fixture Control without a Vive Hub see section to the right.

vive.lutron.com

X