Occupancy Sensor
LOS-C Series
Installation Instructions
Description
The LOS-C Series of ceiling-mounted sensors incorporate ultrasonic (CUS), infrared (CIR), and dual
technologies (CDT). They integrate into Lutron
R
systems or function as stand-alone controls using a
Lutron
R
power pack.
Features
• Intelligent, continually adapting sensors
• 20 to 24 V
-
, IEC PELV/NEC
R
, 33 mA nominal
• 450 ft
2
to 2000 ft
2
(42 m
2
to 140 m
2
) coverage, as indicated in model number (when mounted on 8 ft to 12 ft /
2.4 m to 3.7 m ceiling)
• Dry contact closure available on -R models
• LED indicators: Ultrasonic (US)-green, Infrared (IR)-red, Dual Tech (DT)-red and green
• For indoor use only
Coverage and Placement
• The occupant sensor must have an unobstructed view of the room. Do not mount behind or near tall cabinets,
shelves, hanging fixtures, etc.
• For -CIR models, do not place sensor within 4 ft (1.2 m) of air vents, air handlers, windows, fans, etc., as this
may cause false triggering.
• For -CDT and -CUS models, do not place sensor within 6 ft (1.2 m) of air vents, air handlers, windows, fans,
etc., as this may cause false triggering.
• If installing a 180° occupant sensor, place the sensor on the same wall as the doorway so that hallway traffic
will not affect the sensor; otherwise, place in center of room.
• Closely follow the diagrams for major and minor motion coverage.
• Decrease total coverage area by 15% for “soft“ rooms (e.g. heavy draperies or heavy carpeting).
• Indicated range is when unit is mounted on an 8 ft to 12 ft (2.4 m to 3.7 m) ceiling.
(U)LOS-CUS-500 / 1000 / 2000
(U)LOS-CIR-450 / 1500
(U)LOS-CDT-500 / 500R / 1000 / 1000R / 2000 / 2000R
IEC PELV/NEC
R
Class 2 Devices
Model
US Minor Motion
US Major Motion
IR Minor
Motion
IR Major
Motion
CUS-500 *
16 ft x 16 ft (4.9 m x 4.9 m)
22 ft x 22 ft (6.7 m x 6.7 m)
NA
NA
CUS-1000 *
23 ft x 23 ft (7.0 m x 7.0 m)
32 ft x 32 ft (9.8 m x 9.8 m)
NA
NA
CUS-2000 **
23 ft x 45 ft (7.0 m x 13.7 m)
32 ft x 64 ft (9.8 m x 19.8 m)
NA
NA
CIR-450 **
NA
NA
6.5 ft (1.9 m)
12 ft (3.7 m)
CIR-1500 **
NA
NA
12 ft (3.7 m)
22 ft (6.7 m)
CDT-500 *
23 ft x 16 ft (7.0 m x 4.9 m)
32 ft x 22 ft (9.8 m x 6.7 m)
12 ft (3.7 m)
22 ft (6.7 m)
CDT-1000 *
23 ft x 23 ft (7.0 m x 7.0 m)
32 ft x 32 ft (9.8 m x 9.8 m)
12 ft (3.7 m)
22 ft (6.7 m)
CDT-2000 **
23 ft x 45 ft (7.0 m x 13.7 m)
32 ft x 64 ft (9.8 m x 19.8 m)
12 ft (3.7 m)
22 ft (6.7 m)
Range Diagram and Dimensions
US Major Motion
US Minor Motion
US
Minor
Motion
US
Major
Motion
IR Minor Motion
IR Major Motion
US -
Ultrasonic
IR -
Infrared