Installation and Operating Manual
Radio module UNI-EO
- Please pass on to the user -
I EN
About this manual
Read this manual carefully and completely before assembly! Always observe
the general safety instructions and the safety symbols with information in the
text.
Hand out this manual to the user (tenants, proprietors, property management
etc.) after completing assembly.
Caution!
Any assembly work may only be carried out after dis-
connecting the supply voltage!
This symbol warns you against risks of injury
This symbol warns you against risks of injury from electricity
Safety instructions
Attention!
The electric connection may only be made by authorised
qualified personnel and according to the applicable version of VDE 0100!
Disposal
The packaging must be sorted before disposal. If you wish to dispose of
the ventilation device, observe the currently applicable regulations.
Pursuant to the German Electrical and Electronic Equipment Act
(ElektroG) this device can be returned to your municipal collection point
free of charge.
Operating voltage:
3.3V DC
Power consumption (module) :
< 1W
Radio frequency:
868 MHz
Range:
up to 40 meters (free field)
Operating temperature:
0°C / 40°C
EPP profile:
D2-50 (for coupling with radio control centre)
Dimensions:
44mm x 23mm x 13mm
Technical data UNI-EO
Installation on the universal control 5/UNI-FT
DIP-switches - Display
DIP switches - Description
Coupling mode
To teach further radio components to the radio module UNI-EO, it must be set
to coupling mode. To do this, press and hold the button for 5 seconds. To
simplify matters, the LED lights up green every second during this time. Re-
lease the button after 5s. The module is now in coupling mode, indicated by
the red LED lighting up every second.
The coupling mode is automatically terminated after 30 s if no coupling pro-
cess has taken place.
Radio remote control RC-EO
For coupling the RC-EO radio remote control, set the UNI-EO module to
coupling mode as described above. Then press the "+" button on the RC-EO
three times within 2 seconds. If the coupling process was successful, the red
LED will stop lighting and the green LED will confirm the process by lighting
up five times.
Humidity and temperature sensor SFT-EO
1 2 3 4
ON
DIP-Schalter
DIP switch 1:
ON: Slave mode
OFF: Stand-alone operation (standard)
DIP 1 must be set before commission-
ing!
DIP switch 2:
ON: Outdoor sensor
OFF: Indoor sensor (standard)
DIP switch 3:
ON: Radio master
OFF: - (standard)
DIP switch 4:
ON: Transmit mode
OFF: Receive mode (standard)
DIP switch 1:
In stand-alone mode, buttons / sensors / other fans can be coupled as signal trans-
mitters. Slave mode only in connection with a SmartHome central unit or a 5/UNI-FT
with UNI-EO module in Master mode (see DIP 3)
DIP switch 2:
Used to teach additional sensors (see teaching SFT-EO)
DIP switch 3:
Configured as radio master, the module transmits the switched stage and the opera-
ting mode (heat recovery or summer ventilation ) to coupled UNI-EO modules with
Slave mode setting (see DIP 1). The reversing time is synchronised cyclically.
DIP switch 4:
If an exhaust fan (e.g. RA 15-60 or E
go
) is connected to the universal control 5/UNI-
FT, the radio module will transmit the operating stage to coupled UNI-EO or FM-EO
radio modules in order to actively convey supply air.
Stage +1
Stage -1
Activate
humidity-controlled
automatic mode
Deactivate
humidity-controlled
automatic mode
The summer ventilation is activated by simultaneously pressing the buttons
"+" and "l" and deactivated by simultaneously pressing "-" and "o".
The filter is reset by pressing the "-" button five times within 5 seconds while
fan stage 0 is active.
For coupling, the housing of the SFT-EO sensor must be opened. To do this,
loosen the two screws on the bottom.
Only one indoor and one outdoor sensor can be coupled per UNI-EO module.
DIP switch 2 of the UNI-EO must be set to ON (outdoor sensor) or OFF
(indoor sensor) and the module must be set to coupling mode as described
above.
To couple the SFT-EO sensor, press the button on the bottom of the solar cell
one time. If the process is successful, the red LED of the UNI-EO will stop
lighting and the green LED will confirm the process by lighting up five times.
The humidity and temperature sensor of the 5/UNI-FT is still active even
when the indoor sensor is coupled. In automatic mode, the higher humidity
value of the two sensors is used for control operation.
If an outdoor sensor is connected, the difference between indoor and outdoor
air humidity above 50% RH in the interior is used for intelligent control.
button
DIP-switches
LED green
LED red
radio module
antenna
The radio module is plugged onto
the 6-pole connector of the 5/UNI-
FT. Make sure that all poles are
correctly connected.
When installing in the flush-
mounted box, the antenna should
be positioned in the direction of the
opening, if possible.
If a switch is installed on the control
at the same time, it must always
have priority. The operating mode
Slave is excepted.