background image

ROUTINE TEST RECORD

Type Test

Year 1

Year 2

Year 3

Year 4

Year 5

 

Signed

Date

Signed

Date

Signed

Date

Signed

Date

Signed

Date

Functional 1
Functional 2
Functional 3
Functional 4
Functional 5
Functional 6
Functional 7
Functional 8
Functional 9

Functional 10
Functional 11

3hr Duration 12

Installation Engineers Contact Details:

Luminaire Reference / Location

Name:

Tel:

Luminaire Details:

Full Recharge Duration 

24 Hours

Emergency Duration 

3 Hours

Lamp Type 

LED

Wraysbury 1200 x 600 Panel

Technical Helpline: +44 (0)1507 328031

Part No.

Description

Watts L

 (mm)

W

 (mm)

H

 (mm)

Weight

430116

Wraysbury 1200 x 600 

TP(a) - 4000K

48W

595

1195

38

4.2Kg

430117

Wraysbury 1200 x 600 

TP(a) - 6000K

48W

595

1195

38

4.2Kg

WRAYSBURY DIMENSIONS

L (mm)

H (mm)

W (mm)

1.   The installation of an emergency fitting MUST BE  

  CONNECTED AS SHOWN in diagrams below.
2.  For the emergency unit to operate correctly the permanent 

  live feed must not be interrupted. Note: Ensure no lighting 

  controls are on the permanent Live feed, such as PIR’s or 

  SWITCHES, failing to observe this will reduce the batteries 

  lifetime of the emergency pack considerably.
3.  After switching on an emergency equipped unit, the LED 

  indicator should illuminate this is to indicate battery  

 charging.
4.  Should power to an emergency equipped unit be  

  disrupted or isolated, the indicating LED will switch off, 

  triggering the emergency function illuminating the LED’s
5.  The backup battery must be charged for 24 hours before  

  a full duration test.

Wiring instructions for units equipped  

an with EMERGENCY function

If the LED Driver & Downlight jack leads do not match the gender as in 

diagram, please use provided gender changing leads to correct.

Emergency lighting luminaries must be installed and 

maintained in accordance with the emergency lighting 

standard BS 5266-1

This product contains a light source of energy efficiency Class E.

The self-test version of emergency is fitted with control gear that will carry out  

periodic functional tests every 1 month and full duration test every 12 months. 

Self-Test EMERGENCY function

Fault/Test/Status

Reason

Battery fully charged  

and operational

Standard daily use

Battery Charging

Initial charge /  

battery topping up

Battery Failure

Battery is disconnected or 

damaged/faulty

Duration Test Failure

Maintenance check required  

by qualified engineer

Automatic Testing - Function  

5 minute test (Every 30 days)

Self-testing in  

operation

Automatic Testing -   

Duration test is 3 hours  

(every 12 months)

Self-testing in  

operation

Charge Indicator Status

Battery Fully Charged 

and Operational

Battery Charging

Auto Test 

5 Min

 

(every 30 days)

Auto Test 

3 Hours 

(every 12 months)

Duration Test Failure

1 Sec ON

1 Sec OFF

3 Sec ON

3 Sec OFF

3 Sec ON

1 Sec OFF

0.5 Sec ON

0.5 Sec OFF

Battery  

Disconnected/Faulty

This luminaire is warranted for a 

period of 5 years from the date of 

purchase**.

 The backup battery  

pack in the emergency version 

is warranted for a period of 12 

months. The warranty could be 

invalidated should the light fitting 

not be installed according to these 

instructions, outside the scope of 

the specification or the product 

has been altered or tampered with 

in any way. Please see website for  

terms and conditions.  

Standard 

0 to +40ºC

Emergency  0 to +30ºC

DISPOSAL

WARRANTY

PRODUCT TEMP SPECIFICATION

Revision 2 - February 2022

The light source of this unit is not  

replaceable; when the light source  

reaches its end of life the whole  

luminaire shall be replaced.
Disassemble instructions for end of 

life disposal available on website.
Disposal of Electronic Equipment 

WEEE Directive 2002/96/EC This 

product falls within the scope of 

the Waste Electrical & Electronic 

Equipment Directive (WEEE), which 

means the product should not be 

disposed of as normal household 

waste. Please recycle where  

facilities exist or check with your 

Local Authority.  RoHS – All  

components and materials used in 

this product are RoHS 2002/95/EC 

compliant.
Specifications may change from time 

to time. The information contained 

in this leaflet is for guidance only 

and should not be considered as  

always accurate and should be  

treated as not representative.

** Please see our website for more detailed information on warranty.