26
10. TECHNICAL DATA
Input signals
acc. 3
Input signals and measuring ranges for inputs
Table 3
Sensor type/inputs
Marking
Range
Basic error
[°C]
[°C]
Pt100
acc.to EN 60751+A2
Pt100
-50...100
0.8
Pt100
Pt100
0...250
1.3
Pt100
Pt100
0...600
3.0
Fe-CuNi
acc.to EN 60584-1
J
0...250
3.0
Fe-CuNi
J
0...600
4.0
Fe-CuNi
J
0...900
5.0
NiCr-NiAl
acc.to EN 60584-1
K
0...600
4.0
NiCr-NiAl
K
0...900
5.0
NiCr-NiAl
K
0...1300
6.0
PtRh10-Pt
acc.to EN 60584-1
S
0...1600
7.0
Current flowing
through Pt100
220
m
A
Measurement time
0,5 s
Detection of error in
the measuring circuit:
- thermocouple, Pt100
overflow of the measuring range
Kinds of outputs:
- relay
voltageless make contacts
maximal load:
voltage: 250 V a.c., 150 V d.c.
current: 5 A 250 V a.c., 5 A 30 V d.c.
resistance load: 1250 VA, 150 W
- logic voltage
napiêcie 5 V
(without isolation from the sensor side)
resistance limiting the current: 66
W
Содержание RE60