6.7. Emergency restoration of default parameters
In case when standard communication parameters have been changed
and the new confi guration has been lost, one can set temporary on the
transducer plate communication parameters by means of the jumper
marked with the symbol ZW:
• transducer address 247
• baud rate 9600kb/s
• mode
RTU 8N2
After removing the jumper, the transducer returns to previous settings
or to settings changed during the operation with the jumper.
7022
7511
min DP
r
o
C
Min. Dew point
7024
7512
max DP
r
o
C
Max. Dew point
7026
7513
-
-
-
7028
7514
-
-
-
7030
7515
min RH
r
%
Min relative humidity
7032
7516
max RH
r
%
Max relative humidity
7034
7517
min AH
r
g/m
3
Min. absolute humidity
7036
7518
max AH
r
g/m
3
Max. absolute humidity
Fig. 10. Placement of the Jumper Setting Temporary
Communication Parameters.