2-14
Issue 5
May 1997
363-208-010
Installation Procedures
ARM Shelf Installation
NOTE
:
Only one ARM shelf can be installed in the RT Bay. The shelf must be
located at the specific location depicted in the figure even if only one MDS
shelf is provided.
For ease of assembly the Power Interface Unit (PIU) should be mounted on
the ARM shelf before the shelf is mounted to its bay position.
404A User Interface Panel (UIP)
NOTE
:
This unit is considered a plug-in and shall be installed in accordance with
the instructions detailed in the User Service Manual (Lucent Technologies
363-208-001, DLP-518).
ED7C734-30 PIU Mounting Procedure
Step 1:
Open the cartons to the ARM shelf and the PIU and inspect the contents
especially the connectors and cable assemblies for damage or misalign-
ment.
Step 2:
Refer to Figure 2-6 and mount the PIU to the ARM shelf as follows:
a. Using the three screws provided, fasten the PIU hinge to the right
side of the ARM shelf from the inside of the shelf.
b. Temporarily close the hinged door by finger-tightening the attached
knurled screw head into the ARM shelf.
c. Verify that the attached cables drape downward and are not entan-
gled.
P103
P202
P104
P203
P204
Left Duct
Right Duct
Содержание SLC-2000 Access System Central Office Terminal
Страница 1: ...SLC 2000 Access System Customer Assembly Manual for RT Frames 363 208 010 Issue 5 May 1997...
Страница 4: ...This page is intentionally blank...
Страница 10: ...viii Issue 5 May 1997 Contents...
Страница 16: ...xiv Issue 5 May 1997 Tables...
Страница 24: ...1 ii Issue 5 May 1997 Contents General Information...
Страница 34: ...2 iv Issue 5 May 1997 Tables Installation Procedures 2 1 Dimensions for Figure 2 2 6...
Страница 66: ...3 viii Issue 5 May 1997 Contents Cabling Wiring and Assembly...