Lucent Technologies Lineage
®
2000 ECS-12 Controller J85501D-2
4 - 10 Installation and Setup
Issue 3 August 1998
Wiring
Each circuit pack in the controller may require connection to
systems outside the power plant or to other parts of the power
system. The user must provide these connections.
Basic Controller
The installer wiring associated with the basic controller is
connected to four removable terminal blocks on the 113B
Control Unit. The types of signals on these terminal blocks fall
into four categories:
•
Alarm Outputs (BD, HV, ACF, LV, MJF, MNF, PMJs, and
PMNs)
•
Alarm Inputs (RMJ, RMN, and OS)
•
Control Inputs (TEQ, TEL, TF/ER, and TRs)
•
Miscellaneous Outputs (ABS and DG)
Three of the four terminal blocks (TB102, TB103, and TB104)
are assigned to the various office alarm outputs from the
controller. Terminal block TB101 has the connection points for
the remaining three categories of office interfaces. The signal on
each terminal is indicated on the label inside the controller front
panel.
Table 4-D: Terminal Block Pin Assignments
for LVD/Fuse Board
Pin
No.
Designation Definition
TB501-1
CBA
Plant Distribution Circuit
Breaker Alarm
TB501-2
EMJF1
External Major Fuse Alarm
TB501-3
EMNF1
External Minor Fuse Alarm
TB501-4
EMJF2
External Major Fuse Alarm
TB501-5
EMNF2
External Minor Fuse Alarm
TB501-6
Low power distribution via
F519
TB501-7
Low power distribution via
F520
TB501-8
Low power distribution via
F521
TB501-9
Spare
No connection
TB501-10
Spare
No connection
TB501-11
Spare
No connection
TB501-12
Spare
No connection