Product Description
General
Description
The H569-418 Battery Switch Bay can come equipped with up
to six ED83134-30 panels (600-2000 Ampere Switch and Fuse).
These switch and fuse panels have the capacity to carry and
switch up to 2000 amperes at up to 65 volts dc.
Each switch and fuse unit comes mounted in a 12-inch panel. A
protective clear cover protects users from electrical contact.
Rear access busbars allow cable connections.
You may order the ED83134-30 switch and fuse panel as either
Group 1 or Group 2. Group 1 panels use fuses ranging from 600
to 1200 amperes, while Group 2 panels uses fuses ranging from
1000 to 2000 amperes. Group 1 comes equipped with a 1200
ampere shunt and Group 2 comes equipped with a 2000 ampere
shunt for current monitoring.
Features
The following features are provided with this product:
•
Distributes or switches ± 24VDC and ± 48VDC
•
Single pole, double throw switch
•
Compact size allows six units to be mounted in one H569-
418 bay
•
Accommodates fuses ranging from 600 to 2000 amps
•
Fuse operation generates visual alarm within the unit
•
Remote access for monitoring alarm conditions through
controller
•
1200 or 2000 ampere monitoring shunts
•
Rear access for cabling
•
Cable entry from top or bottom of cabinet
•
Allows connection of cable sizes from 4/0 to 750MCM
•
Protective front and rear clear covers
•
Front access for fuse replacement