© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED
FUIF511-27D_DBL_LST_EN_0804.PDF • PAGE 1
A
Building Safety. Building Security.
• Up to 32 radio detectors can be
controlled
• Radio detectors can be assigned to 2
detector zones
• Individual detector identifi cation
display via 32 LEDs
• High range of radio transmission
• Two frequency bands (868/434MHz)
with automatic change-over
• Channel checked for availability
Description
Specifi cations
Mains voltage
10/-15%, 50Hz
Connection power
12VA
External supply voltage (supply through external power unit)
10 – 30VDC
Current consumption at 12V (supply through external power unit)
max. 110mA (quiescent), 120mA (alarm)
Range of radio transmission (free air)
400m
Frequency band
868MHz or 434MHz
Ambient temperature
0°C to +60°C
Dimensions W × H × D
300 × 390 × 140 (mm)
Colour
white
Weight (without battery)
8.7kg
Approval
VdS G206015
Order number
249201
Order name
RF Interface/4Rel FUIF511-27D
The RF Interface FUIF511-27D serves for the connec-
tion of up to 32 automatic or manual radio detectors.
The interface is provided with two detector zones, each
of them having separate alarm and fault detection re-
lays. Up to 16 detectors can be assigned to each zone.
The two zones can be reported to the fi re detection
control panel as collective messages, either in conven-
tional technology or by means of auxiliary modules via
the ADM loop. After an alarm activation the RF interface
can be reset by the fi re detection control panel, via the
remote reset input.
The detectors are programmed (learned) at the RF inter-
face by using built-in keys. For each radio component
the receiver unit provides an individual LED indicator.
If necessary, several radio detection systems can be
used in the same building, in order to integrate more
than 32 radio components or to create more than 2
detector zones. A unique key, based on a choice of
several million codes, is created, which ensures the
unambiguous identifi cation of the detectors.
The RF Interface FUIF511-27D is equipped with a power
unit and can be protected against a power failure by
means of a stand-by battery 7Ah. It is also possible to
use an external power supply.