• Connect a wired EN54-4 compliant PSU to the appropriate
two terminals.
• There are also terminals for Fault Monitoring using a feed.
• You can now apply power to the EN54-4 compliant PSU.
7
9
8
10
Ensure the LED indicates that the discovery mode
is enabled, alternating green and yellow colors.
To benefit from the remote commissioning mode, ensure
you leave the Expander in “discovery” mode. Using the keypad
and the display system:
• Press “select” button.
• Insert level 1 password (default 0001), using the arrow buttons
and confirming with “select” button.
• Select “Expander Config” using the arrow buttons
and press “select” button.
• Select “Set Discovery Mode” using the arrow buttons
and press “select” button.
• Insert level 2 password (default 0002) using the arrow buttons
and confirm with “select” button.
• Select discovery channel A (or B or C depending on survey
results) using the arrow buttons and confirm with “select” button.
• Press “select” button to start “discovery” mode as shown on the screen.
• Press “select” button again to confirm.
• Screw the lid to the back box using the supplied plastic
screws and refit top and bottom front plastics that cover
screw housings.
• Put the QR code available in the box either on the system
map or on the dedicated pages at the end of expander
manual.
GREEN LED
YELLOW LED
DISPLAY
LEFT
DOWN
RIGHT EXIT SELECT
UP
MAINS FAULT
PULL-UP TO 3V3
BATTERY FAULT
BATTERY
CHARGER FAULT
BATTERY O/C
ext. power (
-
)
ext. power (
+
)
QUICK START GUIDE
FI750/RF/WE
WIRELESS EXPANDER