background image

• Connect a wired EN54-4 compliant PSU to the appropriate

two terminals.                                                                                                             

• There are also terminals for Fault Monitoring using a feed.
• You can now apply power to the EN54-4 compliant PSU.

7

9

8

10

Ensure the LED indicates that the discovery mode 
is enabled, alternating green and yellow colors.

To benefit from the remote commissioning mode, ensure 
you leave the Expander in “discovery” mode. Using the keypad 
and the display system:

• Press “select” button. 
• Insert level 1 password (default 0001), using the arrow buttons

and confirming with “select” button.

• Select “Expander Config” using the arrow buttons 

and press “select” button.

• Select “Set Discovery Mode” using the arrow buttons 

and press “select” button.

• Insert level 2 password (default 0002) using the arrow buttons 

and confirm with “select” button.

• Select discovery channel A (or B or C depending on survey

results) using the arrow buttons and confirm with “select” button.

• Press “select” button to start “discovery” mode as shown on the screen. 
• Press “select” button again to confirm.

• Screw the lid to the back box using the supplied plastic

screws and refit top and bottom front plastics that cover
screw housings.

• Put the QR code available in the box either on the system

map or on the dedicated pages at the end of  expander 
manual.

GREEN LED

YELLOW LED

DISPLAY

LEFT

DOWN

RIGHT EXIT SELECT

UP

MAINS FAULT

PULL-UP TO 3V3

BATTERY FAULT

BATTERY

CHARGER FAULT

BATTERY O/C

ext. power (

-

)

ext. power (

+

)

QUICK START GUIDE

FI750/RF/WE

WIRELESS EXPANDER

FI750-RF-WE_IA_EN--2020--Installationsanleitung.pdf