![LST BC016 Series Скачать руководство пользователя страница 179](http://html1.mh-extra.com/html/lst/bc016-series/bc016-series_user-manual_1944502179.webp)
Connection of detectors Labor Strauss
Chapter 3 • ADM technology
179
3.12.11 Sounder(-Strobe) FI700/WB/MT/SOUW - FI700/WB/MT/SOUW/STRC
If this sounder is used on the BC216, three tones according to Chapter 3.12.11.2: „Tone setting“ are
available. On the BC600, this sounder can be parameterised [FI7x0/WB/MT (32 tone)] to the full extent
as regards the sound level and the tones. Therefore you can choose from among 32 tones. Tone 0 which
is mentioned in the enclosed packet corresponds to tone 32 (PARSOFT).
If the product is to be used without tone emission, tone 32 is to be selected. With this method, the
sounder-strobe's tone emission can be suppressed.
3.12.11.1 Connection
3.12.11.2 Tone setting
To set the tone, a Programming Unit FI700/PU or FI750/PU with software revision 2.4L or higher must
be used.
In the FI700/PU or FI750/PU menu „Set Mod/Set Op“, the operation mode / the sound level is set.
Operation Mode
Sound level
2
Low – 84.5dB(A)
66
Medium – 88.9dB(A)
130
High – 90.3dB(A)
194
Very high – 92.5dB(A)
According to this setting, the following tones are available for selection on the fire detection control
panel. The tone is defined by parameterising the element.
Setting in PARSOFT
Frequency [Hz]
Repetition
Application
Sound A
500 – 1200
3.5s increasing, 0.5s silent
Slow whoop tone
Sound B
1200 – 500
1Hz
DIN tone
Sound C
1000
Continuous tone
Continuous tone
Connection-LST.odt / 2009 / AN9161298
200/179
179