LST 5251EM Скачать руководство пользователя страница 2

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED

5251EM_DBL_LST_EN_0804.PDF • PAGE 2

A

Building Safety. Building Security.

Specifi cations

Operating voltage 

Supply through loop voltage

Current consumption  

max. 200µA (quiescent)

Alarm temperature  

    Class A1S 

typ. 58°C (maximum principle), max. room height 7.5m

    Class A1R 

typ. 58°C (rate-of-rise principle), max. room height 7.5m

    Class BS 

typ. 78°C (maximum principle), max. room height 6m

Operating temperature 

    Classes A1S and A1R 

max. +45°C

    Class BS 

max. +68°C

Ambient temperature 

-20°C to +60°C (continuous operation)

Relative humidity 

10 – 93% (no condensation)

Dimensions ø × H 

102 × 51 (mm)

Colour 

cream

Weight 

102g

Approval 

VdS G200094

Order number 

242002

Order name 

Thermal Detector/Anal./200/SS 5251EM