background image

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED

2351E_DBL_LST_EN_0804.PDF • PAGE 1

A

Building Safety. Building Security.

Description

The Optical Smoke Detector 2351E uses the scattered 

light principle, and was developed for the detection of 

smoke particles in a wide range of fi re detection applica-

tions. The modern design of the measurement chamber 

allows to reliably evaluate the characteristics of fi re.

An internal drift compensation adjusts the alarm thres-

hold by continually evaluating the contamination of the 

detector. With that, the sensitivity of the detector is kept 

constant for a long time.

Addressable conventional technology is used for alarm 

transmission to the fi re detection control panel. The de-

tector addressing can be achieved in 2 ways:

•   A detector with an Address Module NG58-1 can be 

individually identifi ed by the suitable control panel.

•   An address, which has been stored in the detector by 

means of the Remote Programming and Test Unit, is 

displayed on the Zonal Display Unit S300ZDU. 

 

A  test  activation  of  the  detector  can  be  carried  out 

using the Remote Test Unit ECO1000RTU. In addition to 

the test activation of the detector, the Remote Program-

ming and Test Unit S300RPTU can also be used to set 

and display the following detector parameters:

•  the sensitivity in 3 levels,

•  the detector address, and

•  the date of the previous maintenance.

Furthermore, the degree of drift compensation (detec-

tor contamination) and the current condition of the de-

tector can be read out.

The detector can be attached to various detector bases 

and it can be protected against theft.

•   Addressable conventional technology
•   Sensitivity selectable in 3 steps
•   Addressing by means of address 

module or detector parameterisation

•   Remote readout of detector condition
•   Extremely fl at design
•   Function testable with Remote Test 

Unit ECO1000RTU

Specifi cations

Operating voltage 

Supply through the detector line voltage

Current consumption 

typ. 75µA (quiescent)

Ambient temperature 

-30°C to +70°C

Relative humidity 

5 – 95% (no condensation)

Dimensions ø × H 

102 × 32.5 (mm)

Colour 

cream

Weight 

75g

Approval 

VdS G202012

Order number 

241040

Order name 

Optical Smoke Detector/Conv./300/SS 2351E