background image

 

 

Right choice for ultimate yield 

LSIS strives to maximize customers' profit in gratitude of choosing us for your partner. 

Programmable Logic Controller 

  XGT FEnet I/F Module

 

User’s Manual

 

 

Read this manual  carefully before 
installing,  wiring, operating, servicing 
or inspecting this equipment.   

 

 

Keep this manual within easy reach 
for quick reference. 

XGL-EFMT(B) 

XGL-EFMF(B) 

XGL-EH5T

 

XGT Series

 

 

http://eng.lsis.biz 

Содержание XGL-EFMF

Страница 1: ...us for your partner Programmable Logic Controller XGT FEnet I F Module User s Manual Read this manual carefully before installing wiring operating servicing or inspecting this equipment Keep this manual within easy reach for quick reference XGL EFMT B XGL EFMF B XGL EH5T XGT Series http eng lsis biz ...

Страница 2: ...me applicable instruction is violated This symbol indicates the possibility of severe or slight injury and property damages if some applicable instruction is violated Moreover even classified events under its caution category may develop into serious accidents relying on situations Therefore we strongly advise users to observe all precautions properly just like warnings The marks displayed on the ...

Страница 3: ...ut signals are designed to be turned off and stopped for safety However there are cases when output signals remain active due to device failures in Relay and TR which can t be detected Thus you are recommended to install an addition circuit to monitor the output status for those critical outputs which may cause significant problems 2 Never overload more than rated current of output module nor allo...

Страница 4: ...PLC power is off If not electric shock or damage on the product may be caused 3 Be sure that every module is securely attached after adding a module or an extension connector If the product is installed loosely or incorrectly abnormal operation error or dropping may be caused In addition contact failures under poor cable installation will be causing malfunctions as well 4 Be sure that screws get t...

Страница 5: ...s 2 Secure terminal screws tightly applying with specified torque If the screws get loose short circuit fire or abnormal operation may be caused Securing screws too tightly will cause damages to the module or malfunctions short circuit and dropping 3 Be sure to earth to the ground using Class 3 wires for FG terminals which is exclusively used for PLC If the terminals not grounded correctly abnorma...

Страница 6: ... installing or disassembling the module let all the external power off including PLC power If not electric shock or abnormal operation may occur 3 Keep any wireless equipment such as walkie talkie or cell phones at least 30cm away from PLC If not abnormal operation may be caused 4 When making a modification on programs or using run to modify functions under PLC operations read and comprehend all c...

Страница 7: ...Safety Instructions Safety Instructions for waste disposal Product or battery waste shall be processed as industrial waste The waste may discharge toxic materials or explode itself Caution ...

Страница 8: ...odifying Overview 2 Adding CPU 3 Adding contents on standard setting One IP Solution DHCP CH1 2 1 CH1 3 2 CH5 3 V1 7 2011 05 1 How to enable link through flag added 2 Write_NC Send_NC instruction added CH5 5 2 CH7 2 1 V1 8 2013 10 1 Adding Communication load specifications 2 Changing Modbus server offset area CH2 2 3 CH8 3 1 V1 9 2014 03 1 Changing Communication load specifications 2 Adding info U...

Страница 9: ...ow to use instructions that are used PLC system with XGK XGB CPU XGI XGR Instructions Programming User s Manual User s manual for programming to explain how to use instructions that are used PLC system with XGI XGR CPU XGK CPU User s Manual XGK CPUU CPUH CPUA CPUS CPUE CPUSN CPUHN CPUUN XGK CPUU CPUH CPUA CPUS CPUE CPUSN CPUHN CPUUN user manual describing about XGK CPU module power module base IO ...

Страница 10: ...5 1 4 2 XG5000 1 7 1 4 3 Version checking 1 7 Chapter 2 Product Specifications 2 1 General Specifications 2 1 2 2 Performance Specifications 2 2 2 2 1 XGL EFMT B EFMF B 2 2 2 2 2 XGL EH5T 2 2 2 2 3 Specification of Communication load amount 2 4 2 3 Structure and Characteristics 2 5 2 3 1 Structure of XGL EFMT B EFMF B 2 5 2 3 2 Structure of XGL EH5T module 2 8 2 4 Cable Specifications 2 9 2 4 1 UT...

Страница 11: ...ork and dedicated network system composed of LSIS and other company s PLCs 4 4 4 1 6 System configuration using dedicated Ethernet between HMIs PLCs at XGR system 4 5 4 1 7 System configuration using dedicated Ethernet between HMIs PLCs at XGR system 4 6 Chapter 5 XG5000 Program 5 1 Introduction 5 1 5 2 Basic Settings 5 2 5 2 1 PLC type setting 5 2 5 2 2 Register of communication module 5 3 5 2 3 ...

Страница 12: ...work 6 15 6 6 2 Monitor of High speed link information 6 17 6 7 High Speed Link at Redundant system 6 18 6 7 1 In case of redundant system 6 18 6 7 2 In case of single network 6 25 Chapter 7 P2P Service 7 1 Introduction 7 1 7 1 1 Introduction to P2P service 7 1 7 1 2 Configuration of P2P parameters 7 2 7 2 Type of P2P Service 7 3 7 2 1 Type of P2P Instructions 7 3 7 2 2 Type of P2P Service 7 4 7 3...

Страница 13: ... 9 2 1 Remote 1 connection If RS 232C cable used 9 3 9 2 2 Remote 2 connection If RS 232C cable is used for local connection 9 6 9 2 3 Remote 1 connection directly from PC connected with Ethernet 9 8 9 2 4 Remote 2 connection directly from PC connected with Ethernet 9 10 Chapter 10 Troubleshooting 10 1 Check through communication module LED 10 1 10 1 1 Abnormal operation display XGL EFMT EFMF 10 1...

Страница 14: ...1 Specifications applicable to XGT series 11 4 11 2 2 Selection of XGT series PLC 11 4 Appendix A 1 XGT CPU Memory Device List A 1 A 1 1 Device of XGK CPU A 1 A 1 2 Device of XGI CPU A 2 A 1 3 Device of XGR CPU A 2 A 2 Terminology A 3 A 3 List of Flags A 8 A 3 1 List of Special Relays F A 8 A 3 2 List of Communication Relays L A 16 A 4 ASCII Code Table A 22 A 5 Comparison Table of Ethernet Technol...

Страница 15: ...data can be transferred with high speed FEnet I F module is an interface module to communicate data between higher level system such as host PC and PLC or between PLCs with electric optical media 10BASE T 100BASE TX 1000BASE T 100BASE FX 1000X Fig 1 1 1 Configuration diagram of FEnet system FEnet I F module has variety applicable communication systems Refer to Chapter 4 System Configuration for de...

Страница 16: ...e through Dynamic Connection 10BASE T 100BASE TX 1000BASE T 100BASE FX 1000X media supported Data is accessible via the public network LS protocol XGT and other company s protocol MODBUS TCP supported dedicated service Convenient client function supported for communication between LSIS PLCs and for communication with other company s Ethernet device XGT Modbus TCP P2P client function Dynamic IP sup...

Страница 17: ... to install at XGT base It doesn t need a external power source and can be installed at XGT base Compact size for easy installation 2 Reliability applying to industrial standard It passed the noise environment test based our company standard comparing other switches 3 Built in Auto Cross Over function For convenience of wiring 4 High speed link function is guaranteed It canceled Broadcast storm fu...

Страница 18: ... but its baud rate will be limited to 10Mbps Pay attention to installation of the system 3 XGL EH5T can be installed on XGT base and used as switch without specific program It has maximum 100Mbps speed 1 3 2 Available units to be installed on each CPU The maximum installation number of modules based on CPU type of each FEnet I F module is described in the table below After due consideration of the...

Страница 19: ...ation Programming tool and Frame Setting XGL EFMT B 10BASE T 100BASE TX 1000BASE T XG5000 XGL EFMF B 100BASE FX 1000X XGL EH5T Switch No relation 2 CPU version to use FEnet I F module Section Section Available version recommended Reference XGK series XGK CPUH V4 55 XGK CPUS V4 55 XGK CPUA V4 55 XGK CPUE V4 55 XGK CPUU V4 55 XGK CPUSN V1 05 XGK CPUHN V1 05 XGK CPUUN V1 05 XGI series XGI CPUU D V4 0...

Страница 20: ...er to get the applicable installation CD ROM to use Internet web site http www lsis com 2 RS 232C and USB port of CPU module is available for downloading the program made by XG5000 and communication configuration made by XG5000 Refer to CPU or XG5000 manual for connection diagram of each cable 3 At the lower version than above table some function may not work properly Check the version before usin...

Страница 21: ...g Prior to use of FEnet I F module please check the version of the applicable module 1 Through XG5000 Connect with communication module directly via on line so to read information of the communication module If interface status with CPU is normal the information will be acquired as shown below a Execute XG5000 b Use on line connection with CPU c If connection between XG5000 and CPU is established ...

Страница 22: ...ch communication module product information of the module is printed The version can be checked module may be removed and then installed if on line checking is unavailable due to unavailable external connection device with PC The label is adhered to the back of the product where designation and version information of the product are described ...

Страница 23: ...ischarge Voltage 4kV Contact discharge IEC61131 2 IEC61000 4 2 Radiated electromagnetic field noise 80 1000 MHz 10V m IEC61131 2 IEC61000 4 3 Fast transient Burst noise Classific ation Power supply Digital Analog Input Output Communication Interface IEC61131 2 IEC61000 4 4 Voltage 2kV 1kV 8 Operation ambience Free from corrosive gases and excessive dust 9 Altitude Less than 2 000m 10 Pollution deg...

Страница 24: ... Mbps 100Mbps 100 1000Mbp s Transmission Type Base Band Max extended length between nodes 100m Node Hub 2km Max segment length Max number of nodes Hub connection Up to 9 recommended 30 Segments Distance between nodes Integral times of 0 5m Max protocol size 1 500 Byte Access method to service zone CSMA CD Frame error check CRC 16 X15 X14 X13 X2 X 1 Basic Specification Current consumption 5V 100 Mb...

Страница 25: ...bps Port type and number 10 100BASE TX TP cable RJ 45 socket 5 port Comm Interface Auto Crossing Auto Nego Auto Polirity Transmission length 100m Node interval Diagnosis LED PWR power Link Status Data Basic Specification 5V side consumption current mA 550 Weight g 90 Table 2 2 2 Performance Specification of FEnet switch module ...

Страница 26: ...agnosis media information packet sec Symptoms of FEnet module when exceeding max load amount communication error diagnosis service error connection error If receive block is not set in high speed link parameter interrupt still occur It might be influenced by load amount Symptoms of exceeding max load amount set communication period in FEnet module which high speed link transmission is set longer t...

Страница 27: ...rks properly In case initialization is done successfully LED is on In case initialization is not normal or done abnormally LED is off I F Indicates whether FEnet I F module interface with CPU or not In case of normal LED flickers In case of abnormal LED holds on or off HS Indicates whether High speed link service is normal or not In case HS link setting is done service is enabled and service is ex...

Страница 28: ...tom service center TX Indicates whether FEnet I F module is transmitting or not In case of transmission LED is on When transmission and stop is repeated LED will flicker RX Indicates whether FEnet I F module is receiving or not In case of transmission LED is on When transmission and stop is repeated LED will flicker PHY Indicates speed of media In case of 100Mbps LED is on In case of 10Mbps LED is...

Страница 29: ... connected LED is on If not LED is off SVR Indicate whether connection with remote Ethernet interface communication device include PC and dedicated communication service In case dedicated communication is used LED is on ERR Indicates hardware error It means heavy error so if this LED is on contact custom service center RELAY Indicate whether use frame relay function between Port1 and Port2 In case...

Страница 30: ...WR Power is OFF Power is ON 1 ACT Not Sending Receiving data Sending Receiving data LNK 10Mbps Link 100Mbps Link 2 ACT Not Sending Receiving data Sending Receiving data LNK 10Mbps Link 100Mbps Link 3 ACT Not Sending Receiving data Sending Receiving data LNK 10Mbps Link 100Mbps Link 4 ACT Not Sending Receiving data Sending Receiving data LNK 10Mbps Link 100Mbps Link 5 ACT Not Sending Receiving data...

Страница 31: ...ually Pair cable Max 500MHz Phonetic Data Video signal Substitute for 75Ω coaxial cable Notes 1 UTP Unshielded Twisted Paired Copper Cable FTP Overall Foiled Twisted Paired Copper Cable STP Overall Shielded and Shielded Individually Pair Twisted Paired Copper Cable 2 Patch Cable or Patch Cord Conductor composed of stranded cable instead of solid conductor may be used to increase the flexibility of...

Страница 32: ...adband cable Category 6 Category 6A 250 500 1000 10000 Category 7 Category 7A 600 1000 10000 10000 Notes 1 Presently classified items are Category 3 5 En Cat 5 and Cat 6 inside and outside of the country where Category 4 has been replaced by Category 5 and Category 7 is being under development all over the world as STP structure 3 Example CTP LAN5 of Category 5 twisted pair cable UTP Item Unit Val...

Страница 33: ...ngth used 1 310 nm Attenuation 2dB 1 000m or less Near end crosstalk Attenuation 11dB or less Notes 1 Since the type of the connectable cable used for communication module differs from each other based on the system configuration and its environment applicable professional advice will be required prior to installation 2 The optical cable may have communication errors due to attenuation if any fing...

Страница 34: ...munication cable disconnected into the base groove and then apply enough strength until its top is locked up with the locking device of the base If the lock is not applied it may cause an error on the interface with CPU 6 The cable available for the communication module shall be installed with one type only between 10 100BASE TX and 100BASE FX 7 Select standard products of switching hub and cable ...

Страница 35: ...the communication module and CPU with the diagnosis function of XG5000 8 If the module status is normal check if response comes in when PING test is executed through a computer connected to the network if a computer is connected to the network If computer is not connected to the network use the live check item among diagnosis services of XG5000 to check the response 9 Setup the communication servi...

Страница 36: ...distance between module and hub Generally the hub is of straight cable with TD and RD stranded inside If only 2 communication modules are connected 1 to 1 cross cable form shall be used Pin No Sign Straight cable between hub and module 1 to 1 cross cable 1 2 3 6 4 5 7 8 TD TD RD TRD2 TRD2 RD TRD3 TRD3 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 1 3 2 6 3 1 4 7 5 8 6 2 7 4 8 5 Ethernet Switch RJ45 Connector Tw...

Страница 37: ...ength of the cable intensely during wiring 3 When escaping from the coat sheathed let it as long as the length only to be wired and with the insulation kept from damage 4 Jumper wire and patch code shall be applied rather loosely If wired too tight the characteristics of Category 5 may be deteriorated 5 When UTP cable is installed a suitable distance shall be maintained between EMI source and UTP ...

Страница 38: ...ch s Rx and the module s Rx with the optical switch s Tx Notes 1 Since the optical cable is vulnerable to impact pressure folding and pulling pay good attention to its treatment The optical contact between the connector and the end of the cable may have communication errors if contaminated which may result in unavailable communication If the cable is installed outdoors additional countermeasures a...

Страница 39: ... Operation 3 6 3 2 3 Installation of XGL EH5T This switch module provides interface used between Ethernet module using 10 100BASE TX So interfaces between PCs are also supported Twist Pair Cable Figure 3 2 3 Installation of XGL EH5T ...

Страница 40: ...T uses UTP cable that is same one used in XGL EFMT For more detail refer to 3 2 1 This switch module provides Auto Cross Over function so the user can use both cross and direct cable Redundancy PLC Open Network Ethernet GMR GM1 2 3 GM4C GM4 GMR 1 2 3 K1000S XGK CPUH S XGI CPUH Ethernet between PLCs Engineering Workstation PC Card ...

Страница 41: ...al error may occur to communication 5 If cable is connected long distance keep the cable far away from power line or inductive noise 6 Since the flexibility of coaxial cable is low it is to be diverged min 30cm away from the connector in communication module If the cable is bent at a right angle or transformed compulsorily cable disconnection or connector damage in communication module may be caus...

Страница 42: ...each PLC model 6 Check if LED status of communication module is normal or not If abnormal refer to Chapter 10 Troubleshooting in this user manual 7 Set system parameters correctly so to download Programming Program execution program with XG5000 and write to CPU module Sequence check Confirm the operation of communication module according to program Program modification If abnormal in sequence prog...

Страница 43: ...n module is installed on 2 Disconnect the network cable 3 Install a new module as specified in the steps of 3 3 2 above 2 Replacement by the module change switch of CPU Refer to how to use the module exchange switch of CPU 3 Replacement by the module wizard switch of XG5000 Refer to how to use the module change wizard of XG5000 Notes 1 When FEnet I F module is replaced reset the opposite side devi...

Страница 44: ... So you can monitor local PLC via broadband monitoring system 1 2 GLOFA VIEW using Internet And you can monitor PLC via local monitoring system connected to local network Fig 4 1 1 Ethernet System Public network with LSIS PLCs Broadband monitoring system 1 Broadband monitoring system 2 Hub Router or Gateway Public network Router or Gateway Hub Ethernet network Network 1 Local monitoring system 2 L...

Страница 45: ...sing P2P High Speed Link and the dedicated service Fig 4 1 2 Ethernet System Dedicated Network with LSIS PLCs 4 1 3 Dedicated Network composed of LSIS and Other Company s PLCs Figure 4 1 3 shows Ethernet system composed of LSIS s and other company s PLCs LSIS s PLC can us user defined communication So if you know the frame structure of other company s PLCs LSIS s PLC can communicate with other PLC...

Страница 46: ...stem 1 Ethernet network Network 1 4 1 4 Public Network and Dedicated Network system LSIS s Ethernet system can connect to Internet public network using open protocol TCP IP So you can monitor local PLC via broadband monitoring system 1 2 GLOFA VIEW using Internet And you can monitor PLC via local monitoring system connected to local network Fig 4 1 4 Ethernet System Public Network Dedicated Networ...

Страница 47: ...ompany s PLCs Fig 4 1 5 Ethernet System Public Network Dedicated Network Other Company s System Broadband monitoring system 1 Broadband monitoring system 2 Hub Router or Gateway Public network Router or Gateway Hub Local monitoring system 2 Local monitoring system 1 Ethernet network Network 1 Other company s PLC D ...

Страница 48: ... as STANDBY CPU doesn t execute the communication service Ethernet Network 2 A Side IP 192 168 91 191 XGK I PLC IP 192 168 91 192 IP 192 168 91 192 Upper system IP 192 168 91 193 Upper system IP 192 168 91 193 GLOFA VIEW GLOFA VIEW Ethernet Network 1 B Side IP 192 168 91 191 XGR Figure 4 1 6 XGT Ethernet redundancy system Redundant Network A Side IP 192 168 91 191 XGK I PLC IP 192 168 91 193 Upper...

Страница 49: ...and other company s controller Ethernet communication module can be used and For communication with XGT PLC industrial Ethernet communication can be used to improve the reliability and speed Figure 4 1 8 XGT redundancy system Between HMIs PLCs RAPIEnet Ring GMR PC Card HMI Master Ethernet XGK Smart I O Software HMI Info U Switch Modbus Pnet Dnet Rnet Switch XGI GM4C Standby ...

Страница 50: ...rameters including system parameters service parameters module and network diagnosis etc With regard to Ethernet network the functions of XG5000 can be mainly classified as follows 1 Basic parameters setting of communication system 2 Parameters setting of communication service HS link P2P dedicated service 3 Diagnosis service for module and network Parameters and files the user has specified can b...

Страница 51: ...connect XG5000 to PLC it is necessary to set PLC type To create new project click File New File in XG5000 Menu At new project menu set the project name project type and PLC type Fig 5 2 1 is initial screen of XG5000 Fig 5 2 1 Start Page of XG5000 Fig 5 2 2 Create new project ...

Страница 52: ...communication module Here describes standard setting that is necessary to execute FEnet module 1 Selection and execution of communication module For standard setting of communication module register the communication module at relevant base slot The user can register in on line or off line status A Register in off line status If you register a communication module without connected to XGT Use a Co...

Страница 53: ...hapter 5 XG5000 Program 5 4 a Right click unspecified Network add item Communication module Fig 5 2 4 Select communication module menu b Click Select communication module Add module Fig 5 2 5 Add module ...

Страница 54: ...dule setting FEnet module is registered on Slot 2 of Base 0 is as shown below Fig 5 2 7 Manually register communication module B Register in Online status If Connect XG5000 and PLC on which the communication module is installed I O sync can help automatically register module a Select Online Diagnosis I O information ...

Страница 55: ...Chapter 5 XG5000 Program 5 6 Fig 5 2 8 I O information b Click I O information I O sync Fig 5 2 9 I O Sync ...

Страница 56: ...XG5000 Program 5 7 c Check message and click OK button fig 5 2 10 I O sync warning messange FEnet module is registered on Slot 2 of Base 0 is as shown below Fig 5 2 11 Automatically register communication module ...

Страница 57: ...ing etc Thus surely set basic parameters on the standard settings screen of the module window so to download for the Ethernet communication Standard settings are classified into for XGI XGK and for XGR 1 In case CPU is XGK XGI series Fig 5 2 12 shows specified standard parameters in case CPU is XGI XGK Fig 5 2 12 Standard settings details in case of XGK XGI Details on the screen displayed in Fig 5...

Страница 58: ... FEnet module is included DNS server Specify the IP address of domain name server DHCP note1 Check DHCP option when not fixed but dynamic IP is to be used ADSL Relay Using when send frame received at one port to another port Reception wating time If there is no request during the specified time from the host PC or MMI connected for dedicated communication it will end the dedicated service connecti...

Страница 59: ...is reset when module is disconnected from server or Power is off 3 In case of using Remote connection to module using DHCP when remote side restart you have to check the IP address of remote station 4 In case of using DHCP with XGL EFMTB EFMFB you have to use only port 1 1 In case CPU is XGR series Fig 5 2 13 shows specified standard parameters in case CPU is XGR CPU In case of XGR some of items i...

Страница 60: ...function is activated and you register only one IP 3 When using ONE IP Solution IP address should be even number That number become FEnet module IP address of master base 4 The above number 1 becomes FEnet module IP address of standby base High speed link station No Specify station No for High speed link communication between LSIS PLCs FEnet I F modules which shall not be duplicated identically to...

Страница 61: ... number of TCP dedicated services accessible at a time 1 16 A B B A This option is activated When One IP Solution is not is not used After setting parameter of A side or B side if you click A B B A the parameters in one side is copied into another side 2 Driver server setting Classification Description XGT server Set when operated as dedicated communication server slave Modbus TCP IP server Set wh...

Страница 62: ...umber of installed module For each HS link 32 transmission blocks 128 reception blocks are available And in case of combined setting of transmission reception block 128 blocks are available 1 Choose one method in two methods from Initial selection screen 1 Click project tab Right click Unspecified network fig 5 3 1 Select High speed Communication from Project tab 2 Click view High speed Link tab R...

Страница 63: ...0sec Output data setup in case of emergency Latch Maintain and send the latest data received from CPU It is seen that it is cleared if CPU sends data as 0 even though latch is set Make sure to check the emergency output data setting of CPU Clear It sends by setting received High speed Link data as 0 in ignoring data from CPU If emergency data is set as clear in emergency output data setting of XG5...

Страница 64: ...ion Station type MASTER This item is not related with FEnt I F module so this is always fixed as MASTER SLAVE Mode 1 Send Sends data 2 Receive Receives data Station No In case of Send Mode it indicates station number of this module And in case of Receive Mode it indicates that of target module Block No Specify Tx Block and Rx Block Read area Memory area of this module P L M K Read area Word size S...

Страница 65: ...Chapter 5 XG5000 Program 5 16 5 Writing High speed Link Parameter 1 Click Online Write fig 5 3 7 Write menu 2 Check High speed Link and Click OK button Fig 5 3 8 Writing High speed Link parameter ...

Страница 66: ...Chapter 5 XG5000 Program 5 17 2 Reading High speed Link parameter 1 Click Online Read Fig 5 3 9 Read menu 2 Check High speed Link and Click OK button Fig 5 3 10 Reading High speed Link parameter ...

Страница 67: ... set respectively At redundant system available number of module is up to 6 1 Standard settings For standard setting in redundancy you can set one HS link station number and IP address etc by using One IP Solution or can set parameters of A side and B side separately by not using One IP Solution For more detail refer to CH6 High Speed Link service Fig 5 3 11 Redundant standard setting screen ...

Страница 68: ... is possible to up to 8 Each P2P set the block up to 64 1 Choose one method in two methods from Initial selection screen 1 Click project tab Right click Unspecified network fig 5 4 1 Select communication module from Project tab 2 Click view P2P tab Right click PLC name fig 5 4 2 Select View P2P tab 2 Setting Communication module ...

Страница 69: ...e setting is completed P2P setting details screen will be displayed as in Fig 5 4 3 Refer to Chapter 7 P2P Service for detailed setting Classification Description P2P channel User defined frame Edit the user defined protocol XGT client Set dedicated service master Modbus TCP client Set to Modbus TCP master P2P Block Set each command block based on specified XGT client of P2P channel User defined f...

Страница 70: ...dule installed on whose parameters are desired to write through Online Connect menu Fig 5 5 1 Connect menu After connection is established select Online Write standard settings HS link P2P to display Fig 5 5 1 screen where to specify standard settings items of the base and slot positions FEnet I F module to write download is installed on Notes 1 XG5000 can be programmed through RS 232C port or USB...

Страница 71: ...screen Notes 1 In case any service allows link when downloading parameter to CPU by using XG5000 it automatically works with the parameter newly downloaded after downloading the parameter if the service does not allow the link the parameter is not applied until the link is allowed ...

Страница 72: ...arameter window After connected select Online Read standard settings HS link P2P to display Fig 5 5 5 screen Fig 5 5 5 Read Parameter menu Where confirm Base No and Slot No among the standard settings items and then select standard settings of the applicable communication module After Read is completed confirm edit standard settings of the XG5000 screen to find the data read from FEnet module save...

Страница 73: ...x service of the communication module which will enable or disenable the operation relationship separately from the specified parameters where the communication will be kept on based on the Enable conditions even if CPU stops 1 Link Enable from XG5000 The next is to specify XG5000 for the Enable conditions Click the setting menu on Fig 5 5 6 to display Fig 5 5 7 Check the items which need the link...

Страница 74: ...G5000 Program 5 25 Fig 5 5 7 Selection of Enable Link If Enable Link Write is executed a message will be displayed as in Fig 5 5 8 which means that Link is normally enabled Fig 5 5 8 Message Screen of Enable Link ...

Страница 75: ...e Device Description _HS1_ENABLE_STATE BIT F09600 HS link 1 enable disable current state _HS2_ENABLE_STATE BIT F09601 HS link 2 enable disable current state _HS3_ENABLE_STATE BIT F09602 HS link 3 enable disable current state _HS4_ENABLE_STATE BIT F09603 HS link 4 enable disable current state _HS5_ENABLE_STATE BIT F09604 HS link 5 enable disable current state _HS6_ENABLE_STATE BIT F09605 HS link 6 ...

Страница 76: ...tate _P2P6_ENABLE_STATE BIT F09625 P2P6 enable disable current state _P2P7_ENABLE_STATE BIT F09626 P2P7 enable disable current state _P2P8_ENABLE_STATE BIT F09627 P2P8 enable disable current state _P2P1_REQ BIT F10320 P2P1 enable disable request _P2P2_REQ BIT F10321 P2P2 enable disable request _P2P3_REQ BIT F10322 P2P3 enable disable request _P2P4_REQ BIT F10323 P2P4 enable disable request _P2P5_R...

Страница 77: ...ion so to allow the user to precisely diagnose and debug the data Tx Rx relation of the communication module presently used 5 6 1 Execution of the diagnosis function Run XG5000 to connect with and then select Online Communication module setting System Diagnosis to display Fig 5 6 2 which shows base and slot information the present module is installed on and the operation status Fig 5 6 1 Selection...

Страница 78: ...6 2 Type of diagnosis functions Through the pop up menu as in the initial diagnosis screen Fig 5 6 3 system status can be diagnosed for the various communication modules Main functions for each item are as described below in Table 5 6 1 Fig 5 6 3 Diagnosis function pop up of module ...

Страница 79: ...n status of other station specified on the network Autoscan Provides active IP information for all the modules specified on the present network Table 5 6 1 Detailed diagnosis services 1 Communication module information Communication module information shows basic information such as base information High speed link station No IP information etc in addition to media and start status of the communic...

Страница 80: ...lays the service status of MMI or HMI dedicated protocol by means of higher client and monitors Tx Rx data and errors of the specified IP Fig 5 6 5 Dedicated service monitor 2 P2P Service Displays detailed information on the user defined service executed and checks normal service to read if P2P parameters are set and enabled where real time monitoring is available with Individual Read or Continuou...

Страница 81: ...meters for High speed link setting data Run link link trouble and individual information can be all monitored by High speed link service Fig 5 6 7 High speed link service monitor 3 Media Information Displays the packet information input through the media Fig 5 6 8 Media information ...

Страница 82: ...st monitor for the destination station number 5 Auto scan Display the link interface status of the whole network The service status of FEnet I F module connected with the public network is displayed as simple as shown in the diagram Fig 5 6 10 Network Auto scan ...

Страница 83: ...r to make use of all functions surely specify the basic communication parameters in the status of communication available High speed link functions are specified as below 1 High speed link block setting function 1 If there are many Send Receive areas up to 128 blocks can be setup 2 200 words are available for a block 2 Communication period setting function Send Receive period can be setup per bloc...

Страница 84: ...rds from M0020 to M0029 word with block No 1 There are 32 blocks for Send data and 64 blocks for Rx data in the High speed link parameters The block number can be set 0 31 for transmission or 0 63 for receiving The Send side needs only to decide which data to read and which block number to send to without setting the destination station No when transmitting the data is setup Table 6 2 1 Diagram of...

Страница 85: ...15 above Specify and download the basic parameters such HS link station No media IP address etc Reset the PLC to apply downloaded basic parameters Open HS link setting window of XG5000 Select HS link number 1 HS link number is available for 1 communication module 1 Self station No for Send blocks auto Correspondent station No for Receive blocks 2 Totally 128 blocks are available Send Receive data ...

Страница 86: ...pective items for High speed link after selecting High speed link parameter number on the Hs link screen of XG5000 The setting steps and the functions of respective items are explained below 6 4 1 Execution of XG5000 The initial screen of XG5000 will be displayed as shown below Fig 6 4 1 when XG5000 is executed Fig 6 4 1 Initial screen of XG5000 ...

Страница 87: ...rogram for more details 2 Downloading standard settings Select Online Write to open the Write parameter window of Fig 6 4 2 Check applicable standard settings and click OK button After standard settings are downloaded surely let PLC power turn off and on or reset If the communication module is not reset the new communication parameters information will not be applied Fig 6 4 2 Write Parameter wind...

Страница 88: ... parameters Select HsLink window of XG5000 to display the window where High speed link parameters can be setup 12 High speed links are available for XGT series PLC And parameters setting are available for the communication modules installed on the basic or extended base Fig 6 4 3 Initial screen of High speed link settings ...

Страница 89: ...er where applicable FEnet module is installed Communication period settings Period type High speed link service is used to send and receive data by user defined parameters when the execution of PLC program is ended Thus if the scan time of PLC program is as short as or less the communication data will be increased since the communication module sends data at the end of every scan which will cause ...

Страница 90: ...ata from CPU If emergency data is set as clear in emergency output data setting of XG5000 High speed Link module setting even though emergency output data setting of device area of High speed Link sending part is set as latch in CPU the data set as 0 is sent Make sure to set it after checking desired operation Table 6 4 2 Setting of communication module and communication period 3 High speed link p...

Страница 91: ... included in the identical network since it is a specific number to discriminate FEnet I F modules in the network system Classification Description Block No Block number Used to specify Send Receive blocks Read area Address The data memory address where the data to be transmitted is stored Available memory area 1 XGK P M K F T C U Z L N D R ZR 2 XGI XGR I Q M L K U R W F Refer to the list of XGT C...

Страница 92: ...2P on XG5000 check applicable High speed link and then click OK Fig 6 4 7 Write Parameters Screen 6 High speed link parameters enable Select Online Communication module setting Enable Link on XG5000 check applicable High speed link and click Write If High speed link enabled HS LED will be turned ON on the module s LED display to start High speed link Fig 6 4 8 Link Enable Screen ...

Страница 93: ...t when programming and also monitor the High speed link status using the monitor function of the High speed link information Prior to its application the user is requested to check the reliability of the communication data through High speed link information of Run link and Link trouble when operating several PLCs with High speed link service Table 6 5 1 shows the functions and definition of the H...

Страница 94: ...destination stations specified in the parameters is Run and with no error at the same time 2 Link trouble _HSxLTRBL where x is HS link No 1 12 As the whole information it shows if High speed link is normally executed through the user defined parameters which will be turned On if condition to be turned On the Run link flag is violated when Run link is On and will be turned Off if the condition is r...

Страница 95: ... status just like the max register number which synthesizes the information of the individual items to display the general information of the registered items In other words if the applicable list s Tx Rx status is normal with the operation mode of Run and with no error it will be turned On and if the conditions above are violated it will be turned Off 6 5 2 Monitor of High speed link information ...

Страница 96: ...tem Diagnosis 3 With the mouse cursor placed on the applicable module click the right button of the mouse and select Status for Respective Services to open Fig 6 5 3 screen as shown below Fig 6 5 3 XG5000 Diagnosis Services status for respective services ...

Страница 97: ... XGR system the reception side should determine which data to get And when there is error in one side the reception part needs program to get the data of another side and not to get the data of one in error The reception part can receive the correct data by receiving the data of updated sequence number 3 Input data setting of reception side Reception part take the data of updated sequence number a...

Страница 98: ...ser can t use this 2 In case XGK I is transmission mode and XGR is reception mode 1 TRX setting Make the two modules of XGK I send same data by same setting At this time sequence number is not necessary Take the data entering to the Master as input data and considering the network error use the STATE FLAG as condition to take the input data If STATE FLAG is OFF copy the data of Standby to Master b...

Страница 99: ... transmission since station to receive is only one communication setting is same with that of XGK I XGK I In the reception side when FLAG is ON receive the data of A Side and when FLAG is OFF receive the data of B Side 2 In case XGK I is transmission mode and XGR is reception mode 1 Data TRX Make the XGK I send the same data to two communication module In the reception side take the data entering ...

Страница 100: ...ame HS link station number is applied Fig 6 7 1 Communication redundant standard setting b HS link block setting In case sequence number is saved in Block 0 Fig 6 7 2 HS link block setting including sequence c HS link block setting In case of setting sequence number First Word and user data in Block 0 Fig 6 7 3 HS link block setting not including sequence 2 Ladder program XGR reception side a Incr...

Страница 101: ...andard setting of Comm Module connected to A Side Standard setting of Comm Module connected to B Side Fig 6 7 5 Reception communication standard setting b HS link block setting Comm module connected to XGR A Side Fig 6 7 6 HS link parameter setting including sequence reception Increasing SEQ NO for HS link transmission Writing the user HS link data to send ...

Страница 102: ...ing Comm module connected to XGR B Side Fig 6 7 8 HS link parameter setting including sequence reception The user can set SEQ NO and user data in one block like the figure below Fig 6 7 9 HS link parameter setting not including sequence reception 4 Ladder program XGK I reception side a Setting the input data by using HS_FB Function Block Fig 6 7 10 Function Block for redundant HS link reception da...

Страница 103: ...f HS link first input block RCV_B1 Reception data of B Side flexible Array RCV_DATA Input data considering SEQ No of A Side SEQ No of B Side and STATE b HS link reception ladder program at XGK Since Function block is not provided at XGK refer to the following ladder Input SEQ No of A Side B side at RX_SRI_A B and input device of input data at RCV_A1 B1 MOV instruction is set as size of 10 at the b...

Страница 104: ...er 6 High speed Link Service 6 22 Adding MOD_A MOD_B Fixing the problem that another network doesn t operate when one network is down Though connection of FEnet fails NDR bit is added because Run Link is set ...

Страница 105: ...tting connected to A Side Fig 6 7 11 Single standard setting a HS link block setting Comm module connected to XGR A Side Fig 6 7 12 A SIDE High Speed Link parameter setting b HS link block setting Comm module connected to XGR B Side Fig 6 7 13 B SIDE High Speed Lik parameter setting 2 Ladder program XGK I reception side Fig 6 7 14 Ladder program to send data High speed link reception data setting ...

Страница 106: ...Ladder program XGR reception side In case network is normal the user can take data of Master side but in case network is not normal the user copy the data of Standby to Master and take it as input data by using STATE FLAG and SYNC instruction At this time user should set all reception block of both A B Side so use STATE FLAG not _HSx_LTRBL as a condition to check network status Fig 6 7 17 Ladder p...

Страница 107: ... I is reception mode 1 Communication setting XGR reception side Fig 6 7 18 redundant standard setting Fig 6 7 19 Redundant HS link parameter setting including SEQ No 2 Ladder program XGR reception side Fig 6 7 20 sequence ladder program Increasing SEQ NO for HS link reception Writing HS link data for user to send ...

Страница 108: ... 6 7 21 Reception side Hs link parameter setting including SEQ No 4 Ladder program XGK I reception side Fig 6 7 22 HS link reception FB setting 2 In case XGK I is transmission mode and XGR is reception mode 1 Communication setting XGK I reception side Fig 6 7 23 HS link parameter setting ...

Страница 109: ...sion side Fig 6 7 24 Ladder program setting screen 3 Communication setting XGR reception side Fig 6 7 25 Redundant reception Hs link parameter setting 4 Ladder program XGR reception side Fig 6 7 26 Ladder program through SYNC instruction HS link transmission data setting ...

Страница 110: ...ve P2P parameter is composed of up to 64 P2P blocks Fig 7 1 1 shows an example of P2P parameters setting window in XG5000 Fig 7 1 1 Setting window of XG5000 s P2P parameters 1 P2P parameters registration window Up to 8 P2P parameters can be setup Multiple P2P parameters can be setup for an identical communication module However Enable is available only for 1 parameter among the multiple P2P parame...

Страница 111: ...e below Fig 7 1 2 P2P parameters module setting Fig 7 1 3 Setting and registration screen of P2P parameters 1 P2P channel Logical channel of P2P Service IP PORT dedicated driver to be executed can be setup User defined frame XGT client and MODBUS TCP client setting available Communication device setting available which uses other protocol than XGT MODBUS TCP 2 P2P block 64 P2P blocks setting separ...

Страница 112: ... destination station Modbus TCP Client Read Reads the area specified by destination station Write Transmits native station s area data to destination station E mail ESend Transmits a message if an event occurs EReceive Receives a message if an event occurs Table 7 2 1 Type of P2P instructions Note 1 Difference between Write Send and Write_NC Send_NC In general P2P communication it sends the reques...

Страница 113: ...tween XGT FEnet I F module and other company s Ethernet devices Since the communication protocol of devices based on Ethernet is differently defined by different makers all kinds of communication drivers can not be provided for respective device Thus the user is allowed to edit appropriately to the characteristics of the applicable communication module for which the user needs to specify User Defi...

Страница 114: ...driver used where FEnet responds if MMI PC requests to read or write data 데이터 읽기 쓰기 요청 MODBUS GLOFA 사용 데이터 읽기 쓰기 응답 MODBUS GLOFA 사용 MMI PC ETOS 이더넷 Fig 7 3 1 Example of Ethernet server driver application 2 Type of Ethernet server drivers Driver types available are as specified below Type Description XGT server XGT FEnet dedicated protocol by LSIS Modbus TCP IP server Open type of protocol by Modic...

Страница 115: ...vailable for P2P service is the maximum number of channels 16 minus the number of dedicated connections in the basic parameters The number of P2P channels 16 the number of dedicated connections P2P communication is available with simple parameters setting to communicate with the device using XGT or Modbus TCP protocol for user s convenience And for the communication with other devices than describ...

Страница 116: ... TCP Client Server Select Client Server If user select the protocol as XGT Modbus TCP this item is fixed as Client Partner Port Inputs port number of partner When defining protocol as User frame definition user can define port number H400 H1024 For XGT client this item is fixed as 2004 and Modbus TCP client is fixed as 502 Partner IP address Input IP address of Partner device Table 7 3 2 Type of P...

Страница 117: ...Read 03 Output Register Read Read Holding Registers 4XXXX word output Word Read 04 Input Registers Read Read Input Registers 3XXXX word input Word Read 05 Output Contact 1 Bit Write Force Single Coil 0XXXX bit output Bit Write 06 Output Register 1 Word Write Preset Single Register 4XXXX word output Word Write 15 Output Contact Continuous Write Force Multiple Coils 0XXXX bit output Bit Write 16 Out...

Страница 118: ... Each item is as follows 1 E mail Used for E mail service 2 Channel Select a communication port which will be used by the applicable block The communication port for each block is decided when P2P Channel is setup which can not be changed during Run 3 Driver Setting Indicates communication driver set in P2P setting When setting channel driver is loaded automatically according to channel If it is d...

Страница 119: ...tion block Rx function block about Rx frame determines one 5 Condition flag Define the condition to operate P2P block A bit device is available for condition flag and the P2P block will be operated at the rising edge of the condition flag 6 Command type Decide details of Read operation Single and Continuous are available for Instruction Type Up to 4 memory areas are available for Single Read funct...

Страница 120: ... 7 P2P Service 7 11 11 Setting When setting XGT client or user definition frame it defines the memory area to send receive In case of TX it sets the area to send M0000 and to save the data from partner device ...

Страница 121: ...roup 1 Group of frames with identical header and tail 2 Group registration surely necessary for the frame registration 2 Frame 1 Composed of Header Body and Tail 2 Send Receive frame shall be defined 3 Fixed and Variable size variables can be added to Body 4 Frame is composed of lots of segments and up to 4 variable segments can be registered for a Body 3 Type of segments Header Body and Tail of t...

Страница 122: ...de Fig 7 3 10 String Constant to select and register 3 Fix sized variable It is available only in the Body area of the frame and used to process data whose size is as long as defined value size is of Byte Check Assign memory to read data from PLC memory when send frame is registered and save the received data on PLC Memory when receive frame is registered Conversion and swap processing are availab...

Страница 123: ... 1 Conversion Hex To ASCII Send converts read data from PLC memory to ASCII code so to configure send frame Receive converts received data to ASCII so to save ASCII To Hex Send converts read data from PLC memory to Hexadecimal code so to configure send frame Receive converts received ASCII code data to Hexadecimal code so to save Fig 7 3 13 Data processing method to select If 2 Words of PLC memory...

Страница 124: ...apter 7 P2P Service 7 15 If h1234567811223344 is converted by respective methods above its results are as follows 2 Bytes swap h3412785622114433 4 Bytes swap 7856341244332211 8 Bytes swap 4433221178563412 ...

Страница 125: ...PU 1 P2P parameters downloading In order to download the prepared P2P parameters select Online Write on XG5000 menu window to display the parameters downloading window where registered basic setting P2P parameters and HIGH SPEED link parameters can be selected Fig 7 4 1 P2P parameters downloading Among P2P 0 7 only the prepared P2P parameters will be displayed after sorted where P2P parameters to ...

Страница 126: ...ication module setting Enable Link HS link P2P on the menu Fig 7 4 2 Enable setting of P2P service Select P2P parameters to start on the Enable Link HS link P2P window The P2P parameters already checked is during run whose P2P service will stop if cancelled In order to confirm normal downloading and normal P2P service operation select System Diagnosis on the menu ...

Страница 127: ...display the service status and information of the communication program after the driver of the communication module is specified The user can check the normal P2P service through the diagnosis system Refer to Chapter 5 XG5000 Program for more details Fig 7 5 1 Information of system diagnosis module ...

Страница 128: ...y detailed information on the user defined service executed check and read the service status if P2P parameters are set and enabled where real time monitoring is available with Individual Read or Continuous Read specified on the menu Fig 7 5 2 P2P service monitor ...

Страница 129: ...occurs it notified the status to manager by using E mail or SMS service But there is some restriction to use E mail service It supports ASCII and Decoding for security is not supported Since authorization function is not supported set the mail server not to do authorization process for TX 1 E mail setting of P2P service Double click E mail to activate the E mail setting window Fig 7 6 1 P2P projec...

Страница 130: ...use E mail service In order to use E mail function check this box User information User name User name seen when partner receives the mail If it is set as PLC PLC will be name of E mail sender Mail address E mail address for reply Though PLC sends E mail other PC can receive the reply about E mail PLC sent ...

Страница 131: ...us periodically If PLC becomes Stop mode or error status communication parameter can t operate so this function is provided to prepare the Stop mode or error status Item Details Event information Message surveillance period Set to be larger than 10s Time for checking whether PLC mode is changed RUN STOP Communication sends message when mode of PLC is changed from Run to Stop STOP RUN Communication...

Страница 132: ...P2P Service 7 23 Fig 7 6 4 Setting screen of Address Lock Select the No and press Edit or double click the No to active the following screen Fig 7 6 5 Address Edit window Fig 7 6 6 complete screen of Address Lock ...

Страница 133: ...complete screen of Address Lock including Group If you select Group already registered individual address is indicated at left side Select individual to be member of group and press OK to create Group address In the above screen if you send to Friend ParkHanJin and Choi MyungHo will get message simultaneously ...

Страница 134: ...ig 7 6 10 E mail message registration window Click Add to activate the following screen Set the Form and Size and write the message data Form is classified into String and Byte data receiving from CPU Form MB is used to send as many message data of P2P ESend parameter as byte set in Size Change is used to change the line when outputting data at the received screen ...

Страница 135: ...Chapter 7 P2P Service 7 26 Fig 7 6 11 E mail message edit window Fig 7 6 12 E mail Edit setting MB Fig 7 6 13 Registration result screen of E mail message ...

Страница 136: ...f P2P block to send message set in the previous steps If setting the E mail button after clicking the P2P block P2P instruction can be selectable Fig 7 6 14 P2P project window P2P block Fig 7 6 15 P2P parameter setting window Fig 7 6 16 Setting screen in case of E mail TX ...

Страница 137: ...in P2P Determines title and data of mail Mail address number Sets registration number set in Address Lock Determines who to send When you want to send many people use Group But before using Group the address of partner should be inputted The number of Group member is limited to maximum 10 Mail data Indicates the start address of data to send It sends as many data as the number of array 10 byte sta...

Страница 138: ...eck if the STATUS of relevant block is 0 or not take the data of one side by checking STATUS is 0 and normal service count increases 1 In case XGR and XGK I are configured as redundant system by using different IP address at single network since P2P service have to configure service with different one block you can write ladder program like the figure below After checking if P2P no 1 is normal or ...

Страница 139: ... 1 and P2P service connected to Standby master is no 2 If you write ladder about P2P block no 0 you can write the ladder like figure below After checking whether P2P no 1 is normal or not if it is normal set the set_p2p1 After checking whether P2P no 2 is normal or not if it is normal set the set_p2p2 If no 1 is normal data of No 1 is taken If no 1 is abnormal data of No 2 is taken ...

Страница 140: ...nt system with same IP address at the separated network only standard setting is different with 2 You can configure the redundant system by using same ladder program to configure redundant system If no 1 is normal data of No 1 is taken If no 1 is abnormal data of No 2 is taken ...

Страница 141: ... 502 for the port number of MODBUS TCP driver This service mainly used to communicate between higher level system PC program MMI and LS Ethernet module or between LS Ethernet modules 1 Setting of XGT dedicated driver Fig 8 1 1 Driver setting screen As basic parameters shall be surely specified and downloaded prior to use in the Ethernet communication the dedicated communication services shall be a...

Страница 142: ...t 00 05 CPU TYPE 01 XGK R CPUH 02 XGK CPUS 05 XGI CPUU Bit 06 0 Redundancy Master Single 1 Redundancy Slave Bit 07 0 CPU normal operation 1 CPU error Bit 8 12 System status 1 RUN 2 STOP 4 ERROR 8 DEBUG Bit 13 15 Reserved CPU Info 1 It is determined to be the XGK I R series through a reserved area XGK 0xA0 XGI 0XA4 XGR 0xA8 Source of Frame 1 Client MMI Server PLC h33 Server PLC Client MMI h11 Invok...

Страница 143: ...or checking for errors in PC or MMI Length Length of the data area at the back of Header in the frame 2 Data Request frame external communication device FEnet I F module Header Instruction Data type Reserved area 2 bytes Structurized data area 3 ACK Response frame FEnet module external communication device if data is received normally Header Instruction Data type Reserved area 2 bytes Error status...

Страница 144: ...sed on each data type Continuous Writes byte type of variables in block unit up to 1 400 bytes Table 8 1 1 List of Instructions 8 1 4 Data type 1 Data type of variables The Data types of variables in the P M L F K C D T N R etc device areas are to be included after the variable indicating letter of Data type Example Bit PX0 LX0 FX0 Byte MB0 PB0 DB0 Word PW0 LW0 FW0 DW0 Double Word PD0 LD0 FD0 DD0 ...

Страница 145: ...e Max 16 Direct variable Length of variable name Direct variable only available Repeatedly as many as the number of blocks up to 16 Variable length 2 The number of characters in the Direct variable up to 16 characters Direct variable Length of variable name Direct variable only available Format name Header Instruction Data type Reserved area Number of blocks Variable length Direct variable Code Ex...

Страница 146: ...Ex h0054 5400 3 Response format For PLC s ACK Response Read Response of Individual variable PLC MMI Item Size byte Description Instruction 2 h0055 Read Response Data type 2 Refer to Data Type table Reserved area 2 h0000 Don t Care Error status 2 Normal if it is 0 abnormal if not 0 Error code 2 If Error State is abnormal the lower Byte is the error code Number of blocks If Error State is normal it ...

Страница 147: ... M L K F T X 1 Lowest bit only effective Word W P M L K F T C D S W 2 Table 8 2 2 Number of data based on variables Notes 1 Number of data H04 means that 4 bytes of Hexadecimal data Double Word exists in the data 2 If data type is Bit the read data will be displayed in one byte HEX In other words if BIT value is 0 h00 will be displayed and if the value is 1 h01 will be displayed 4 Response format ...

Страница 148: ... F It displays block s start address Ex MB0 PB0 Number of Data 2 Data Size in byte whose Maximum value is 1400 h0578 Format name Header Instruction Data type Reserved area Number of blocks Variable length Variable Number of data Code Ex h0054 h0014 h0000 h0001 h0006 MB000 h0006 Notes 1 Number of data means the number of data in byte unit up to 1 400 bytes available 1 Data type h0014 only can be us...

Страница 149: ...tate is normal Number of data 2 The Size of Data in byte Data Data size Data to read up to 1400 bytes Format name Header Instruction Data type Reserved area Error status Number of blocks Number of data Data Code Ex h0055 h0014 h0000 h0000 h0001 h0006 h012345 6789AB Number of data means the number of bytes in Hexadecimal number 4 Response format For PLC s NAK Response Format name Header Instruction...

Страница 150: ...umber of blocks up to 16 Length of variable name 2 Length of direct variable Max 16 Variable name Length of variable name Direct variable only available Data size 2 Byte size of Data Data Data size Data to write Repeatedly as many as the number of blocks up to 16 Data size 2 Byte size of Data Data Data size Data to write Format name Head er Instruc tion Data type Reserv ed area Number of blocks Va...

Страница 151: ...is used the address must be calculated in Bit unit For example to write a data in the hC 12th bit of M172 word the Bit address can be calculated as follow processing Wrong Expression MX172C Right Expression 172 Word number x 16 12 Bit number 2764 MX2764 3 Response format For PLC s ACK Response Format name Header Instruction Data type Reserved area Error status Number of blocks Code Ex h0059 h0002 ...

Страница 152: ... L K T C D N It displays block s start address Ex MB0 PB0 Data Data size Data to write up to 1400 bytes Format name Header Instruction Data type Reserved area Number of blocks Variable length Variable Number of data Data Code Ex h0058 h0014 h0000 h0001 h0006 MB1 00 h0002 h1234 1 Number of data It means the number of data in byte unit up to 1 400 h0578 bytes available 2 Number of blocks h0001 only ...

Страница 153: ...rror code Error code h0001 If Error State normal Format name Header Instruction Data type Reserved area Error status Number of blocks Code Ex h0059 h0014 h0000 h0000 h0001 1 Data type Available data type is byte MB IB QB 2 Number of data It means the number of bytes Hexadecimal 4 Response format in case of PLC NAK response Format name Header Instruction Data type Reserved area Error status Error c...

Страница 154: ... of XGT status Item Size byte Byte position Description Slot Info 4 0 Slot information Bit00 Bit03 Local s slot information remotely connected with other station Bit04 Bit07 Local s base information remotely connected with other station Bit08 Bit11 Other station s slot information remotely connected Bit12 Bit15 Other station s base information remotely connected Bit16 Bit19 Slot information this m...

Страница 155: ...N_EDIT_ST Bit F00008 Modification in progress during Run program being downloaded Modified program standing by while modified during Run _RUN_EDIT_CHK Bit F00009 Modification in progress during Run internally processed Modification during Run being processed Internally _RUN_EDIT_DONE Bit F0000A Modification complete during run Modification normally complete during run _RUN_EDIT_END Bit F0000B Inte...

Страница 156: ...CB2 Bit F0001F Compile code 2 No 2 compile code being executed 4 _CNF_ER It displays the error flags related with the operation stop errors Variable Type Device Function Description _CPU_ER Bit F00020 CPU configuration Error Normal operation unavailable due to CPU module error found by self diagnosis _IO_TYER Bit F00021 Module type discordant Error Different configuration between each slot s I O c...

Страница 157: ...power abnormal _WDT_ER Bit F00030 Scan watch dog Displayed if program scan time exceeds scan watch dog time specified with parameters F00031 F0003F 5 _CNF_WAR It displays all the warning flags related with continuation of the operation DWORD F004 F005 Variable Type Device Function Description _RTC_ER Bit F00040 RTC data error Displayed if RTC data abnormal _DBCK_ER Bit F00041 Data back up error Di...

Страница 158: ...Bit F0004A HS parameter 3 error _HS_WAR4 Bit F0004B HS parameter 4 error _HS_WAR5 Bit F0004C HS parameter 5 error _HS_WAR6 Bit F0004D HS parameter 6 error _HS_WAR7 Bit F0004E HS parameter 7 error _HS_WAR8 Bit F0004F HS parameter 8 error _HS_WAR9 Bit F00050 HS parameter 9 error _HS_WAR10 Bit F00051 HS parameter 10 error _HS_WAR11 Bit F00052 HS parameter 11 error _HS_WAR12 Bit F00053 HS parameter 12...

Страница 159: ...ocol Communication 8 19 8 3 Modbus TCP Dedicated Server This is used when it operates as the master of other device or higher PC MMI Modbus 8 3 1 Driver setting Fig 8 3 1 Modbus TCP driver setting Fig 8 3 2 Modbus TCP address ...

Страница 160: ... each function code s request Respective setting details are as follows Item Description Remarks DI area address XGT address applicable to digital input area Bit address DO area address XGT address applicable to digital output area Bit address AI area address XGT address applicable to analog input area Word address AO area address XGT address applicable to digital output area Word address The addr...

Страница 161: ... disconnect the Local connection with Disconnect menu To access the PLC n station select PLC n by setting the IP address of PLC n and Base and Slot No where FEnet module is installed in the PLC 1 station in the remote connection dialog box and connect Then logical connection between XG5000 and PLC n will be established via RS 232C and Ethernet This status is identical to the status that RS 232C ca...

Страница 162: ... followings explains remote 1 and remote 2 connections Fig 9 2 1 Remote connection Fig 9 2 1 shows an example of network system composed of two networks Network 2 XG5000 PLC n IP 192 168 91 190 PLC 1 IP 192 168 91 188 PLC 2 IP 192 168 91 189 FDEnet 1 USB or RS 232C Local connection Logical connection via Ethernet module remote 1 PC Logical connection via Ethernet module remote 2 PLC A IP 192 168 9...

Страница 163: ...e It designates the connecting method for local connection Local connection is applied with RS 232C used as in Fig 9 2 3 Select the port used in PC for a communication port The case that Ethernet is used for local connection will be described in the next section Refer to user s manual of each communication module for the case with other connection types 2 Connection depth Decide a PLC connection s...

Страница 164: ...Network type Select a network type for stage 1 connection among Rnet Fdnet Cnet FEnet and FDEnet XGL FEnet is to be selected because stage 1 connection is applied through FEnet in Fig 9 2 3 4 Base No Specify the base No where FEnet I F module of PLC 1 for remote connection is installed ...

Страница 165: ...s on slot No 0 Now click OK and then select Connect on the Online menu Since stage 1 connection completed status is the logical connection status identical to the local connection with RS 232C cable is connected to the PLC where all of the on line menus are available Except that CPU type between PLC and presently open project is disagreeable Notes 1 Precautions for remote connection Prepare a prog...

Страница 166: ...onnection settings like fig 9 2 2 1 Connection type Select Local connection Fig 9 2 4 shows that select RS 232C for Type and Remote 2 for Depth The communication port choose using PC port If use Ethernet explain it in the next chapter If use other communication module Please refer to manual each communication modules 2 Connection depth Select Reome 2 Fig 9 2 4 XG5000 remote stage 2 connection ...

Страница 167: ...n is with FEnet in Fig 9 2 4 2 IP address Specify the IP address of FEnet I F module installed in the PLC B which will be connected with XG5000 in the network 2 Use the IP address of FEnet module installed in PLC B station 192 168 91 192 in Fig 9 2 4 3 Base and slot No Set the Base and Slot No where FEnet module is installed in the PLC 2 which will be connected with stage 2 in the network 2 Stage ...

Страница 168: ...hernet where connection to all PLCs on the network is available without RS 232C used in XG5000 In this case local connection is omissible and remote 1 connection is available with all PLCs Select Connection settings on the Online menu and change the setting in the dialog box as specified below to establish remote stage 1 connection directly via Ethernet Fig 9 2 6 Remote 1 connection directly via E...

Страница 169: ...emote stage 1 or 2 Select remote 1 here 3 IP address Set the IP address of FEnet I F module to connect to Use IP address 210 206 91 190 to connect to PLC n in Fig 9 2 6 The rest procedures are the same as with RS 232C used Now click OK and then select Connect on the Online menu It is accessible through Ethernet which the CPU module direct connection without Ethernet I F module CPU direct connectio...

Страница 170: ...ction is available via Ethernet if a PC where XG5000 is operating is included in one PLC Ethernet network and one Ethernet is connected with other Ethernet network The procedures are the same as in remote 1 connection and a setting example of Connection Setting is as Fig 9 2 7 Fig 9 2 7 Remote 2 connection directly via Ethernet ...

Страница 171: ...r D Flash memory E Set Link Enable F I O information G Compulsory I O information H I O SKIP 2 Execute the remote connection with applicable project open of the station to connect to for XG5000 programming through remote stage 1 2 connections 3 Up to 2 stages only are available for the remote connection More than that is not available for the remote connection 2 In case of remote connection via XG...

Страница 172: ...ked through LED in front of Ethernet module LED of XGL EFMT Fig 10 1 1 LED structure of XGL EFMT EFMF module LED Error Action RUN Turned off after FEnet powered on 1 Ethernet communication module incorrectly installed check DC 5V power supply of power module check the communication module if correctly installed on the base 2 Check if communication module is correctly perceived with XG5000 I F LED ...

Страница 173: ...d check if the IP address of HMI PC is registered in the host table 3 Check if connection is requested from MMI PC device ERR Turned on during normal communication 1 Check if the basic parameter is downloaded correctly 2 Check for any error in interface with CPU 10 1 2 Abnormal operation display of XGL EFMTB EFMFB The operation status can be checked through LED in front of Ethernet module Fig 10 1...

Страница 174: ...t I F module is used as dedicated service 1 Check if IP address for dedicated connection is normal 2 Check if dedicated connection table is enable and in case enable check if IP of HMI PC at dedicated connection table is registered 3 Check connection requirement is normal aat HMI PC ERR Turned on after Ethernet I F module power on 1 In case of major failure turn on If LED is on again after power r...

Страница 175: ...urning on if all LEDs except power LED flicker one time switch module is normal LED Error Action PWR LED off after power on 1 Abnormal equipment of switch module Check DC 5V power supply of power module check the communication module if correctly installed on the base ACT ACT LED off 1 Check if cable is connected to port correctly LED is off in the disconnection status 2 Check if data is communica...

Страница 176: ...and then select Online PLC History PLC Error Warning in XG5000 Fig 10 2 1 PLC history If a hardware error or a CPU interface error occurs on the module LED of the communication module itself operates abnormally in general whose status can be monitored simply through its dedicated program Fig 10 2 1 shows error warning information through PLC History on the XG5000 Online menu which can be settled b...

Страница 177: ...error 0x0051 Channel connection overflow 0x0062 Channel setting error 0x00F0 Internal buffer allotment error 0xFF00 User defined data send error user defined frame 0xFF01 User defined frame event receive error 0xFFD7 Internal data send overflow 0xFFEB Internal interlock error 0xFFFF When it request connection for server setting User defined send frame size error E mail 0x0001 Email address error 0...

Страница 178: ... Troubleshooting 1 Run LED Off H W error Powered normally Installed as specified Restart the power Same error Communication module H W error Contact service center Operation normal Shoot the trouble of the applicable error H W error Check power voltage Let the conditions as Specified Run Yes Yes Yes No No No Yes No Communication module installed correctly Install communication module correctly No ...

Страница 179: ...ge Let the conditions modified or complemented as specified Yes Yes No No Communication Module installed correctly on basic base Install communication module correctly on the basic base No Yes Any error on connector pin of communication module Correct connector pin Communication module or CPU H W error Contact service center No End Yes ...

Страница 180: ...rite the number of block is larger than 16 2 0x0002 Data type which is not X B W D L is received 3 0x0003 Device not serviced is requested XGK P M L K R XGI I Q M 4 0x0004 Exceed the device area 5 0x0005 It can read or write maximum 1400byes at once That restriction is exceeded Single block size 6 0x0006 It can read or write maximum 1400byes at once That restriction is exceeded Total size per bloc...

Страница 181: ...LCare asfollows Specification Testitems Testdetails Standardvalue EN50081 2 EN55011Radiated noise 2 Measurethe wave emittedfrom a product 30 230 QP 50 m 1 230 1000 QP 57 m EN55011conducted noise Measure the noise that a product emits to the power line 150 500 QP 79 Mean 66 500 230 QP 73 Mean 60 EN61131 2 EN61000 4 Electrostatic immunity Immunity test allowing static electricity to the caseof a dev...

Страница 182: ...ws 1 Panel Thepanelfor PLCshould beinstalledandmanufacturedas follows 1 Thepanelshouldbemadeof SPCC ColdRolledMild Steel 2 Theplateshouldbe1 6mmand thicker 3 Thepowersuppliedtothepanelshouldbeprotected againstsurgebyusing insulatedtransformer 4 Thepanelshouldbestructuredsothatelectric wave is notleakedoutside Forinstance make thedooras abox as presentedbelow Themainframeshouldbealso designedtobeco...

Страница 183: ...t TheextensioncableofXGTseries is withfast electricsignal Therefore highfrequencynoise wave is emittedfrom the extensioncable Tocomplywith theCEspecifications please attachtheferritecore on the extensioncableas presented in thefigure Mode Manufacturer Remarks CU1330D ETechElectronics ZCAT3035 1330 TDK 2 Fixingacable inthepanel If the extension cable of XGT series is to be installed on the metallic...

Страница 184: ...f the device used in measurement control lab XGTseries is developedinaccordance withtheabovespecifications evenfor amodule operating attherated voltagehigherthan AC50V DC75V 11 2 2 Selection of XGT series PLC 1 Power module Thepowermoduleof whichrated input voltage is AC110 220Vmayhave dangerous voltage higherthan 42 4V peak insideit soanyCEmark compliance product is insulatedbetween the primaryan...

Страница 185: ...is the memory addresses of CPU for the data send receive Device type Range Size Word Read Write P P0 P2047 2048 R W M M0 M2047 2048 R W K K0 K2047 2048 R W F F0 F1023 1024 R F F1024 F2047 1024 R W T T0 T2047 2048 R W C C0 C2047 2048 R W U U00 00 U7F 31 4096 R W Z Z0 Z127 128 R W L L0 L11263 11264 R W N N0 N21503 21504 R W D CPUH D0 D32767 32768 R W D CPUS D0 D19999 20000 R W R R0 R32767 32768 R W ...

Страница 186: ...igh Speed Link flag N 42K byte NW0 NW25087 P2P flag U 8K byte UW7 15 31 Analog refresh flag A 1 3 Device of XGR CPU Device type Size Range Reference Memory Input variable I 16KB IW0 0 0 IW127 15 3 Output variable Q 16KB QW0 0 0 QW127 15 3 Automatic variable A 512KB AW0 AW262143 Max 256K byte can be set as retain area Direct variable M 256KB MW0 MW131071 Max 128K byte can be set as retain area R 64...

Страница 187: ... networks so to be operated as one network Bridge is used not only to connect two different types of networks but also to divide one big network into two small networks in order to increase the performance 4 Client A user of the network service or a computer or program mainly the one requesting services using other computer s resource 5 CSMA CD Carrier Sense Multiple Access with Collision Detectio...

Страница 188: ...end about 10Mbps and use the packet of 1 5kB Since Ethernet can allow various types of computers to be connected as one via the network it has been called a pronoun of LAN as a universal standard with various products available not limited to some specific companies 10 FTP File Transfer Protocol An application program used to transfer files between computers among application programs providing TC...

Страница 189: ...k is called Node 22 Packet A package of data which is the basic unit used to send through the network Usually the package is made of several tens or hundreds of bytes with the header attached in front to which its destination and other necessary information are added 23 PORT number Used to classify the applications on TCP UDP Ex 21 tcp Telet 24 PPP Point to Point Protocol Phone communication proto...

Страница 190: ...into packets to send through IP and the packets sent will be united back together through TCP 30 Telnet It means remote login via Internet To login to remote host via TELNET account of that host is necessary But for some hosts providing public service you can connect without account 31 Token Ring As short distance network using Token to connect to network having physical ring structure one of the ...

Страница 191: ...as 3 Change connection speed 34 FDDI Fiber Distributed Data Interface Based on optical cable provides 100Mbps Shared Media Network as Dual Ring method Token Passing is done in two way Max 200Km distance for entire network Max 2Km between Nodes Max 500 nodes Generally this used as Backbone Network 35 Reset This function is used to initialize the communication module with errors Use XG5000 to select...

Страница 192: ...IT_END Modification complete during run Modification complete during run F0000C BIT _CMOD_KEY Run Mode Run Mode changed by key F0000D BIT _CMOD_LPADT Run Mode Run Mode changed by local PADT F0000E BIT _CMOD_RPADT Run Mode Run Mode changed by remote PADT F0000F BIT _CMOD_RLINK Run Mode Run Mode changed by remote communication module F00010 BIT _FORCE_IN Compulsory input Compulsory input status F000...

Страница 193: ...BIT _CPPRM_ER Communication module parameter Communication module parameter abnormal F0002C BIT _PGM_ER Program error Program error found F0002D BIT _CODE_ER Code error Program code error found F0002E BIT _SWDT_ER System watch dog System watch dog active F0002F BIT _BASE_POWER_ ER Power error Base power abnormal F00030 BIT _WDT_ER Scan watch dog Scan watch dog active F0004 DWORD _CNF_WAR System wa...

Страница 194: ... 6 P2P parameter6 error F0005A BIT _P2P_WAR7 P2P parameter 7 P2P parameter7 error F0005B BIT _P2P_WAR8 P2P parameter 8 P2P parameter8 error F0005C BIT _CONSTANT_ER Fixed cycle error Fixed cycle error F0009 WORD _USER_F User contact point Timer available for user F00090 BIT _T20MS 20ms CLOCK of 20ms cycle F00091 BIT _T100MS 100ms CLOCK of 100ms cycle F00092 BIT _T200MS 200ms CLOCK of 200ms cycle F0...

Страница 195: ...qual F00123 BIT _GT GT flag ON if greater than F00124 BIT _GTE GTE flag ON if greater than or equal F00125 BIT _NEQ NEQ flag ON if not equal F0013 WORD _AC_F_CNT Inspected power cut Number of inspected power cuts displayed F0014 WORD _FALS_NUM FALS No FALS No displayed F0015 WORD _PUTGET_ERR0 PUT GET error 0 Main base PUT GET error F0016 WORD _PUTGET_ERR1 PUT GET error 1 Added base step 1 PUT GET ...

Страница 196: ..._FPU_LFLAG_U Underflow latch Latched if underflow found F00572 BIT _FPU_LFLAG_O Overflow latch Latched if overflow found F00573 BIT _FPU_LFLAG_Z Latch divided by 0 Latched if divided by 0 F00574 BIT _FPU_LFLAG_V Invalid calculation latch Latched if invalid calculation F0057A BIT _FPU_FLAG_I Incorrect error Reported if incorrect error found F0057B BIT _FPU_FLAG_U Underflow Reported if underflow fou...

Страница 197: ...ype 2 error Added base step 2 module type error F0099 WORD _IO_TYER3 Module type 3 error Added base step 3 module type error F0100 WORD _IO_TYER4 Module type 4 error Added base step 4 module type error F0101 WORD _IO_TYER5 Module type 5 error Added base step 5 module type error F0102 WORD _IO_TYER6 Module type 6 error Added base step 6 module type error F0103 WORD _IO_TYER7 Module type 7 error Add...

Страница 198: ...dule RW 7 error Added base step 7 module Read Write error F0128 WORD _IO_IFER_0 Module IF 0 error Main base module interface error F0129 WORD _IO_IFER_1 Module IF 1 error Added base step 1 module interface error F0130 WORD _IO_IFER_2 Module IF 2 error Added base step 2 module interface error F0131 WORD _IO_IFER_3 Module IF 3 error Added base step 3 module interface error F0132 WORD _IO_IFER_4 Modu...

Страница 199: ...Write ON when writing Flash N block data F0164 DWORD _RBLOCK_ER_F LAG Flash error Error found during Flash N block service F1024 WORD _USER_WRITE_ F Available contact Contact point available in program F10240 BIT _RTC_WR RTC RW Data Write Read in RTC F10241 BIT _SCAN_WR Scan WR Scan value initialization F10242 BIT _CHK_ANC_ERR Detect external serious error Detection of serious error in external eq...

Страница 200: ...le The link trouble will be On if one of those conditions 1 2 and 3 above occurs And if such a condition is back to normal it will be Off L000020 L00009F _HS1_STAT E k k 000 127 Bit Array Displays HS link parameter No 1 Block No k s general status Displays the general status of the communication information for the specified parameter s respective data blocks HS1STATE k HS1MOD k _HS1TRX k _HS mERR...

Страница 201: ...stered in XG5000 for convenient application 3 L001000 L00149F 4 L001500 L00199F 5 L002000 L00249F 6 L002500 L00299F 7 L003000 L00349F 8 L003500 L00399F 9 L004000 L00449F 10 L004500 L00499F 11 L005000 L00549F K as a block number is displayed through 8 words by 16 for 1 word for the information of 128 blocks from 000 to 127 For example block information of 16 31 32 47 48 63 64 79 80 95 96 111 112 12...

Страница 202: ...o 00 service abnormal execution times Displays P2P parameter No 1 block No 0 service abnormal execution times L006310 _P2P1_NDR01 Bit P2P parameter No 1 block No 01 service is completed normally P2P parameter No 1 block No 1 service is completed normally L006311 _P2P1_ERR01 Bit P2P parameter No 1 block No 01 service is completed abnormally P2P parameter No 1 block No 1 service is completed abnorma...

Страница 203: ...ock No 00 Read area size 3 Saves P2P parameter No 1 block No 00 Read area size 3 N00016 N00019 _P1B00RD 4 Device structure P2P parameter No 1 block No 00 Read area device 4 Saves P2P parameter No 1 block No 00 Read area device N00020 _P1B00RS 4 Word P2P parameter No 1 block No 00 Read area size 4 Saves P2P parameter No 1 block No 00 area size 4 to read saved N00021 N00024 _P1B00W D1 Device structu...

Страница 204: ...1R D3 Device structure P2P parameter No 1 block No 01 Read area device 3 Saves P2P parameter No 1 block No 01 Read area device 3 N00056 _P1B01R S3 Word P2P parameter No 1 block No 01 Read area size 3 Saves P2P parameter No 1 block No 01 Read area size 3 N00057 N00060 _P1B01R D4 Device structure P2P parameter No 1 block No 01 Read area device 4 Saves P2P parameter No 1 block No 01 Read area device ...

Страница 205: ...vice 4 saved N00081 _P1B01W S4 Word P2P parameter No 1 block No 01 saved area size 4 P2P parameter No 1 block No 01 saved area size 4 saved Notes 1 If P2P parameters are to be specified with XG5000 used for N area the setting will be performed automatically And its modification during Run is also available by P2P dedicated command 2 Since the addresses of N area available are classified according ...

Страница 206: ... ˆ C8 200 È 09 009 HT 49 073 I 89 137 C9 201 É 0A 010 LF 4A 074 J 8A 138 Š CA 202 Ê 0B 011 VT 4B 075 K 8B 139 CB 203 Ë 0C 012 FF 4C 076 L 8C 140 Œ CC 204 Ì 0D 013 CR 4D 077 M 8D 141 CD 205 Í 0E 014 SO 4E 078 N 8E 142 Ž CE 206 Î 0F 015 SI 4F 079 O 8F 143 CF 207 Ï 10 016 DLE 50 080 P 90 144 D0 208 Ð 11 017 DC1 51 081 Q 91 145 D1 209 Ñ 12 018 DC2 52 082 R 92 146 D2 210 Ò 13 019 DC3 53 083 S 93 147 D3...

Страница 207: ...27 039 67 103 g A7 167 EA 231 ç 28 040 68 104 h A8 168 EB 232 è 29 041 69 105 i A9 169 EC 233 é 2A 042 6A 106 j AA 170 ª ED 234 ê 2B 043 6B 107 k AB 171 EE 235 ë 2C 044 6C 108 l AC 172 EF 236 ì 2D 045 6D 109 m AD 173 F0 237 í 2E 046 6E 110 n AE 174 F1 238 î 2F 047 6F 111 o AF 175 F2 239 ï 30 048 0 70 112 p B0 176 F3 240 ð 31 049 1 71 113 q B1 177 F4 241 ñ 32 050 2 72 114 r B2 178 F5 242 ò 33 051 3...

Страница 208: ...lue ASCII Value ASCII Value ASCII Value Hex Dec Hex Dec Hex Dec Hex Dec 3B 059 7B 123 BB 187 FE 251 û 3C 060 7C 124 BC 188 FF 252 ü 3D 061 7D 125 BD 189 EF 253 ý 3E 062 7E 126 BE 190 EF 254 þ 3F 063 7F 127 BF 191 À EF 255 ÿ ...

Страница 209: ...10 Coaxial Cable 185m Fast Ethernet 100BASE T4 100 UTP 100m 100BASE TX 100 UTP 100m 100BASE FX Multi Mode 100 Optical Cable 412m Half Duplex 2km Full Duplex 100BASE FX Single Mode 100 Optical Cable 20km Gigabit Ethernet 1000BASE T 1000 UTP 100m 100BASE FX Single Mode 1000 Optical Cable 3km 100BASE FX Multi Mode 1000 Optical Cable 500m 100BASE T 1000 Coaxial Cable 25m 100VG AnyLAN 100 UTP ATM 155 6...

Страница 210: ...Appendix A 26 A 6 External Dimensions XGL EFMT EFMF XGL EH5T is equal design Please refer to a lower picture for the dimension Unit mm ...

Страница 211: ...circumstances where the expectations exceed that of the science and technology level when LSIS produced the product 6 Problems caused by natural disaster 3 This warranty is limited to the PLC itself only It is not valid for the system which the PLC is attached to Environmental Policy LSIS Co Ltd supports and observes the environmental policy as below LSIS considers the environmental preservation a...

Страница 212: ...54 Fax 86 20 8326 6287 e mail chenxs lsis com cn LSIS Chengdu Office _ Chengdu China Address 12FL Guodong Buiding No 52 Jindun Road Chengdu 610041 P R China Tel 86 28 8612 9151 9226 Fax 86 28 8612 9236 e mail comysb lsis biz LSIS Qingdao Office _ Qingdao China Address YinHe Bldg 402 Room No 2P Shandong Road Qingdao City Shandong province 266071 P R China Tel 86 532 8501 6068 Fax 86 532 8501 6057 e...

Отзывы: