Chapter 2 Specifications and Functions
2-3
2.2.2 Performance specifications of diagnostic digital Output module (XGQ-RY1D)
Table 2.3 shows performance specifications of XGQ-RY1D.
Item
Specifications
Output point
8 points
Insulation method
Relay insulation
Photo coupler insulation
Rated load voltage
DC24V (resistance load) / AC220V (COS
Ψ
= 1)
Rated load
current
1point
2A
Common
5A
Min. load voltage / current
DC5V / 1mA
Max. load voltage / current
AC250V, DC125V / 2A
Leakage current at Off
0.1mA (AC220V, 60Hz)
Max. switching frequency
1,800 times/hour
Surge killer
None
Life
Mechanical
20 million and more times
Electrical
Rated load voltage/current 100 thousand and more times
AC200V / 1.5A, AC240V / 1A (COS
Ψ
= 0.7) 100 thousand and more times
AC200V / 1A, AC240V / 0.5A (COS
Ψ
= 0.35) 100 thousand and more times
DC24V / 1A, DC100V / 0.1A (L / R = 7ms) 100 thousand and more times
Response
time
Off -> On
10ms and lower
On -> Off
12ms and lower
Diagnosis function
Wire break detection
Internal output signal diagnosis
Common method
8 point/1COM
Current consumption(mA)
Max. 400mA
Operation display
LED On with output On
LED On during wire break
LED On when the internal output signal fail
External connection method
9 point Terminal strip connector (M3 X 6 screws)
Weight
145g
[Table 2.3] performance specifications of XGQ-RY1D