8.30 Fire Mode
Fire mode is used in case of an emergency to operate the inverter to extract smoke
outdoors in traffic tunnels, subway stations, stairwells, etc
When Fire mode is activated the inverter ignores all internal faults and motor protecting
features to keep the motor running.
Few fatal faults is not ignored as it can cause secondary explosion in a critical situation.
Group
Code
Parameter Name
Setting
Range
Default
Unit
I/O group
I17-20
Multi-function digital
input 1-4
-
28. Fire Mode
I54-55
Relay Define x
-
27. Fire Mode
Application
Group
A42
Fire Mode Freq
-
0-Max
Freq.[Hz]
50.00
Hz
On receipt of a digital fire input, the drive will run with following conditions.
a) Regardless of preset control method such as PID mode, the inverter switches to V/f
control automatically.
b) The preset command frequency will be ignored and the inverter will run at A42_Fire
Mode Freq. The fire mode frequency has the highest priority even over Jog operation.
c) The acceleration and deceleration time is fixed as 10 seconds and it is not changeable
d) the following faults or trips will be ignored and not displayed.
- Inverter overload, Overload trip, Cooling fan fault, Electronic thermal, External fault
A/B contact input,
- Frequency command loss, Input/Output phase loss, Instantaneous output cut-off,
Parameter save error, BX trip.
e) There is no limitation of on the number of attempts the inverter restarts.
‘
Auto restart after
fault
’
function is activated automatically and delay time will be applied as preset.
- Overcurrent trip, Overvoltage trip, Low voltage trip, Ground fault current
f) The inverter will not restart in case of the following faults:
- Hardware fault, Keypad communication error
www.barghmaher.ir
Содержание iG5H Series
Страница 13: ...www barghmaher ir ...
Страница 22: ...9 Installation Wiring Installation 2 3 Terminal wiring Control I O www barghmaher ir ...
Страница 23: ...10 Installation Wiring www barghmaher ir ...
Страница 50: ...37 Programming Keypad Basic operation Basic Ops Wiring Operating pattern www barghmaher ir ...
Страница 173: ...Protective functions 160 www barghmaher ir ...
Страница 219: ...206 DECLARATION OF CONFIRMITY www barghmaher ir ...
Страница 223: ...210 www barghmaher ir ...
Страница 225: ...212 Revision History No Date Edition Changes 1 2018 05 08 First Release First Release 2 3 4 5 6 7 8 9 www barghmaher ir ...