background image

 
 
 
 
 

Appendix 1 Troubleshooting

 

App1-1 

Appendix 1 Troubleshooting

 

 

1. Type of Problem

 

 
It classifies problems from XGT Panel including an indicated figure, indication of the object, and problems 
appeared when downloading. Refer to the following chart. 

 

Classification of 

problem 

Description 

Problem when starting 

Malfunction when starting. 

Please refer to the 2. Problem when starting.

 

Problem after the 
monitor on 

In case that there is no reaction when touching. 

  Please refer to the 3. Problem after the Monitor on.

 

Display problem of   
figure and object. 

In case that the figure or object is different from when editing.   

  Please refer to the 4. Indication problem of figure and object.

 

Communication problem 

In case that communication is not executed properly. 

  Please refer to the 5. Communication problem.

 

USB Removal of 
Memory Card 

In case that USB device is not working for a while when USB memory is removed. 

  Please refer to the 6. USB Removal of Memory Card

 

Error message   
when executing program 

In case that an error message occurs when operating the XGT Panel. 

  Please refer to the 7. Error message when executing program.

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

  

    

Содержание eXP Series, eXP20-TTA

Страница 1: ... partner Human Machine Interface XGT PANEL eXP Series User s Manual eXP20 TTA eXP30 TTA eXP30 TTB eXP30 TTE eXP40 TTA eXP40 TTB eXP40 TTE eXP60 TTA eXP60 TTB Read this manual carefully before installing wiring operating servicing or inspecting this equipment Keep this manual within easy reach for quick reference ...

Страница 2: ...o Warming and Caution and their meanings are as follows Warning Violating the instruction may result in serious personal injury or death Caution Violating the instruction may result in slight personal injury or product damage The indicated illustrations on the product and in the manual have the fallowing meanings Be cautions for danger may be present Be cautions for there is a possibility of an el...

Страница 3: ... power wires Otherwise it may cause erroneous output operation Use the HMI in an environment that meets the general specification contained in this manual or datasheet Otherwise it could result in electric shock fire erroneous operation or deterioration In case of much vibration in the installed environment be sure to insulate the HMI from direct vibration Otherwise it could result in electric sho...

Страница 4: ...ay result in fire electric shock or erroneous operation Tighten terminal screws with specified torque when wiring If terminal screws are loose it may result in short circuits fire or erroneous operation Use the exclusive HMI 3 type grounding for the FG terminal If not grounded it may result in erroneous operation Be sure not to let any foreign substances such as wiring debris inside the module Suc...

Страница 5: ...semble heat short circuit solder etc other battery Mishandling the battery may cause overheating crack fire and may result in injury or fire Do not disassemble PCB from the product case or modify the product Otherwise it may result in fire electric shock or erroneous operation Use cellular phone or walky talky at least 30cm away from the HMI Otherwise it may result in erroneous operation When disp...

Страница 6: ...ion Date Contents Revised location V1 0 16 05 First Edition V1 1 16 07 Additional model eXP20 TTA 1 2 2 1 2 3 3 10 3 6 App2 1 V1 2 17 08 Additional model eXP30 TTA TTE 2 3 4 3 2 11 3 5 App2 2 V1 3 18 05 eXP30 TTAgeneral standard revision 3 1 ...

Страница 7: ... The number of User s manual is indicated the right side of the back cover ⓒ LSISCo Ltd2016 All Rights Reserved ...

Страница 8: ......

Страница 9: ...andards 3 1 3 2 Function Standards 3 3 Chapter 4 System Configuration 4 1 4 13 4 1 Backlight Setting 4 2 4 2 Touch Calibration 4 3 4 3 Date Time Setting 4 4 4 4 Environment Setting 4 5 4 5 Ethernet Setting 4 11 4 6 XP Remote Setting 4 12 4 7 Buzzer Setting 4 13 Chapter 5 Diagnostics 5 1 5 8 5 1 Screen Diagnosis 5 2 5 2 Touch Diagnosis 5 3 5 3 Backup Memory Diagnosis 5 4 5 4 Flash Memory Diagnosis ...

Страница 10: ...onitor 6 8 Chapter 7 Storage Function 7 1 7 4 7 1 General Introduction 7 1 7 2 Downloading Project through the Storage Equipment 7 2 7 3 Uploading Project through the Storage Equipment 7 3 7 4 Updating the Device through Storage Equipment 7 4 Chapter 8 XGT Panel S W Update 8 1 8 1 General Introduction 8 1 Chapter 9 File Backup through External Storage Equipment 9 1 9 7 9 1 Path Structure in case o...

Страница 11: ...MC Standard Certification 12 1 12 1 1 CE standard certification 12 1 12 1 2 KC standard certification 12 2 12 2 Requirement for Low Voltage Command Suitability 12 2 12 2 1 Standard certification for XGT Panel 12 2 12 2 2 Selection of XGT Panel 12 2 Appendix 1 Troubleshooting App1 1 App1 24 1 Type of Problem App 1 1 2 Problem when Starting App 1 2 3 Problem after the Monitor on App 1 4 4 Display Pr...

Страница 12: ...onnection status information of PLC which is connected with XGT Panel Chapter7 Transmission of Project from USB Storage Device It describes the way to execute the project by using USB storage device Chapter8 XGT Panel S W Update It describes the way to update engine at XGT Panel Chapter9 Backup files by using Storage Devices It describes the way to backup recipe logging and etc files by using stor...

Страница 13: ...th control device Status LED When power on USB DEVICE eXP30 40 60 Project download through XP Builder Battery Cover Reset Switch Battery Setting Switch RS 422 485 eXP40 60 Control device that can be communicated such as PLC USB HOST Data Backup alarm logging recipe etc Project data storage image upload project etc Mouse Keyboard RS 485 eXP40 60 RS 422 485 eXP20 30 Control device that can be commun...

Страница 14: ...ty like computer software Fast reaction is available when adding new equipment Wide data sharing and management with upper system is available Later 3 Improvement of project transmission time a It provides Ethernet which is faster than RS 232C b It provides the transmission function from USB storage device 4 High quality screen a It provides the high quality screen and clearness by high quality LC...

Страница 15: ... transmits the Windows User font used in computer to XGT Panel Additional language development is not necessary Multilingual language is an advantage of Windows CE b It can express twelve kinds of language simultaneously It can express 12 kinds of language simultaneously Language switching is available by using special switch during operation c It can provide the various fonts Various expressions ...

Страница 16: ...kup data s type is stored in Excel it is easy to use c Recipe function It provides READ WRITE function It provides 128Kbyte areas for backups General recipe it set up 10 000 double words for each of one of them Backup into the USB storage device is available Backup data s type is stored in Excel it is easy to use d Scheduler function It can be set up to Max 32 e Print function It provides a Screen...

Страница 17: ... XP Builder Software used to write and edit the project XP Manager It is the software for edition download monitoring to realize data communication between XGT Panels through XP Link with online control function XP Remote Software used to remote monitor and control the XGT Panel Cnet module Computer Link FEnet module Fast Ethernet Network RTC Abbreviation of Real Time Clock It is used to call gene...

Страница 18: ...figuration are as follow 2 1 Part Names 1 eXP20 TTA DC eXP20 TTA DC CERTI Items Part Names Descriptions Front Part 1 Analog Touch Panel Input by user s touch 2 LCD Screen indication Power LED Indicating the state of device On BLUE High Luminance Blue LED Panel Mounting Panel Fixing XGT Panel on the panel using bracket ...

Страница 19: ...function Battery Cover Reset Switch Backup Battery Setting Switch Setting Switch No 1 A Side Backup Battery On B Side Backup Battery Off No 2 3 A Side RS 422 485 Terminating Resistance On B Side RS 422 485 Terminating Resistance Off No 4 A Side O S Download Mode B Side Operating Mode Ethernet Terminal Ethernet 10Base T 100Base TX 1 Send Project Data 2 Receive backup data and project file 3 Send XP...

Страница 20: ...uch 2 LCD Screen indication Power LED Indicating the state of device On BLUE High Luminance Blue LED USB Device 1 Logging Recipe Screen Data Backup 2 Send project data and XP Run time 3 Receive back data and project file Panel Mounting Panel Fixing XGT Panel on the panel using bracket Power Terminal Composed of Power Input DC24V and PE Terminal ...

Страница 21: ...itch Backup Battery Setting Switch Setting Switch No 1 A Side Backup Battery On B Side Backup Battery Off No 2 3 A Side RS 422 485 Terminating Resistance On B Side RS 422 485 Terminating Resistance Off No 4 A Side O S Download Mode B Side Operating Mode Ethernet Terminal Ethernet 10Base T 100Base TX 1 Send Project Data 2 Receive backup data and project file 3 Send XP Runtime 4 PLC Control Device C...

Страница 22: ...Logging Recipe Screen Data Backup 2 Send project data and XP Run time 3 Receive back data and project file Panel Mounting Part Fixing XGT Panel on the panel using bracket USB Host 1 USB Memory Connection Backup of data such as alarm logging recipe and storage of screen data Send Receive project data Send XP Runtime 2 User s Interface Connection Using mouse keyboard 3 Printer connection Printing fu...

Страница 23: ...oad Mode B Side Operating Mode Power Terminal Composed of Power Input DC24V and FG Terminal Ethernet Terminal Ethernet 10Base T 100Base TX 1 Send Project Data 2 Receive backup data and project file 3 Send XP Runtime 4 PLC Control Device Communication COM3 Connector RS 422 485 PLC or Control Device Communication COM1 COM2 Connector RS 485 RS 232C PLC or Control Device Communication Remark 1 For fur...

Страница 24: ... Recipe Screen Data Backup 2 Send project data and XP Run time 3 Receive back data and project file Panel Mounting Part Fixing XGT Panel on the panel using bracket USB Host 1 USB Memory Connection Backup of data such as alarm logging recipe and storage of screen data Send Receive project data Send XP Runtime 2 User s Interface Connection Using mouse keyboard 3 Printer connection Printing function ...

Страница 25: ...oad Mode B Side Operating Mode Power Terminal Composed of Power Input DC24V and FG Terminal Ethernet Terminal Ethernet 10Base T 100Base TX 1 Send Project Data 2 Receive backup data and project file 3 Send XP Runtime 4 PLC Control Device Communication COM3 Connector RS 422 485 PLC or Control Device Communication COM1 COM2 Connector RS 485 RS 232C PLC or Control Device Communication Remark 1 For fur...

Страница 26: ...t it to XGT Panel Normally you can connect with XGT Panel using RS 232C Maximum Communication speed is 115 200 bps With Ethernet in use you can transfer project data more quickly With LAN environment built in the following configuration you may use it more easily and effectively 1 1 connection will be supported just in case LAN environment is not built ...

Страница 27: ...o use in details please see the Chapter 7 and XP Builder User s Manual Remark 1 Recommend to transfer project by using Ethernet than RS 232C 2 For how to make Ethernet cable please see the Communication User s Manual 3 For how to transfer project please see XP Builder User s Manual 4 eXP30 TTE DC and eXP40 TTE DC are not support Ethernet ...

Страница 28: ...de 5 f 9 Hz 1 75mm 9 f 150 Hz 4 9m s2 6 Shock endurance Maximum shock acceleration 147m s2 15G Duration time 11ms Pulse wave half sine pulse 3 times each in X Y and Z directions IEC 61131 2 7 Noise Immunity Square wave Impulse noise DC 1 200V LSIS Standard Electrostatic Discharge Immunity 6 kV Contact Discharge 8 kV Air Discharge IEC 61131 2 IEC 61000 4 2 Electromagnetic Radiated Emissions 80 1 00...

Страница 29: ...representing the pollution degree of an environment to determine the insulation of a device pollution degree 2 generally means the status generating non conductive contamination However it also contains the status generating temporarily conduction due to condensation 3 Definition of Overvoltage Categories Equipment of overvoltage category II is energy consuming equipment to be supplied from the fi...

Страница 30: ...te Hour data Logging Alarm Recipe data and nonvolatile device Battery duration Approx 3 years Operating ambient temperature of 50 RTC Time error Approx 3 sec 1day Operating ambient temperature of 25 Ethernet 1 channel IEEE802 1a 10Base T 100Base TX USB Host 1 channel USB 2 0 Host mouse keyboard printer and USB memory driver is available USB Device 1 channel USB 2 0 Device for download and upload p...

Страница 31: ...onvolatile device Battery duration Approx 3 years Operating ambient temperature of 50 RTC Time error Approx 3 sec 1day Operating ambient temperature of 25 Ethernet 1 channel IEEE802 1a 10Base T 100Base TX USB Host 1 channel USB 2 0 Host mouse keyboard printer and USB memory driver is available USB Device 1 channel USB 2 0 Device for download and upload project file RS 485 RS 232C 2channels RS 485 ...

Страница 32: ...witch No 1 4 Battery Operation and Life Battery is used for RTC date time when the power of device is off Battery is not consumed with power applied 5 LCD Backlight Replacement Please replace LCD if you want to replace LCD backlight 6 Protection standard XGT Panel is designed by IP65 Standard in front parts Ingress Protection IP is based on the IEC 60529 Standard for degrees of protection provided...

Страница 33: ......

Страница 34: ...escribes the system configuration including XGT Panel s time setting Ethernet connection setting and Backlight settings If you press Settings button in XGT Panel s Main screen you can set XGT Panel s environment as follows XGT Panel main screen System Configuration screen ...

Страница 35: ...screen Backlight setting screen Dialog box setting option Name Description Brightness It may adjust brightness of backlight Do not turn off backlight It doesn t turn off backlight power Turn off backlight after idle time It automatically turns off backlight if not in touch for a certain period of time Turn off minutes It turns off backlight after a designated time unit of minute ...

Страница 36: ...ss five marks XGT Panel s touch location adjustment is completed XGT Panel setting screen Touch setting screen Remark 1 XGT Panel s Touch Calibration setting is basically set If Touch location is way off adjusting menu with touch can be hard through touch In that case You can select the Touch Calibration setting menu by USB mouse or simply touch 5 times at the empty space on the main screen 2 When...

Страница 37: ...g If you press DateTime Setting button in System Configuration as follows you can set XGT Panel s data and time Remark You can set data time at device information of communication dialog at the XP Builder For details please refer to the XP Builder s manual ...

Страница 38: ...ystem Configuration 4 5 4 4 Environment Setting If you press Environment Setting button in System Configuration screen as follows you can set Auto Goto Screen and Buzzer On Off XGT Panel setting Environment screen ...

Страница 39: ...Chapter 4 System Configuration 4 6 Environment General Environment General Environment setting screen ...

Страница 40: ...his case if you want to go out to the waiting screen you have to use the special switch to close the monitoring screen Enable Arabic text display right left It enables the language indicated from right to left directions Set startup screen The screen that corresponds to the number entered at the start of the monitoring is displayed first Hide mouse cursor After the screen has been moved to another...

Страница 41: ... RAPIEnet communication setting data XP manager setting data and etc Setting through Environment Setting menu of device is not initialized If the menu is not in English it is necessary to reboot device to delete the multilingual related files Set Background Image If you select the image through Set Background Image background image of waiting screen is set as the selected image If you want to canc...

Страница 42: ...ays the following message and must be downloaded from the XP Builder You can prepare your download then go to the Start menu in XP Runtime and use the menu after using the printer settings from XP Builder Printer driver and Information None Download Required The printer driver is ready to use ...

Страница 43: ...ttings Cancel To cancel the setting Printer Check To diagnose the connection status of the printer This feature is only supported Sewoo printer LK P30 LK P41 LK P43 Press the button to display the current printer status Please mount again the printer cable if the printer is already powered with the cable connected Messages 1 OK Normal state 2 No Printer Not connected to the printer 3 Cover Open Pa...

Страница 44: ...ateway By pressing OK button changed IP information is reserved Remark We recommend the following method when connecting with PC solely If you reboot after pressing Disable button the device will not use Ethernet In this case booting speed gets faster If you use Ethernet again reboot after pressing Enable 1 XGT Panelsetting IP Address 192 168 0 10 SubnetMask 255 255 255 0 Gateway 192 168 0 1 2 PCs...

Страница 45: ...ions It designates the maximum number of XP Remote connected with XGT Panel Timeout value It stops communication when there is no request of communication from XP Remote within the designated time In case XP Remote is entitled to manipulation it withdraws the right to manipulation 10 300 seconds Enable control by XP Remote after Monitor Start XGT Panel will automatically allow state control after ...

Страница 46: ...d height of XGT Panel Buzzer XGT Panel Setting Buzzer Settings Screen Dialog box setting option Name Description Buzzer On It may turn on or off the buzzer that occurs when in touch mode Buzzer volume It may adjust the volume of Buzzer Buzzer tone It may adjust the tone of Buzzer ...

Страница 47: ......

Страница 48: ...ostics It describes the diagnosis function for XGT Panel s communication terminal screen and touch function If you press Diagnostics button on the XGT Panel s basic screen the menu for diagnosis shows up Main Screen Diagnostics setting screen ...

Страница 49: ...creens continuously change into diverse color with buzzer After all screen for diagnosis pass Then Close button shows up with white ground If you press Close button the initial screen shows up Diagnosis screen Screen diagnosis Display Sequence RED GREEN BLUE BLACK WHITE GRAPH ...

Страница 50: ... the screen the touched location is displayed as follows If pressing the OK button you can quit the screen If the touched location is not correct reset the Touch setting For detailed information please refer to the Chapter 4 2 Touch Calibration Touch diagnosis ...

Страница 51: ... If NVRAM Data Access Fail error is occurred please contact with customer service center 2 If BATTERY STATUS BAD error is occurred battery should be changed Please contact with Customer service center If the DIP switch No 1 is set up as B please set it up as A The B is the mode in which the backup battery is not used Completion of Backup Memory diagnosis ...

Страница 52: ...sh Memory Diagnosis If you press Flash Memory button you can see the result of diagnosis in the result widows Remark If Read Disk Information Error occurs please contact with Customer service center Completion of Flash Memory diagnosis ...

Страница 53: ...utton the result of diagnosis shows up in the result windows Remark If Read Disk Information Error occurs remove it first and test it after inserting it again If the error message shows up repeatedly please contact with customer service center Completion of USB Memory diagnosis ...

Страница 54: ...ation Diagnosis If you press Serial button you can diagnose Serial ports which is equipped at XGT Panel In case of diagnosis purpose you have to connect the loop back terminal at each port Serial port selection Completion of serial port diagnosis ...

Страница 55: ... and 3 pin The RS 485 and RS 422 485 port terminal should be made as follows Only eXP40 60 Connect the RS 485 No 1 with RS 422 485 No 2 and No 4 Connect the RS 485 No 6 with RS 422 485 No 1 and No 3 eXP20 eXP30 TTA DC does not provide for the communication diagnostics of RS 485 422 communication ...

Страница 56: ... Status 6 1 Chapter 6 Viewing Information of PLC Connection Status PLC Information it shows XGT Panel configuration PLC CPU status and various records Remark You can check the status of PLC connection after project data is transmitted into XGT Panel ...

Страница 57: ...ou can select Settings button to change PLC communication settings PLC information screen PLC Communication Configuration setting Remark PLC Communication Configuration setting dialog box may look different depending on drivers For further information about the settings please refer to the PLC user manual ...

Страница 58: ...ction information Dialog box Description Name Description Connection No The communication connection No is displayed from No 0 15 Vendor The vendor of the communication target device is displayed Target device The communication target device is displayed Connection type The connection type is displayed Timeout value The set up timeout value is displayed Send wait value The transmission wait value ...

Страница 59: ...The following PLC is available for view of PLC information MASTER K CPU FEnet Cnet GLOFA GM CPU FEnet Cnet XGK XGB XGI XGR CPU FEnet Cnet 6 4 History of PLC Error You can check the PLC Error History Remark The following PLC is available for viewing Error History MASTER K CPU doesn t have the Error History GLOFA GM CPU FEnet Cnet XGK XGB XGI XGR CPU FEnet Cnet ...

Страница 60: ...y MASTER K CPU doesn t have the history about operation mode conversion GLOFA GM CPU FEnet Cnet XGK XGB XGI XGR CPU FEnet Cnet 6 6 History of PLC Power You can check the history about when PLC was turned on and off Remark The following PLC is available for viewing the history of when our PLC was turned off and on MASTER K CPU doesn t have the history about when our PLC was turned on and off GLOFA ...

Страница 61: ...u can check history about PLC system Remark The following PLC is available for viewing history about system MASTER K CPU doesn t have the history about system Only GLOFA GM CPU GM4C has the history about system Other CPUs don t have the history about system XGK XGB XGI XGR CPU FEnet Cnet ...

Страница 62: ...ting options Name Description Use N 1 Communication The matter of performing N 1 communication is designated N 1 station number The station number of N 1 communication is input Number of XGT Panel The number of XGT Panel in N 1 communication is input Master Holding Time The master holding time of N 1 communication is input Remark For detail information about the N 1 communication please refer to t...

Страница 63: ... adopt Ladder language of XGK series can be monitored Remark Program Monitor driver can be downloaded from XP Manager Only support for XGK XGB CPU Cnet Enet communication To enable the Program Monitor button program monitor should be checked in which locates in the XP Builder project property menu ...

Страница 64: ...lly However when those connections are not available you can use USB storage equipment XGT Panel main screen 1 If you touch Storage Function the following dialog box shows 2 In case of downloading the project by using USB storage equipment touch Project Download button 3 In case of transmitting the project data stored in the device to USB storage equipment touch Project Upload button 4 In case of ...

Страница 65: ...geted external memory in Select Source Following path is indicated depending on the selected external memory USB USB Storage XP_Project In case of downloading the project by using storage equipment the project should be saved in the one lower directory between those directories 3 Select one among directory lists and touch OK 4 Touch OK button then download is started ...

Страница 66: ...owing path is indicated depending on the selected external memory USB USB Storage XP_Backup 3 If you touch OK button project backup file is transmitted to the selected path 4 The project backup file is saved when Download project backup file is selected when downloading the project If you don t select project backup file is not saved in the device and transmission to the storage equipment is not a...

Страница 67: ...l memory in Select Source Following path is indicated depending on the selected external memory USB USB Storage XP_Software In case of updating the device by using storage equipment the XGT Panel Software project should be saved in the one lower directory between those directories 3 If you touch OK button the device is updated with XGT Panel Software in the designated path ...

Страница 68: ...hod Select Upgrade Update XGT Panel on the XGT Panel s main screen Then XGT Panel becomes update mode In order to return to the main screen touch a MENU button or touch the screen for 3 seconds After downloading XGT Panel software from LSIS website make a temporary folder and save it Designate the folder where the software will be saved in the XP Builder s XGT Panel Update windows and update XGT P...

Страница 69: ......

Страница 70: ...p data of logging recipe and screen image 1 XGT Panel can back up the logging recipe and screen image data at USB storage equipment according to setting in XP Builder 2 In case there is no space for backup in the designated storage equipment it continues backup deleting previous data or stops backup according to setting in XP Builder 3 Monitors attachment status of backup equipment at XP Builder ...

Страница 71: ...inHour EndHour 0 space for one folder is full HH BeginMinute FF Lhhmmss0 CSV Recipe Rhhmmss0 CSV same as lower structure of each logging number DD BeginHour EndHour 1 DD BeginHour FF There is free space for one folder 1 Logging Number 2 same as lower structure 1 ScreenImage Shhmmss0 BMP same as lower structure of each logging number Root directory of CF or USB storage equipment There is free space...

Страница 72: ...2010 10 01 15 0 f In case there is the year month directory having same start day and end day when changing directory s name due to over 500 day directories or change of month last digit index number increases Ex In case there are three year month directories that are having over 500 day directories created in October first and 2010 year October directory 2010 10 01 01 0 2010 10 01 01 1 2010 10 01...

Страница 73: ...f USB storage device 2 Directory in the name of Year and Month will be formed below the Memo Directory 3 Structure of directory thereafter is same as that of logging backup route 4 Memo backup file has the name made of hour minute second when it was created a Backup file is created in the type of bitmap b File name starts with M that represents the screen image which includes the index information...

Страница 74: ...s case you have to delete directory including the changed hour and its lower directory for normal operation For example if you change time from December 10 th to December 5 th you have to delete year month directory created in December 10 th and restart the device 2 Sorting by project is not supported for each logging recipe screen image For example there are no 1 2 and 3 logging groups in the pro...

Страница 75: ... deleted 2 Searches the oldest day directory under the oldest year month directory 3 Searches the oldest hour directory under the oldest day directory 4 Deletes the oldest backup file under the oldest hour directory 5 Checks the space and if more space is necessary the above steps of 1 4 are repeated and checks the space 6 When deleting file in case all data in time directory are deleted relevant ...

Страница 76: ...rder to use this monitoring function you have to set about system alarm window and then the project should be downloaded In case USB storage equipment is removed during operation after setting the path for saving Logging backup file as USB storage equipment and downloading the project into device the designated system alarm HS951 0 is set In case storage equipment is equipped again alarm is reset ...

Страница 77: ...quipped again alarm is reset In case USB storage equipment is removed during operation after setting the path for saving Screen Image backup file as USB storage equipment and downloading the project into device the designated system alarm HS951 2 is set In case storage equipment is equipped again alarm is reset Internal address of the designated system alarm can be checked in XP Builder as follows...

Страница 78: ...rwise the screen may be changed or cause malfunction f This machine should be installed within 10 85 relative humidity Moisture by rapid temperature change can cause malfunction and damage g Avoid corrosive gas and burnable gas h Dry location use only 2 Installation construction a When doing screw s processing or wiring construction be careful that the remains do not enter the XGT Panel inside b I...

Страница 79: ...ts of water 5 3 IP20 rating guarantees protection from solid foreign objects of 12mm diameter and greater 2 but it does not guarantee protection from water ingress b Notices 1 In the environment where the protection grade of XGT Panel is exceeded or not satisfied the damage of the device or malfunction can occur due to the failure of protecting the product 2 Since the protection grade of XGT Panel...

Страница 80: ...e remains do not enter into XGT Panel 10 1 3 Notice in installing the panel Here describes how to install XGT Panel in panel and notice 1 Panel cut Before installing the XGT Panel in panel panel should be made with the following dimension Classification X Wide Y Height Z Thickness eXP20 TTA DC eXP20 TTA DC CERTI 119 1 93 1 1 6 9 5 0 0 eXP30 TTA B DC eXP30 TTE DC 156 1 123 5 1 0 0 eXP40 TTA B DC eX...

Страница 81: ... the above explanation 2 When installing consider the power and communication cable wiring 3 In case when the size of the panel cut exceeds the range of the standard allowance 0 1mm when producing panels the contact area between Gasket and the panel can get small which can weaken the waterproof dustproof effect When mounting the XGT Panel inside a panel ensure that you use the gasket to protect ag...

Страница 82: ...aged by the deterioration after the use for a certain period of time the waterproof dustproof effect can be noticeably weakened In case when Gasket should be replaced contact the agency or a sales office close by 3 Installation location When installing the XGT Panel consider screen and use of touch When you don t see within the following angle you may not see clearly When installing consider angle...

Страница 83: ...on XGT Panel should be closely contacted to the panel not to have any gap In the environment requiring waterproof dustproof effect install and fix a bracket on a slope 2 The bracket should be fixed symmetrically up down left right In case when it is not fixed symmetrically there could be a gap between the panel and XGT Panel 3 When fixing the bracket it should be installed perpendicularly to the p...

Страница 84: ...TTE DC eXP60 TTA B DC If AC power is applied into the product for DC power It may cause damage or fire Be careful of connection DC is the product which use DC 24V When using the product Please check the label in the back of the product All field wiring connections to this unit shall be from Limited Voltage Limited Current below 24Vdc isolated secondary source with an output fused with a 4A fuse ma...

Страница 85: ...s are also recommended between the point of supply and the XGT panel 3 For safety reasons it is recommended that you use color coded outer sheaths on the conductors to aid safe terminations Wiring of power is as follows DC Power connection Remark 1 Use a regulated power supply transformer when the power fluctuation is bigger than the standard 2 If electromagnetic interference is experienced or exp...

Страница 86: ...cable Maintain a minimum separation of 100mmbetween cables Use a lightning surge protector to prevent damage from lightning strikes Remark 1 Separate E1 the ground connection for lightning surge protector and E2 the ground connection for XGT Panel 2 Set lightning surge protector to below the allowable surge voltage to provide protection if the voltage increases to its maximum E2 XGT Panel E1 Surge...

Страница 87: ...y noises specially the ground is not needed When you use the ground connection refer to the following information 2 Use the exclusive ground connection When you install the ground connection use the third grounding resistance less than 100Ω 3 If you cannot use the exclusive ground connection use the common ground connection like below A Exclusive ground Best B Common ground Good C Common ground Po...

Страница 88: ...ing Screw the unwound terminal Getting loose of communication connector There is no unwinding Screw the unwound terminal Reserved part Amount of reserved part and reservation Check the status Refill the insufficiency and improve the reservation Gasket installation status No gap between the gasket and panel Replace gasket or affix brackets firmly Gasket status No damage or deterioration Replace gas...

Страница 89: ...onnector Loose brackets Retighten screw with Screwdriver Not loose Retighten screws Power voltage maintenance Check the power voltage of input terminal of power by test AC100 240V AC85 264V DC24V DC19 2 28 8V Supply power modification Battery Check when battery is exchanged and voltage drop is indicated It is expressed by system alarm Check the total of power stoppage time and guarantee duration T...

Страница 90: ...lace Battery With Hitachi Maxell Part No CR2032 Only Use of Another Battery May Present A Risk Of Fire or Explosion See Owner s Manual For Safety Instructions WARNING Battery may explode if mistreated Do not recharge disassemble or dispose of in fire 3 As the eXP model has the integrated LCD and backlight the LCD should be replaced when the life is over or it is out of order ...

Страница 91: ......

Страница 92: ...l the EN61000 6 4 EN61000 6 2 EN61000 3 2 and EN61000 3 3 of CE standards were applied Applied Standards Results 1 Emission Conducted Disturbance EN61000 6 4 2007 A1 2011 C Radiated Disturbance EN61000 6 4 2007 A1 2011 C Harmonic Current Emission EN61000 3 2 2014 N T Voltage Change Fluctuations and Flicker EN61000 3 3 2013 N T 2 Immunity Electrostatic Discharge EN61000 6 2 2005 AC 2005 C EN61000 4...

Страница 93: ...ribes attention about installation and wiring for the suitability when using the XGT Panel Though the following data is made by requirement of regulation and standard we don t guarantee that all devices are suitable for the above command The method to be suitable for the EMC command and judgment of suitability should be finally made by device manufacturer himself 12 2 1 Standard certification for ...

Страница 94: ...Please refer to the 3 Problem after the Monitor on Display problem of figure and object In case that the figure or object is different from when editing Please refer to the 4 Indication problem of figure and object Communication problem In case that communication is not executed properly Please refer to the 5 Communication problem USB Removal of Memory Card In case that USB device is not working f...

Страница 95: ...ed Please check the followings Display color Contents BLUE Power is supplied to XGT Panel When applying the option Go to Screen after boot up it displays Failed to load image files as the monitoring has not been started Phenomenon After storing images in the USB storage device and then selecting the option Go to Screen after boot up in the start menu in case when re permitting the power of the equ...

Страница 96: ...er initialization option Reset USB Power of the equipment is selected cancel the selection and then permit the power again The Reset USB Power option is an additional function to improve the initialization of the storage device with slow recognition speed or low recognition ratio Depending on the characteristics of the storage device however the power initialization can be an obstacle to the initi...

Страница 97: ...ter setting to use buzzer check whether the buzzer sounds or not in the 1 s setting windows Phenomenon After the system alarm about the lack of system memory occurs XGT Panel itself closes the monitoring and then moves to the start menu in unspecific time without user s operation Causes 1 The memory usage could be exceeding 95 2 The memory usage can be a bit increased when floating pop up windows ...

Страница 98: ...memory once the amount of image exceeds a certain limit Whenever they are needed thus they are read from the file system and then expressed on the screen This could be the reason why the screen operation speed gets slowed down Solution 1 In case of using vector image instead of raster image the memory share can be reduced In the graphic library of XP Builder the image group marked as OOO_R is the ...

Страница 99: ...hown Word Lamp Image is not shown N State Lamp Image is not shown Clock Present time is shown Bit Message Message is not shown When designating the background image image is shown as it is Word Message Message is not shown When designating the background image image is shown as it is Numeric Display The value is not shown When designating the background image image is shown as it is Numeric input ...

Страница 100: ... viewing data list of object is shown as it is Logging Viewer Change doesn t occur When communication is normal the recorded log data is shown normally But log data is shown as when communication is abnormal Navigator Change doesn t occur Because it shows the group of alarm already developed though communication is abnormal if it has alarm data already developed it shows the name of group where ea...

Страница 101: ...s of previous screen can occur during the time out hour The folded object doesn t sequentially show up Phenomenon The number under the data list shows up above data list Cause 1 The device value is expressed at the top of object screen Solution 1 It is normal status The folded window or part object is not included in screen regardless of sequence of drawing the object changed recently is expressed...

Страница 102: ... that communication doesn t work Phenomenon Communication doesn t work Cause 1 Communication setting or cable may be not normal Solution 1 In case of RS 232C check whether connection setting is normal or not in XP Builder 2 In case of RS 422 485 check whether station and communication connection setting is normal or not 3 If 1 2 is normal do diagnosis about PLC RS232C PLC RS485 422 at the Serial d...

Страница 103: ...SB external memory is not flickering After the repeated attachment detachment of the USB storage device it is not recognized Phenomenon It can happen when the attachment detachment of the USB device is repeated for a short period of time Cause 1 When the USB device is recognized or removed it takes a certain period of time maximum a few seconds to recognize it When the storage device is quickly in...

Страница 104: ... If this symptom is repeated when turning power off and on remove XGT Panel s power and exchange the battery 0x03 XGT Panel Write Operation FAILURE The built in Flash disk has an error Contact the near Customer Service Center 0x04 XGT Panel Read Disk Information Error The built in Flash disk has an error Contact the near Customer Service Center 0x05 XGT Panel Write Operation FAILURE Check that CF ...

Страница 105: ...operty information Number indication device Number input device 0x06 h01 XGT Panel Can t write Data Because of communication error the value can t be inputted Check the communication status and input again h02 XGT Panel No input Data You tried to input with no value Input the value 0x03 XGT Panel Exceeded the max length You exceed the maximum length to input 0x04 XGT Panel Exceeded the minimum Val...

Страница 106: ...t downloading is stopped when it fails to make this file because of device error If this problem is repeated Contact the near Customer Service Center 0x03 XP Builder Invalid Backup Media Communication status is abnormal Route information is not correct to save project data If this problem is repeated Contact the near Customer Service Center 0x04 XP Builder Failed to Create version File In case tha...

Страница 107: ... equipped at device By the way now it can t read information about USB storage device Check the installation status of USB storage device and if it is normal check USB storage device If this problem is repeated contact Customer Service Center 0x0A XP Builder Failed to read Flash memory information In case that it can t know information about memory status download is stopped If this problem is rep...

Страница 108: ... it is designated as CF card it can occur in case CF card is not installed If this problem is repeated and not referred in the above contact Customer Service Center 0x11 XGT Panel Failed to delete previous project archive Please reboot XGT Panel The project backup file downloaded already can be deleted because of error of XGT Panel Reboot XGT Panel If this problem is repeated contact Customer Serv...

Страница 109: ...ce Center 0x19 XGT Panel Failed to unmarshall download file Please download project again The data divided according to the contents is moved to the original storage location but when this fails downloading is stopped If this symptom is repeated contact Customer Service Center 0x1A XGT Panel Failed to install new project data files Please download project again The downloaded project is not instal...

Страница 110: ...nel Cannot find project data in USB Storage There is no USB or device status of USB is not good or project is not saved properly 0x52 XGT Panel Project information file is not in USB Storage The project is not saved normally in the USB Check whether there is XP_Project folder and project name inf in the USB or not 0x53 XGT Panel Failed to read project information file It can t read project informa...

Страница 111: ... version information file But when it can t read this file because of the device error downloading is stopped because it doesn t know the version If this symptom is repeated contact Customer Service Center 0x5A XGT Panel Download data format version is not matched Please update XGT Panel Data storage type is not correct Update XGT Panel 0x5A XGT Panel Download data format version is not matched Pl...

Страница 112: ... invalid The font file s name is saved incorrectly Save the project in the USB again If this symptom is repeated contact Customer Service Center 0x62 XGT Panel Font file is not downloaded The font file which is needed for project is not saved in the USB storage equipment Save the project in the USB If this symptom is repeated contact Customer Service Center 0x63 XGT Panel Font file size is invalid...

Страница 113: ...d contact Customer Service Center XGT Panel booting 0x28 0x01 XGT Panel Previous instance is not terminated XGT Panel software was already started Reboot the device If this symptom is repeated contact Customer Service Center 0x02 XGT Panel Start Server Fail Restart XGT Panel The XGT Panel software can t initialize the communication status normally Check the communication status again If this sympt...

Страница 114: ... update mode update again If this symptom is repeated contact Customer Service Center Communica tion between other XP Builder XGT Panel 0x29 0x30 XGT Panel Failed to modify password file The device connection password can t be modified because of error of Flash Disk of XGT Panel Reboot the device If this symptom is repeated contact Customer Service Center 0x31 XGT Panel Password related command tr...

Страница 115: ...formation list to update is empty Check the module folder newly designated at XP Builder and if there is no error download XGT Panel module and try update again If this symptom is repeated contact Customer Service Center 0x25 XP Builder Downloaded file is not Module to download The wrong file which is not in the new module list of XGT Panel is downloaded Try update of XGT Panel again If this sympt...

Страница 116: ...is developed by downloading wrong module or communication error Touch FlashDisk LSISProduct Update exe and set the device as update mode Then update again If this symptom is repeated contact Customer Service Center 0x2C XGT Panel improper communication command Current state is not authorized To reboot the engine is not available because of wrong file which is developed by downloading wrong module ...

Страница 117: ... XGT can t be set as update mode because of XGT Panel error After downloading new XGT Panel module through homepage etc copy UpdateNew exe file among new module to the FlashDisk LSISProduct directory of XGT Panel through the movable storage equipment Then reboot the XGT Panel and go update mode and update again If this symptom is repeated contact Customer Service Center ...

Страница 118: ...Appendix 2 Dimension App2 1 Appendix 2 Dimension Unit mm 1 eXP20 TTA DC eXP20 TTA DC CERTI 102 64 92 3 32 0 2 128 126 5 118 3 ...

Страница 119: ...Appendix 2 Dimension App2 2 2 eXP30 TTA B DC eXP30 TTE DC eXP30 TTA DC eXP30 TTE DC 163 5 155 5 165 0 2 132 5 0 2 36 1 0 2 90 120 123 ...

Страница 120: ...Appendix 2 Dimension App2 3 3 eXP40 TTA B DC eXP40 TTE DC eXP40 TTA DC eXP40 TTE DC 191 5 144 9 208 0 2 154 0 2 137 5 166 5 44 4 0 2 144 1 ...

Страница 121: ...Appendix 2 Dimension App2 4 4 eXP60 TTA B DC 107 6 276 0 3 218 0 3 201 5 107 3 44 4 0 3 208 1 107 6 259 5 127 3 ...

Страница 122: ...ignated by the company 4 Due to unintended purposes 5 Owing to the reasons unexpected at the level of the contemporary science and technology when delivered 6 Not attributable to the company for instance natural disasters or fire 3 Since the above warranty is limited to HMI unit only make sure to use the product considering the safety for system configuration or applications Environmental Policy L...

Страница 123: ...ijing China Address B Tower 17FL Beijing Global Trade Center B D No 36 East BeisanHuan Road DongCheng District Beijing 100013 P R China Tel 86 10 5825 6027 666 Fax 86 10 5825 6028 e mail xunmj lsis com cn LSIS Guangzhou Office _ Guangzhou China Address Room 1403 14FL New Poly Tower 2 Zhongshan Liu Road Guangzhou P R China Tel 86 20 8328 6754 Fax 86 20 8326 6287 e mail chenxs lsis com cn LSIS Cheng...

Отзывы: