background image

How to set relay elements

Setting Items

INSTANTANEOUS: Indicates instantaneous elements

Indicates the instantaneous action time, and setting range can be
selected up to 30~250ms

Indicates the instantaneous current TAP value, and set by same
method of the 

-1.

③-

1 Indicates time delay current TAP value, and means the multiples

of the CT ratio.
ex) When the CT ratio 100/5, and the correction value is 0.8In as

in the picture In indicates CT ratio, and 0.8 is the multiple.
Therefore, the correction value is...

Based on CT 1st: 0.8 X100 (CT 1st rating) =80A

Based on CT 2nd: 0.8 X5 (CT 2nd rating) =4A

Time Delay: Indicates the time delay element.

It is an item to select characteristic curve. In GIPAM, it supports
Definite-time (DT) and 7 curves of inverse time (SI, VI, EI, LI, KSI,
KVI).

This is an item to select the Time Lever. The setting ranges are up to
0.05~1.2 and can select in 0.01 units. (Can only be corrected when
selecting inverse time curve at 

)

When the definite time curve (DT) is selected at 

, Time Lever

correction as shown in the picture above is not possible.

Indicates the definite time operation time, and the setting range can
be selected up to 0.05~300.00sec.

This item indicates the Constant Time Delay, and can be selected up
to 0.0~10.00sec. (Can only be corrected when selecting the inverse
time curve at 

)

When selecting the Time Lever, if protection is not possible because
the relay’s operation characteristic curve is on the load characteristic
curve, even though the Lever is selected to its maximum, increase
the relay’s operation characteristic curve to delay the operation time
as much as the changed time in this item.

For some of delay elements such as OCR and OCGR, can be set by
synthesizing Low and High curves considering the characteristics of
the loads.

Can select 
protective relay 
element by using

  
.

Put a     in [  ] to 
select the relay, 
by pressing

  
.

Use                   to put a  
in [  ], to select the
feature you want to use.

When every correction is 
completed with the same 

method, press          to save 
the correction value.

Move 
cursor with

The save will be 
completed 
by pressing

  
.

  
.

Go back to the 
previous 
screen by pressing

  
.

Move 
cursor with

To input correction values for 

other relay elements, go 

through the            process.

  
.

Input the 
value by 
using

  
.

Generate a 
cursor by 
pressing

  
.

Input the 
value by 
using

  
.

5-3

Содержание GIPAM 2000

Страница 1: ...s will be skipped and Close Open operation will be conducted through and processes 4 The password is required only when inputting correction values conducting controls and rebooting Checking status and measurement value monitoring will be still available without password Function key Direction key Status LED Operation Power status indication Lights up when operation power is approved Indicates com...

Страница 2: ...mes X 1 times X 1 times Save will be completed by pressing Each Input output contact s names are changeable G2K Manager When faulty connection occurs it must be confirmed as PF power factor and Wh Wattage can be varied But it can be confirmed after the ceiling voltage and current are approved Picturized item of input voltage and phase of current DI DO Monitoring CB2 ON OFF status indication LED se...

Страница 3: ...not possible Indicates the definite time operation time and the setting range can be selected up to 0 05 300 00sec This item indicates the Constant Time Delay and can be selected up to 0 0 10 00sec Can only be corrected when selecting the inverse time curve at When selecting the Time Lever if protection is not possible because the relay s operation characteristic curve is on the load characteristi...

Страница 4: ...e operation Relay Operation OVR time delay T Low set R S phase operation Relay Operation SGR Vo Io operation Output contact status change CB1 ON output contact ON OFF ON Output contact status change CB1 ON output contact OFF ON OFF Output contact status change CB1 OFF output contact ON OFF ON Output contact status change DO 01 output contact OFF ON OFF Output contact status change CB1 OFF output a...

Страница 5: ...us time delay and Low High set are not classified OVR time delay action Low set Fault cause R phase over voltage Fault value Va 7 3kV POR time delay action Fault cause T phase voltage phase sequence Fault value Va 6 6kV Vb 6 7kV Vc 0 0V SGR time delay action Faultcause Vo Io zero phasesequencevoltage zerophasecurrent Fault value Vo 52V Io 0 325A Ph 43 5 DGR time delay action Faultcause Vo Io zero ...

Страница 6: ...com cn LSIS Wuxi Co Ltd Wuxi China Address 102 A National High New Tech Industrial Development Area Wuxi Jiangsu 214028 P R China Tel 86 510 8534 6666 Fax 86 510 522 4078 e mail luw lsis com cn LSIS VINA Co Ltd Hanoi Vietnam Address Nguyen Khe Dong Anh Ha Noi Viet Nam Tel 84 4 882 0222 Fax 84 4 882 0220 e mail sjbaik lsis biz LSIS VINA Co Ltd Hochiminh Vietnam Address 41 Nguyen Thi Minh Khai Str Y...

Отзывы: