background image

iS7 Ethernet Option Manual

 

 

1. 

Introduction 

 

Ethernet  communication  option  module  connects  the  iS7  inverter  to  the 
Ethernet  network.  It  supports  2  kinds  of  protocol,  Modbus/TCP  and 
Ethernet/IP.   
Controlling and monitoring of inverter can be done by PLC sequence program 
or  any  Master  Module.  Since  Ethernet  which  constitutes  Internet  has  been 
used and IPv4 has been supported, wherever Internet can be done, controlling 
and  monitoring  is  possible.    But,  Ethernet  network  of  the  factory  has  to  be 
connected to Internet through Gateway. 
With  simple  wiring,  installation  time  can  be  reduced  and  maintenance 
becomes easier. 

 

2. 

Ethernet Technical Features 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

3. 

Product Constituents 

This product is consisting of the Ethernet communication module, a screw and 
User Manual. 

Transmission Speed 

10Mbps, 100Mbps 

Transmission Method 

Baseband (Half, Full Duplex) 

Max. Extended Distance between 
Nodes 

100m (Node - Hub) 

Max. Node Number 

Hub connection 

Auto Negotiation 

Supported 

Max. Frame size 

1500 Bytes 

Communication Zone Access Method 

CSMA/CD 

Frame Error Checking Method 

CRC32 

Recommended Connecting Socket 

3 Socket 

Recommended Cable

 

UTP, FTP, STP   
(Refer to page 6 for details.) 

Содержание iS7 RAPIEnet

Страница 1: ...sure to read and become familiar with the safety precautions at the beginning of this manual If you have any questions seek expert advice before you proceed Do not proceed if you are unsure of the saf...

Страница 2: ...factory has to be connected to Internet through Gateway With simple wiring installation time can be reduced and maintenance becomes easier 2 Ethernet Technical Features 3 Product Constituents This pr...

Страница 3: ...rnet Option Module 1 The External of Ethernet option module Modbus TCP LED Composition LINK SPEED and CPU LED have a green color ERROR LED has a red color Ethernet IP LED Composition LINK and SPEED LE...

Страница 4: ...iS7 Ethernet Option Manual 4 2 Mounting the communication option module on iS7 inverter...

Страница 5: ...in3 and 6 are twisted together Pin No Signal Description Cable Color 1 TX Transmitting data plus White Yellow 2 TX Transmitting data minus Yellow 3 RX Receiving data plus White Green 4 NONE Not used B...

Страница 6: ...Classi fication Details Purpose of cable UTP U UTP Unshielded Twisted Pair cable for high speed signal Maximum 200MHz Voice Information Data Low video signal FTP S UTP Foil screened Twisted Pair cabl...

Страница 7: ...No 2 3 and 4 of switch are not available Switch State Protocol OFF Switch at the upper position Modbus TCP ON Switch at the lower position Ethernet IP If the option module is operating protocol will...

Страница 8: ...on the Ethernet communication card M E COM 10 Opt Parameter1 0x0000 0x0000 0xFFFF Sets up the IP Address M E COM 11 Opt Parameter2 0x0000 0x0000 0xFFFF COM 12 Opt Parameter3 0x0000 0x0000 0xFFFF Sets...

Страница 9: ...y set up according to the CIP Output Instance E COM 51 Para Control 1 0x0005 0x0000 0xFFFF The Client sets up the reference Inverter Data Address E COM 52 Para Control 2 0x0006 0x0000 0xFFFF The Clien...

Страница 10: ...lled in the iS7 3 FBus Led COM 09 Indication of LED information In case of Modbus TCP Displays the ON OFF statuses of the 4 LEDs on the communication card on the keypad parameter COM 09 Looking up the...

Страница 11: ...sk Gateway Address COM 10 15 Setting The IP version supported by Ethernet option is v4 All the addresses and masks are expressed with decimal decimal decimal decimal and each decimal number is 0 255 I...

Страница 12: ...b in automatic speed setting mode Auto Negotiation the connection will be made at changed speed 6 CIP Input Instance COM 17 This parameter is shown only when the protocol has been set up with the Ethe...

Страница 13: ...See the Assembly Object section of the Ethernet IP 8 Para Status COM 30 38 This parameter is not used in case of Modbus TCP This parameter appears only when the set value of the Input Instance COM 17...

Страница 14: ...is reflected on the Modbus TCP communication card and only this card will be restarted 9 Inverter Communication Address See Chapter 11 Communication Function Inverter IS 7 Manual 10 Modbus TCP Frame...

Страница 15: ...rter Read Holding Registers The function used to read the data in the Inverter Server Constitution of the frame requested from Client to Server Constitution of the frame sent from Server to Master in...

Страница 16: ...sted from Client to Server Requested Frame Length Value Function code 1 Bytes 0x04 Comm address 2 Bytes 0x0000 0xFFFF The number of data requested 2 Bytes 1 16 LSIS Inverter standard Response Frame Le...

Страница 17: ...nse Frame Length Value Function code 1 Bytes 0x06 Comm address 2 Bytes 0x0000 0xFFFF Data Value 2 Bytes 0x0000 0xFFFF Requested Frame Length Value Function code 1bytes 0x10 Comm address 2bytes 0x0000...

Страница 18: ...n is requested ILLEGAL DATA ADDRESS 0x02 Request or modification of the data in unused address ILLEGAL DATA VALUE 0x03 When trying to modify data to a value out of the allowable range SLAVE DEVICE FAI...

Страница 19: ...h is implemented with the CIP Common Industrial Protocol specified by the ODVA using TCP and UDP Originator the device which is requesting connection Also called client The device can be PLC or Scanne...

Страница 20: ...rget with Input Instance and Output Instance at preset period Class 1 connection will be implemented Supported range Transport Type Originator Target Point to Point Target Originator Multicast Transpo...

Страница 21: ...d Actual Low Byte RPM unit 3 Speed Actual High Byte RPM unit 110 0 Running1 Fwd Faulted 1 2 Speed Actual Low Byte Hz unit Note 1 3 Speed Actual High Byte Hz unit 111 0 At Reference Ref From Net Ctrl F...

Страница 22: ...Byte 145 0 Status Parameter 1 data Low Byte 1 Status Parameter 1 data Hi Byte 2 Status Parameter 2 data Low Byte 3 Status Parameter 2 data Hi Byte 4 Status Parameter 3 data Low Byte 5 Status Paramete...

Страница 23: ...yte 10 Status Parameter 6 data Low Byte 11 Status Parameter 6 data Hi Byte 12 Status Parameter 7 data Low Byte 13 Status Parameter 7 data Hi Byte 148 0 Status Parameter 1 data Low Byte 1 Status Parame...

Страница 24: ...rter Error 0x29 10 Warning Not Supported 0x29 11 Running1 Motor is running Forward 0x29 7 Running2 Motor is running Reverse 0x29 8 Ready Motor is ready to running 0x29 9 Ctrl From Net Run Stop control...

Страница 25: ...ef Note 2 NetCtrl Note2 Fault Reset Run Rev Run Fwd 1 0 2 Speed Reference Low Byte RPM unit 3 Speed Reference High Byte RPM unit 100 0 Fault Reset Run Fwd 1 0 2 Speed Reference Low Byte Hz unit 3 Spee...

Страница 26: ...ameter 2 data Hi Byte 4 Control Parameter 3 data Low Byte 5 Control Parameter 3 data Hi Byte 6 Control Parameter 4 data Low Byte 7 Control Parameter 4 data Hi Byte 125 0 Control Parameter 1 data Low B...

Страница 27: ...te 5 Control Parameter 3 data Hi Byte 6 Control Parameter 4 data Low Byte 7 Control Parameter 4 data Hi Byte 8 Control Parameter 5 data Low Byte 9 Control Parameter 5 data Hi Byte 10 Control Parameter...

Страница 28: ...1 Fault Reset Command 0x29 12 NetRef Note2 Not used 0x2A 4 NetCtrl Note2 Not used 0x29 5 Speed Reference Speed Command 0x2A 8 Note1 See the Drive Run and Fault sections in the Control Supervisor Objec...

Страница 29: ...tus Word Note3 6 Get Serial Number Double Word Note4 7 Get Product Name 12 Byte IS7 Ethernet Note1 Product Code 11 designates the iS7 Inverter Note2 Revision agrees with the version of the Ethernet co...

Страница 30: ...ault when the Inverter is in Warning status 9 Minor Unrecoverable Fault N A 10 Major Recoverable Fault when the Inverter is H W tripped 11 Major Unrecoverable Fault when the Inverter is tripped exclud...

Страница 31: ...onous Motor 5 Switched Reluctance Motor 6 Wound Rotor Induction Motor 7 Squirrel Cage Induction Motor 8 Stepper Motor 9 Sinusoidal PM BL Motor 10 Trapezoidal PM BL Motor 6 Get Set Motor Rated Curr 0 0...

Страница 32: ...0 Stop Operation in normal direction Note1 1 4 Get Set Reverse Run Cmd 0 Stop Operation in reverse direction Note1 1 5 N A Net Control Can be set up as Inverter parameter only 6 Get Drive State 0 Ven...

Страница 33: ...Set Drive Fault Reset 0 Trip Reset after a trip Reset can be done only when TRUE is inputted in FALSE status Note2 1 13 Get Drive Fault Code See the Drive Fault Code Table below Note2 14 Get Control F...

Страница 34: ...Inverter is tripped the Drive Fault becomes TRUE At this time the Drive Fault Codes are as follow Drive Fault Code Fault Code Number Description 0x0000 None 0x1000 Ethermal Out Phase Open InverterOLT...

Страница 35: ...Support for Instance 0x0E Get Attribute Single No Yes 0x10 Set Attribute Single No Yes AC Drive Object Class 0x2A Instance 1 Attribute Attribute ID Access Attribute Name Range Definition 3 Get At Ref...

Страница 36: ...tual Hz 0 400 00 Hz Monitors present operating frequency by Hz unit 101 Get Set Reference Hz 0 400 00 Hz When the DRV 07 Freq Ref Src is set to 8 FieldBus the reference frequency can be set up through...

Страница 37: ...bute Instance Access Attribute Number Attribute Name Attribute Value 1 DRV Group Get Set Identical to iS7 Manual Code No iS7 Keypad Title Refer to iS7 Manual Setting range of iS7 Parameter Refer to iS...

Страница 38: ...n None Maintains the previous status Free Run Lost Command Trip occurs and Free Run stopped Dec Lost Command Trip occurs and stops by Trip deceleration time Hold Input Lost Command Warning occurs and...

Страница 39: ...t Protocol Ref 4 Appearance and Installation of Ethernet Option 1 Ethernet Communication Status LED 2 Modbus TCP LED and Troubleshooting LED Color Function and Troubleshooting LED1 CPU Green Flashing...

Страница 40: ...stall the Option ERROR flashes at longer intervals than that of the CPU IP conflicts with another device having the same IP in the Network Check and set the IP again 3 Ethernet IP LED and Troubleshoot...

Страница 41: ...set to 0x00 0x00 0x00 0x00 or 0xFF 0xFF 0xFF 0xFF Since 0 0 0 0 and 255 255 255 255 are special IPs it is recommended not to use them Flashing Ethernet has lost communication with the Option Reinstall...

Отзывы: