199
Learning Advanced Features
This function is used to prevent pump damage due to abrupt deceleration. When the pump
operation frequency reaches the valve ramp frequency (
AP2-38 Dec Valve Freq) while
decelerating rapidly based on the deceleration ramp time (set at AP2-42), it begins to slow
down the deceleration based on the deceleration valve ramp time (set at
AP2-39
DecValve
Time).
Decelerating valve ramp operates when ADV-
24 (Freq Limit) is set to ‘1 (Yes)’.
Deceleration Valve Ramping Setting Details
The time set at AP2-39 refers to the absolute time that it takes for the pump to decelerate
from the frequency set at AP2-38 to the frequency limit set at ADV-25.
5.17 Load Tuning
Load tuning refers to an operation that detects the load applied to a specific section of the
inverter operation (current and voltage) and creates an ideal load curve for the under load
and pump clean operations. The two set points to define the section are user-definable, and
are set at 50% and 85% of the base frequency (DRV-18 Base Freq) by default. The load
tuning result values are saved at codes AP2-2
–AP2-10. These values are user definable as
ADV
24
Frequency limit
options
Limit Mode
0: No
0
No
-
1
Yes
25
Low Freq minimum
value
Freq Limit
Lo
30.00
Start Freq
–
Max Freq
Hz
26
Low Freq maximum
value
Freq Limit
Hi
60.00
Freq Limit Lo
–
Max Freq
Hz
Code
Description
AP2-38 Dec
Valve Freq
Sets the start frequency where the slow deceleration begins in order to
prevent pump damage when the inverter stops. Decelerating valve
ramping is performed from the frequency set at AP2-38 to the frequency
limit set at ADV-25 (low frequency limit for pump operation).
AP2-39
DecValve Time
Sets the time it takes to decelerate from the frequency set at AP2-38 to the
frequency limit set at ADV-25 (low frequency limit for pump operation).
Содержание LSLV-H100 Series
Страница 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Страница 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Страница 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Страница 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Страница 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Страница 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Страница 35: ...Installing the Inverter 22 ...
Страница 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Страница 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Страница 181: ...168 Learning Advanced Features PID Command Block ...
Страница 182: ...169 Learning Advanced Features ...
Страница 183: ...170 Learning Advanced Features PID Feedback Block ...
Страница 184: ...171 Learning Advanced Features PID Output Block ...
Страница 185: ...172 Learning Advanced Features PID Output Mode Block ...
Страница 198: ...185 Learning Advanced Features EPID1 Control block ...
Страница 199: ...186 Learning Advanced Features EPID2 Control block ...
Страница 220: ...207 Learning Advanced Features ...
Страница 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Страница 506: ...Table of Functions 493 ...
Страница 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Страница 549: ...Troubleshooting 536 ...
Страница 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Страница 570: ...Technical Specification 557 110 185 kW 3 phase ...
Страница 601: ...588 ...
Страница 602: ...589 ...
Страница 603: ...590 ...