143
Learning Advanced Features
5.1 Operating with Auxiliary References
Frequency references can be configured with various calculated conditions that use the
main and auxiliary frequency references simultaneously. The main frequency reference is
used as the operating frequency, while auxiliary references are used to modify and fine-tune
the main reference.
Group Code LCD Display
LCD Display Parameter Setting
Setting Range Unit
DRV
06
Frequency
reference source
Freq Ref
Src
0
Keypad-1 0
–11
-
BAS
01
Auxiliary frequency
reference source
Aux Ref Src 1
V1
0
–13
-
02
Auxiliary frequency
reference
calculation type
Aux Calc
Type
0
M+(G*A)
0
–7
-
03
Auxiliary frequency
reference gain
Aux Ref
Gain
100.0
100.0
-200.0
–200.0 %
IN
65
–
71
Px terminal
configuration
Px Define
36
dis Aux
Ref
0
–55
-
The table above lists the available calculated conditions for the main and auxiliary
frequency references. Refer to the table to see how the calculations apply to an example
where the DRV-
06 Frq Src code has been set to ‘0 (Keypad-1)’, and the inverter is
operating at a main reference frequency of 30.00 Hz. Signals at -10 to +10 V are received
at terminal V1, with the reference gain set at 5%. In this example, the resulting frequency
reference is fine-tuned within the range of 27.00
–33.00 Hz [Codes IN-01–16 must be set to
the default values, and IN-
06 (V1 Polarity), set to ‘1 (Bipolar)’].
Auxiliary Reference Setting Details
Содержание LSLV-H100 Series
Страница 17: ...Preparing the Installation 4 37 90 kW 3 Phase ...
Страница 18: ...Preparing the Installation 5 110 132 kW 3 Phase ...
Страница 19: ...Preparing the Installation 6 160 185 kW 3 Phase ...
Страница 20: ...Preparing the Installation 7 220 250 kW 3 Phase ...
Страница 21: ...Preparing the Installation 8 315 400 kW 3 Phase ...
Страница 22: ...Preparing the Installation 9 500 kW 3 Phase ...
Страница 35: ...Installing the Inverter 22 ...
Страница 50: ...37 Installing the Inverter Input and Output Control Terminal Block Wiring Diagram ...
Страница 104: ...91 Learning Basic Features 0 10 V Input Voltage Setting Details V1 Quantizing ...
Страница 181: ...168 Learning Advanced Features PID Command Block ...
Страница 182: ...169 Learning Advanced Features ...
Страница 183: ...170 Learning Advanced Features PID Feedback Block ...
Страница 184: ...171 Learning Advanced Features PID Output Block ...
Страница 185: ...172 Learning Advanced Features PID Output Mode Block ...
Страница 198: ...185 Learning Advanced Features EPID1 Control block ...
Страница 199: ...186 Learning Advanced Features EPID2 Control block ...
Страница 220: ...207 Learning Advanced Features ...
Страница 235: ...222 Learning Advanced Features The Time Chart for the Exception Day ...
Страница 506: ...Table of Functions 493 ...
Страница 520: ...Table of Functions 507 8 16 4 Cooling Tower MC4 Group ...
Страница 549: ...Troubleshooting 536 ...
Страница 569: ...Technical Specification 556 11 3 External Dimensions 0 75 30 kW 3 phase 37 90 kW 3 phase ...
Страница 570: ...Technical Specification 557 110 185 kW 3 phase ...
Страница 601: ...588 ...
Страница 602: ...589 ...
Страница 603: ...590 ...