Profile
36
▶
vl velocity Quick Stop (Object :0x604A)
This object sets the Quick Stop time.
As shown in the following figure, this object determines the Quick Stop deceleration
time with a combination of the Delta Speed and Delta Time.
The Delta Speed is fixed to the maximum speed to maintain stable inverter operation.
Index
Sub-index
Name
Type
Property
Unit
Range
0x604A
VI velocity quick stop
-
-
-
-
0
Number of
entries
U8
RO
-
-
2
Delta Time
U16
RW
sec
0.0~600.0
6.1.3 SDO for G100 Inverter Operation
▶
Common Area SDO Address
•
Inverter Monitoring Area
The inverter monitoring area refers to the read-only common area parameters
between the communication addresses 0h300
–0h37F.
In CANopen communication, the index value is "0x4000" and the sub-index
value is "communication address - 0h300 + 1."
Ex.) If the value at communication address "0h0310" has to be read, the index
is "0x4000" and the sub-index is "0x11" for the data.