6 Technical specifications
Power supply
:
230V AC +10% -10%, 50Hz (Kl21, 22, 23)
Power consumption
:
Max 15VA
Mains fuse
:
13A
Enclosure :
IP 54
Dimensions (hxbxd)
:
120 x 170 x 60 mm
Weight
:
620g
Op. temperature
:
-20 - 50
C, Display 0 - 50
C
PG cable glands
:
1 pcs. PG13,5 and 4 pcs. PG7
Alarm relay
:
250VAC, 8A AC1. (Cl18, 19, 20)
Motor relay
:
250VAC, 3A AC1. (Cl16, 17)
Motor error input
:
Pull-down input, broken = error. (Cl14, 15)
0-10VDC out to motor :
0-10VDC 8bit. Max 20mA. (Cl12, 13)
On/off input
:
Pull-down input, broken = off. (Cl10, 11)
Full speed input
:
Pull-down input, shortened = Fullsp. (Cl8, 9)
Pressure input
:
0-10VDC in, 4,7Kohm, 10bit. (Cl7, 5)
+24VDC supply
:
+24VDC out, +50%, -20%, Max 80mA. (Cl6, 7)
NTC temperature sensor:
22Kohm NTC, +/- 0,5
C, -40 to 60
C
Max. 20 meters cable not shielded. (Cl3, 4)
Night set-back input
:
Pull-down input, shortened = night. (C1, 2)
Pres. transducer ES11 :
0-500Pa, 15VDC to 38VDC, 15VAC to 28VAC, 20mA
IP54, op. Temp -20 - 50
C
Max 40 meters cable between ES10 and ES11.
3x0.25 mm2 cable.
Day setpoint
:
0-5000Pa or 0,00-50,00m/s
Night setpoint
:
0-5000Pa or 0,00-50,00m/s
Full speed setpoint
:
0-5000Pa or 0,00-50,00m/s