ES 10 

 

Constant pressure or 

flow regulator 

 
 
 

 

Содержание ES 10

Страница 1: ...Industrivej 12 Gelsted DK 4160 Herlufmagle Tel 45 5550 5550 Fax 45 5550 2265 www lscontrol dk lsc lscontrol dk ES 10 Constant pressure or flow regulator ...

Страница 2: ... 3 3 Functions 4 3 1 Main menu 4 3 2 Setpoint menu 4 3 4 Alarm control 5 3 5 Outdoor temperature compensation 7 4 Setpoint menu table 9 5 Mounting 10 6 Technical specifications 11 7 Product codes 12 8 Applicable standards 12 9 Document versions 12 ...

Страница 3: ...3 different operation modes and related setpoints are available day operation mode night operation mode and max operation mode The ES10 may be equipped with a temperature sensor for outdoor temperature compensation The ES10 is compatible with all pressure and flow sensors with a 0 10VDC output signal As standard the ES10 is equipped with a voltage free contact for connection to the BMS system or o...

Страница 4: ...ired The display shows MENU enter passw Use arrow up and arrow down to select the first numbers in the password and the enter button to continue to the next figure When the figure has been entered press the enter button to access the setpoint menu The password is 1234 The first line in the display will show Edit setp no 1 Edit setpoint The individual setpoint number is selected by pressing arrow u...

Страница 5: ...justment mode or from 0 00m s to 50 00m s in air flow adjustment mode The motor relay cl16 17 is closed and the motor output cl12 13 receives a voltage signal In night mode the alarm surveillance is active See alarm description in section 3 4 4 Max mode The ES10 is adjusting according to the max mode setpoint This is set in setpoint menu no 3 This setpoint is adjustable from 0Pa to 5000Pa in air p...

Страница 6: ...ted in setpoint menu no 5 The time can be set from 0 to 1000 sec If the pressure air flow falls below this treshold again the alarm will automatically be deactivated See example in fig 3 1 3 Pressure air flow alarm below setpoint If the measured pressure flow falls below the desired regulation setpoint less an alarm threshold pressure air flow setpoint alarm threshold the following alarm will be d...

Страница 7: ...to 500Pa or from 0m s to 5 00m s Note that the outdoor temperature compensation only is active in day mode and max mode and not in night mode See fig 3 2 Fig 3 2 3 6 Motor control Connection The ES10 has a 0 10VDC output cl 12 13 for control of a frequency converter or a triac controller Furthermore the ES10 has a operation relay cl 16 17 which will be closed when the unit is in day night or max m...

Страница 8: ...11 is used it is not necessary to adjust the setpoints concerning the pressure sensor as these have been set at the factory The measuring range of the ES11 is 0Pa to 500Pa Other transducers If a different air pressure or air flow transducer is chosen the setpoint menu no 12 and no 13 are to be set In setpoint menu no 12 the pressure or airflow which the chosen sensor measures is adjusted when the ...

Страница 9: ...00m s 1000Pa 10 00m s 100Pa 1 00m s 5 Time delay alarm Time delay for pressure flow before alarm is activated 0sek 1000sek 300sek 6 Temp comp Outdoor temperature compensation OFF or ON 0 OFF 1 ON 0 OFF 7 Temp comp max Max temperature when compensation is activated 10 0 C 15 0 C 5 0 C 8 Temp comp min Min temperature when compensation is at max 25 0 C 0 0 C 10 0 C 9 Temp pres reduce Temp flow reduce...

Страница 10: ...mounting according to applicable mounting regulations The ES10 is to mounted on a flat and stable surface on which the ES10 is fixed with screws in the 4 corner holes The ES10 is not to be mounted on moving or vibrating surfaces Cables are run through cable gland and tightened Accessory The ES11 pressure transduer is to be mounted according to applicable regulations The ES11 must be mounted on a f...

Страница 11: ...0mA Cl12 13 On off input Pull down input broken off Cl10 11 Full speed input Pull down input shortened Fullsp Cl8 9 Pressure input 0 10VDC in 4 7Kohm 10bit Cl7 5 24VDC supply 24VDC out 50 20 Max 80mA Cl6 7 NTC temperature sensor 22Kohm NTC 0 5 C 40 to 60 C Max 20 meters cable not shielded Cl3 4 Night set back input Pull down input shortened night C1 2 Pres transducer ES11 0 500Pa 15VDC to 38VDC 15...

Страница 12: ...30 Accessory ES11 pressure transducer 0 500Pa Product code 40740 8 Applicable standards EN 61000 6 1 and EN 61000 6 2 Electromagnetic Compatability EMC EN 60 60730 1 The Low Voltage Directive 9 Document versions Ver 0 4 26 9 2006 MJ Ver 1 0 JEH 13 04 2011 Ver 1 1 JEH 14 01 2016 ...