5 Quick-Start Guide
This chapter provides the minimum list of steps necessary to setup the LIP-ME20X.
5.1 Hardware Installation and IP Connection
Connect power, Ethernet, and MS/TP (Section 6.6).
The device is shipped with DHCP. The IP address is displayed on the LCD display.
If a static IP configuration is required, configure the IP address using the jog dial on the
LCD display (Section 5.2.2).
Reboot the LIP-ME20X to commit the new IP settings.
5.2 Configuration of the LIP-ME20X
5.2.1 Configuration on the Web Interface
Connect to the LIP-ME20X using the IP address displayed on the LCD in a Web
browser.
Click on
Config
and enter the administrator and operator passwords on first contact.
This is required before proceeding with configuration on the Web UI.
Click on
BACnet Config
and setup the BACnet Device Configuration (see Section
3.2.17 BACnet Configuration in the LOYTEC Device User Manual [1]).
Click on
Port Config
and setup the BACnet/IP and BACnet MS/TP port configuration
(see Section 3.2.18 BACnet/IP Configuration and Section 3.2.20 BACnet MS/TP
Configuration in the LOYTEC Device User Manual [1]). Make sure to set distinct
network numbers, which is required by the router to operate.
If the LIP-ME20X should also act as a BBMD, click on
BACnet BDT
and setup the
Broadcast Distribution Table (see Section 3.2.24 BACnet BDT Configuration in the
LOYTEC Device User Manual [1]).
Reboot the LIP-ME20X to commit the changes.
5.2.2 Configuration on the LCD Display
Device models with an LCD display can also be configured to their basic settings through
jog dial navigation on the LCD UI. Turn the jog dial to navigate between menu items and
Содержание LIP-ME20X