To Create an External NV manually
1.
Select the L-Proxy/CEA-709 Port/Datapoints folder
2.
Right-click in the data point list and select
New Datapoint…
in the context menu.
This opens the NV creation dialog.
3.
Click on the tab
External
as shown in Figure 110.
Figure 110: Create a new external NV.
4.
Select the device in the box
Select a Device
on the left-hand side.
5.
Enter the properties of the external NV on that device, starting with the local data point
name, the remote programmatic NV name, the NV type (SNVT) and direction. Note,
that the direction is the direction of the external NV on the L-Proxy. Therefore, the
remote output NV nvo00_switch becomes an input on the L-Proxy. Also enter the NV
selector in hexadecimal and the NV index in decimal notation. Choose the preferred
addressing mode, e.g., Node ID.
6.
Click
Create External NV
to add this NV to the data point list.
7.
The external NV now appears in the data point list as shown in Figure 111. For
external NVs which are inputs to the L-Proxy, adapt the poll cycle property to your
needs.