![LOYTEC L-DALI Скачать руководство пользователя страница 87](http://html1.mh-extra.com/html/loytec/l-dali/l-dali_user-manual_1943336087.webp)
L-DALI User Manual
87
LOYTEC
Version 5.2
LOYTEC electronics GmbH
Function
Description
switch is changed.
Recall scene
Recall the scene configured with argument 1.
Recall scene (toggle)
Toggle between recalling scene configured with argument 1
and scene configured with argument 2 whenever button is
pressed or switch is changed.
Colour warmer
Ramp up colour temperature as long as button is pressed.
Note: Requires ballasts of type colour control (device type 8)
supporting the colour type colour temperature.
Colour cooler
Ramp down colour temperature as long as button is pressed.
Note: Requires ballasts of type colour control (device type 8)
supporting the colour type colour temperature.
Table 11: DALI button functions
5.3.4.8 Emergency Light Auto-Test Configuration
To configure the test calendar for the automatic function and duration tests of self-contained
emergency lights supporting this function check the box at the right of the devices row of
the DALI Installation page, choose
Emergency Light: Configure Test
from the
Action on
Selected
drop-down box and click on the
Execute
button. Now the L-DALI will read the
currently configured test calendar from the selected devices. When done it will show a page
similar to the one shown in Figure 83.
Figure 83: Emergency Light Auto-Test Configuration
For both tests – function and duration test – a test interval in days and the time and date of
the next execution of the test can be specified. Click
Save
to store the new values in the
devices selected by the check box at the right of the devices row.