background image

loxone.com

FUNCTIONALITY TEST

SILENCE ALARM

OPERATING AND ALARM SIGNALS

BATTERY REPLACEMENT

Visual inspection:

Check the flue inlet openings for coarse dirt, and the detector

for signs of mechanical damage.

Functionality test by pressing the test button:

(Successful functionality test) if you hear a beep - the detector

works correctly!

No beep - the detector is not functional.

In case of accidental triggering, the alarm can be silenced

by pressing the test button. After 10 minutes the detector will

return to normal operation.

We recommend using a lithium battery.

Remove the detector by rotating it anti-clockwise from the

base.

Insert the new battery into the battery compartment.

Put the detector on the base and lock by rotating clockwise.

Carry out a functionality test.

Function / behaviour

Sound signal

Red LED signal

Normal operation

No sound

Flashes every 40 seconds

Alarm status

Lound beep at 0.5 second intervals

2 flashes every second

Fault/pollution

3 short beeps every 40 seconds

LED off

Low battery

One short beep every 40 seconds

Flashes every 40 seconds with beeps

Alarm silenced

No sound

Flashes every 10 seconds

Alarm memory active, i.e. detector has 

been triggered in the last 24 hours

No sound

Flashes every 43 seconds 3 times

Funtionality test

Loud beep

2 flashes every second until test button 

pressed