SECTION 8: MAINTENANCE
WASHING OF HEAT ExCHANGER
- Intercept the flow and close the ball valves ref.
C
(AFS) e
D
(DHW)
- Introduce the fluid from the valve ref.
D1
- Spill the fluid from the valve ref.
C1
for the necessary flushing
time.
DCW inlet
DHW outlet
C
D
C1
D1
SECTION 9: COMPONENTS
Vortex Flowsensor is a combined flow rate/temperature gauge projected for high volume water production. It
is made of composite material, while the sensor is made of a silicone base realised with MEMS technology.
The gauge is corrosion resistant.
Measuring range 5-100 l/min / 0-100 °C
Immediate time response < 1 s
Maximum pressure > 16 bar
Temperature/flow rate gauge VORTEX FLOWSENSOR (VFS) 5 - 100 l/min
Primary circuit circulator
High-efficiency circulator of the primary circuit Wilo STRATOS PARA 25/1-11
(Check the characteristic curves of the circulators at page 5)
Electric connection:
- 4 control wires 0-10V and SSM
- 3 power wires 230V/ 50Hz AC
Alimentazione:
Black/brown:
L1, 230V/AC 50-60Hz
Light blue:
N, neutral
Yellow/green:
protective ground
Cavi di controllo:
Brown:
0-10V (signal return)
White:
0-10V (signal)
Blue:
SSM
Black:
SSM
Note: circulator data and values are available on the Wilo manual included in the packaging.
3-port motorised mixing valve, placed in the primary circuit to granted the correct withdrawal of water from the
buffer tank and produced the right flow of DHW in function of the ral request.
Electric actuator rotation time 140 s
Maximum pressure
> 16 bar
Kvs mixing valve: 8,3
Primary circuit 3-way motorised mixing valve
Assembling instrunctions and maintenance