LIMIT THRESHOLD STATUS INDICATION (LIMx)
– If the limit thresholds are enabled (see menu P08), the DME D332 displays the page, with the corresponding status and the format indicated in the figure:
– With limit threshold activated, the word ON flashes, while if it is deactivated the word OFF is constant. If no limit threshold is programmed, dashes are displayed.
ALARM INDICATION
– If alarms are enabled (see menu P09), the DME D332 displays the page, with the corresponding status and the format indicated in the figure:
– With alarm activated, the word ON flashes with the triangle symbol, while if it is not activated the word OFF is constant.
– If no alarm is programmed, dashes are displayed. After about 3 s, the scrolling text of the alarm programmed in parameter P09.n.05 appears.
– With several alarms active, the texts are displayed in succession.
– Dedicated parameter P02.14 for the utility menu can be used to make the display backlighting flash in the event of an alarm to highlight the presence of the fault.
– The alarm reset method depends on parameter P09.n.03. This determines whether it can be automatic, on the disappearance of the alarm conditions, or requires manual intervention through the commands menu
(C.07).
MAIN MENU
To access the main menu:
– Press
and
simultaneously. The main menu is displayed (see figure), with the available options:
•
SET
– Access to the setup menu
•
CMD
– Access to the commands menu
•
PAS
– Password entry
– The selected option flashes. Descriptive text for the selection scrolls in the alphanumeric display.
– If the password needs to be set, the menu opens with the
PAS
option already selected.
– Press
to select the desired option, then
to confirm.
– To return to the measurement display, press
and
simultaneously again.
PARAMETER SETTING (SETUP)
– From the standard measurement display, press
and
simultaneously to call up the main menu, then select SET and press
to access the settings menu.
– The display indicates the first menu level P.01 at the top left of the display, with selection 01 flashing.
– Select the desired menu (P.01, P.02, P.03) using the
buttons. During selection, the alphanumeric display scrolls a brief description of the currently selected menu.
– To exit and return to the measurement display, press
and
simultaneously.
Setup: menu selection