  Code           Description                                                                             Default                                Range

  

P-01

           Password                                                                                 0000                            0000 - 9999

  

P-02

           Programmable limit threshold enable                                       OFF                               OFF - THR

  

P-03

           Threshold measure                                                                    kW                    01=kW -  02=kvar - 03=V

                                                                                                                                        04=A - 05=Hz - 06=kWh Part 07=h

                                                                                                                                                  Part – 08 kW demand

  

P-04

           ON threshold                                                                           100.00                          0.00 – 999.99

  

P-05

           ON delay                                                                                    5 s                             0 – 9999 sec.

  

P-06

           OFF threshold                                                                          50.00                           0.00 – 999.99

  

P-07

           OFF delay                                                                                   5 s                             0 – 9999 sec.

  

P-08

           Hour counter enable                                                                  OFF                             OFF-ON-THR

  

P-09

           Enable demand measures                                                         OFF                                 OFF-ON

  

P-20

           Primary address                                                                        001                                001-250

  

P-21

           Secondary address HIGH                                                       Serial n.                           0000-9999

  

P-22

           Secondary address LOW                                                       Serial n.                           0000-9999

  

P-23

           Serial speed                                                                              2400                                   300

                                                                                                                                                                600

                                                                                                                                                               1200

                                                                                                                                                               2400

                                                                                                                                                               4800

                                                                                                                                                               9600

                                                                                                                                                              19200

                                                                                                                                                              38400

SETUP PARAMETER TABLE

P-01

– If set to 0000 (default) the password protection is disabled.

P-02

– Defines the function of the programmable limit threshold:

OFF

– Programmable threshold disabled.

THR

– The programmable threshold is activated by a maximum or minimum limit, depending on values programmed in P-04 and P-06.

If P-04 > P-06, then the limit threshold activates when the measure defined by P-03 is higher than P-04, end de-activates when its value
becomes less than P-06 (maximum limit with hysteresis). 
If P-04 < P-06, then the limit threshold activates when the measure defined by P-03 is lower than P-04, end activates when its value
becomes higher than P-06 (minimum limit with hysteresis). 

P-03

– Selection of measure to compare with thresholds.

P-04 and P-05

– Threshold and delay for output activation. Note: The measurements are updated every 1 second, that means that the

variability of this delay  is in the range from 0 to + 1 second.

P-06 and P-07

– Threshold and delay for output de-activation.

P-08

– Defines the hor counter operation:

OFF

– hour counter disabled. It is not shown on the display.

ON

– The hour counter is incremented as long as the energy meter is supplied.

THR

– The hour counter is incremented as long as the threshold defined with previous parameter ( P-02, P-03, P-04 e P-05) is active.

P-09

– Enable of calculation and visualization of active energy demand and max demand. 

P-20

– Primary address.

P-21

– Secondary address, first half (4 digits).

P-22

– Secondary address, second half (4 digits). The complete secondary address can be got by concatenating the content of

parameter P-21 with the one of parameter P-22. Example: secondary address 12345678, set P-21=1234 and P-22=5678.  

P-23

– Baud rate.

  Codice        Descrizione                                                                             Default                                Range

  

P-01

           Password                                                                                 0000                            0000 - 9999

  

P-02

           Abilitazione soglia limite programmabile                                   OFF                               OFF - THR

  

P-03

           Misura per soglia                                                                       kW                    01=kW -  02=kvar - 03=V

                                                                                                                                        04=A - 05=Hz - 06=kWh Part 07=h 

                                                                                                                                                  Part – 08 kW demand

  

P-04

           Soglia ON                                                                                100,00                          0,00 – 999,99

  

P-05

           Ritardo soglia ON                                                                    5 sec.                           0 – 9999 sec.

  

P-06

           Soglia OFF                                                                                50,00                           0,00 – 999,99

  

P-07

           Ritardo soglia OFF                                                                   5 sec.                           0 – 9999 sec.

  

P-08

           Abilitazione contaore                                                                 OFF                             OFF-ON-THR

  

P-09

           Abilitazione misure demand                                                      OFF                                 OFF-ON

  

P-20

           Primary address                                                                        001                                001-250

  

P-21

           Secondary address HIGH                                                       Serial n.                           0000-9999

  

P-22

           Secondary address LOW                                                       Serial n.                           0000-9999

  

P-23

           Serial speed                                                                              2400                                   300

                                                                                                                                                                600

                                                                                                                                                               1200

                                                                                                                                                               2400

                                                                                                                                                               4800

                                                                                                                                                               9600

                                                                                                                                                              19200

                                                                                                                                                              38400

TABELLA PARAMETRI DI SETUP

P-01

– Se impostato a 0000 (default) la protezione da password è disabilitata.

P-02

–  Definisce la funzione della soglia limite programmabile:

OFF

– Soglia programmabile disabilitata.

THR

– La soglia programmabile è attivata  massima oppure di minima, a seconda dei valori impostati in P-04 e P-06. 

Se P-04 > P-06, allora la soglia limite si attiva con la misura di P-03 > P-04, e si disattiva quando ritorna ad essere < P-06
(funzione di soglia massima con isteresi).
Se P-04 < P-06, allora la soglia limite si attiva con la misura di P-03 < P-04, e si disattiva quando ritorna ad essere > P-06
(funzione di soglia minima con isteresi).

P-03

– Selezione misura alla quale vengono applicate le soglie.

P-04 e P-05

– Soglia e relativo ritardo per attivazione uscita. Nota: le misure vengono aggiornate ed integrate 1 volta al

secondo, quindi questo ritardo ha una variabilità da 0 a + 1 secondo.

P-06 e P-07

– Come sopra, per disattivazione uscita. 

P-08

– Definisce il funzionamento del contaore:

OFF

– Contaore disabilitato, non viene visualizzato.

ON

– Il contaore si incrementa fintanto che l’energy meter è alimentato.

THR

– Il contaore si incrementa fintanto che la soglia definita con i parametri precedenti ( P-02, P-03, P-04 e P-05) è

attivata.

P-09

– Abilitazione misura e visualizzazione potenza attiva integrata attuale e massima (max demand).

P-20

– Indirizzo primario.

P-21

– Indirizzo secondario, prime 4 cifre.

P-22

– Indirizzo secondario, ultime 4 cifre. L’indirizzo secondario completo si ottiene concatenando il contenuto del

parametro P-21 con quello del parametro P-22.
Esempio: indirizzo secondario 12345678, occorre impostare P-21=1234 e P-22=5678.

P-23

– Velocità.

MECHANICAL DIMENSIONS AND WIRING DIAGRAMS

90

44.7

35.8

43.7

63

5

92.5

M-BUS CONNECTION

DME D122 n°1

Max 1000m

Max 25Ohm - 180pF

DME D122 n°250 *

M1

M2

M2 M1

M-Bus

M-Bus Master

M2

M1

M-Bus

M1

M2

M2 M1

M-Bus

NOTE:
The number of connected devices depends on the Master unit load capacity  

DIMENSIONI MECCANICHE E SCHEMI DI COLLEGAMENTO

CONNESSIONE M-BUS

L

L

M2

N

M1

DME D121

220...240V 50/60Hz
0.5-10 (63)A CI. 1

100...120V 50/60Hz

Energy meter

1000

Imp/kWh

LINE

LOAD

N

N

L

L

Содержание DME D122

Страница 1: ... reactive energy 000000 0 kvarh Part Partial reactive energy 000000 0 V Voltage 000 0 A Current 00 00 kW Active power 00 00 kvar Reactive power 00 00 PF Power factor 0 00 Hz Frequency 00 0 h Hour counter hhhhh mm 00000 00 h Part Partial hour counter hhhhh mm 00000 00 kW d Average active power 15 min demand 00 00 kW d Max avg active power max demand 00 00 Icona Misura Formato kWh Energia attiva tot...

Страница 2: ... 60 consecutive seconds the display goes back automatically to normal operation LOST OR FORGOTTEN PASSWORD If password is lost or forgotten after three consecutive faulty attempts to enter the password the display shows a 6 digit unlock code Please contact LOVATO Electric customer service reporting this unlock code The right password will be provided The user is then free to change setting it as d...

Страница 3: ...FF OFF THR P 03 Misura per soglia kW 01 kW 02 kvar 03 V 04 A 05 Hz 06 kWh Part 07 h Part 08 kW demand P 04 Soglia ON 100 00 0 00 999 99 P 05 Ritardo soglia ON 5 sec 0 9999 sec P 06 Soglia OFF 50 00 0 00 999 99 P 07 Ritardo soglia OFF 5 sec 0 9999 sec P 08 Abilitazione contaore OFF OFF ON THR P 09 Abilitazione misure demand OFF OFF ON P 20 Primary address 001 001 250 P 21 Secondary address HIGH Ser...

Страница 4: ... a class IP51 enclosure or better IEC EN 60529 CARATTERISTICHE TECNICHE Tensione Tensione nominale Us 110 120V 220 240V Limiti di funzionamento 88 132V 187 264V Frequenza nominale 50 60Hz Limiti di funzionamento 45 66Hz Potenza assorbita dissipata 1VA 0 4W Corrente Corrente minima Imin 0 5A Corrente di transizione Itr 1A Corrente di riferimento Iref Ib 10A Corrente massima Imax 63A Corrente di sta...