6.  ADDITIONAL FUNCTIONS

     6.1  Configuration of the relay output function

            To configure the function of the relay output with changeover contact (terminals NO-COM-NC) is necessary to set the parameter P420.01.

     6.2  Configuration of the DO1 digital output function

            To configure the function of the digital output (terminals DO1-GND) is necessary to set the parameter P420.02.

Here below are listed the most common functions.

         Parameter              Function                                                                                                                                  Setting                Description

          P420.01               Relay output function                                                                                                                 50                    Function “running”: the relay switches when the output frequency of the VLA1 is 

                                                                                                                                                                                                                 greater than 0.2Hz.

                                                                                                                                                                                        56                    Function “error active”: the relay switches in case of active error.

                                                                                                                                                                                         70                    Function “frequency threshold exceeded”: the relay switches when the output

                                                                                                                                                                                                                 frequency of the VLA1 is greater than the threshold set in P412.00.

                                                                                                                                                                                         78                    Function “current limit reached”: the relay switches when the motor current is

                                                                                                                                                                                                                 greater or equal to the maximum threshold set in P324.00 (calculated as % of the
                                                                                                                                                                                                                 motor rated current P323.00).

 

 

 

 

 

 

 

Here below are listed the most common functions.

         Parameter              Function                                                                                                                                  Setting                Description

          P420.02               DO1 digital output function                                                                                                         50                    Function “running”: the DO1 output is activated when the output frequency of the 

                                                                                                                                                                                                                  VLA1 is greater than 0.2Hz.

                                                                                                                                                                                         56                    Function “error active”: the DO1 output is activated in case of active error.

                                                                                                                                                                                         70                    Function “frequency threshold exceeded”: the DO1 output is activated when the

                                                                                                                                                                                                                  output frequency of the VLA1 is greater than the threshold set in P412.00.

                                                                                                                                                                                         78                    Function “current limit reached”: the DO1 output is activated when the motor

                                                                                                                                                                                                                  current is greater or equal to the maximum threshold set in P324.00 (calculated 
                                                                                                                                                                                                                  as % of the motor rated current P323.00).

 

 

 

 

 

 

 

N

O

C

OM

NC

G

N

D

AI1

AI

2

A

O1

10

V

24V

DI1

DI2

DI3

DI4

DI

5

DO1

GN
D

100mA max
24VDC

Load

Содержание VLA1 series

Страница 1: ...etpoint adjusted with keypad and feedback signal type 0 10V 7 4 8 PID Control Setpoint adjusted with keypad and feedback signal type 4 20mA 7 5 Motor parameters 8 6 Additional functions 9 6 1 Configur...

Страница 2: ...full keypad control Reversal of rotation direction Example of navigation in the menu of the VSD and modification of a parameter Back to the previous level Back to the previous level Back to the previo...

Страница 3: ...ings follow this procedure Set the parameter P700 01 1 load default settings Press the button several times to exit from the programming menu until it appears the text STOP Keep pressed the button for...

Страница 4: ...P400 02 Run stop command 11 Run stop command from digital input DI1 connected between terminals DI1 24V NO COM NC GND AI1 AI2 AO1 10V 24V DI1 DI2 DI3 DI4 DI5 DO1 GND Parameter Function Setting Descri...

Страница 5: ...deceleration time P430 01 Analog input 1 AI1 configuration 0 Analog signal type 0 10V P430 02 Value of frequency when AI1 is at minimum 0Hz Frequency when AI1 is at minimum AI1 0V P430 03 Value of fr...

Страница 6: ...11 00 Maximum frequency 50Hz Insert the value of the maximum frequency P220 00 Acceleration time 5sec Insert the value of the acceleration time P221 00 Deceleration time 5sec Insert the value of the d...

Страница 7: ...mum frequency P220 00 Acceleration time 5sec Insert the value of the acceleration time P221 00 Deceleration time 5sec Insert the value of the deceleration time P430 01 Analog input 1 AI1 configuration...

Страница 8: ...If you need to enable the sensorless vector control set P300 00 4 All the other parameters must be left to default settings Parameter Function Setting Description P327 04 Automatic motor data identifi...

Страница 9: ...greater than the threshold set in P412 00 78 Function current limit reached the relay switches when the motor current is greater or equal to the maximum threshold set in P324 00 calculated as of the m...

Страница 10: ...ange 0 10VDC correspondent to the output frequency range 0 50Hz Parameter Function Setting Description P440 01 AO1 analog output range 1 0 10VDC P440 02 AO1 analog output function 1 Actual output freq...

Страница 11: ...sensor with output 0 10V correspondent to a pressure of 0 15Bar with a linear characteristic as shown in the following diagram This means that if the output of the sensor is 0V it means a pressure of...

Страница 12: ...210 00 Minimum frequency 0 Hz Insert the value of the minimum frequency P211 00 Maximum frequency 50 Hz Insert the value of the maximum frequency P220 00 Acceleration time 5 sec Insert the value of th...

Страница 13: ...mic performance of the load profile overvoltage display in parameter P208 06 results from the Check mains voltage setting of the rated mains voltage in P208 01 Check settings for the brake energy mana...

Отзывы: